KNX eTR MultiTouch Light/Sunblind push button 1
KNX eTR MultiTouch Light/Sunblind push button • Version: 05.02.2021 • from version 0.1.9 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
EN
KNX eTR MultiTouch Light/Sunblind
Button for light, drive, scenes
and temperature control
Technical specifications and installation instructions
Item numbers 71060 (white), 71062 (black)
1. Description
The KNX eTR MultiTouch Light/Sunblind push button has touch-sensitive but-
tons with which functions can be called up in the KNX building bus system. The
glass surface is printed with areas for setting the light and temperature. Coloured
LEDs (one white LED in the light symbol, one red and one blue LED in the thermo-
meter symbol and three white LEDs each for level indication) are integrated in these
areas and their behaviour can be adjusted. Additionally, there is an area for moving
blinds/sun shades (up/down).
A temperature sensor is integrated into KNX eTR MultiTouch Light/Sunblind.
An external temperature reading can be received via the bus and processed with its
own data to create a total temperature (mixed value).
The KNX eTR MultiTouch Light/Sunblind has a PI controller for heating and co-
oling. The setpoint temperature can be changed using the "+" and "-" touch buttons.
Communication objects can be linked via AND and OR logic gates.
Functions:
•Operating zone for light with 3 areas (switching and dimming)
•Operating zone for blinds, awnings, shutters or windows with 3 areas (up/
down with short/long distinction, driving position)
•Operating zone for temperature control with 3 areas (warmer, cooler,
changeover heating/cooling)
• A total of 9 areas, all of which can be assigned either to the intended bus
functions or to other individual bus functions (switches, changeover
switches, dimmers, blinds, awnings, shutters, windows, 8- or 16-bit encoders,
scene call/saving)
•LEDs can be set. All LEDs Off, all LEDs On, active LEDs Always On, all LEDs
On for specific time after button pressed, active LEDs On for specific time after
button pressed. Settable, as to whether LED flashes at block object value = 1.
LED brightness can be pre-set for day and night
•Area function when touching two or more push buttons. Can be configured
as switch, selector switch, as 8 or 16 bit encoder or for scenario recall
•Scene control. 3 scene channels with 5 objects each
•Temperature measurements. Mixed value from own measured value and
external values (proportion can be set by percentage), output of minimum
and maximum values
•PI-controller for heating (one or two-level) and cooling (one or two-level)
according to temperature. Regulation according to separate setpoints or
basic setpoint temperature
•4 AND and 4 OR logic gates each with 4 inputs. All switching events as
well as 8 logic inputs (in the form of communications objects) can be used as
inputs for the logic gates. The output from each gate can be configured
optionally as 1-bit or 2 x 8-bit
Configuration is made using the KNX software ETS 5. The product file can be dow-
nloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu.
1.0.1. Area function
If the area function in ETS has been activated, another function is available alongsi-
de the regular key functions. This is triggered by touching multiple keys, e.g. if you
touch the sensor with the palm of your hand.
Using the area function
If a key is pressed and another (different) key is touched within 0.2 seconds, the ac-
tion set in the ETS is performed for the area operation (See Fig. 1 a) and b)). The keys
are then blocked for 0.5 seconds.
Using the normal key function
If a key is pressed and no other key is touched within 0.2 seconds, the normal key
function is enabled/provided for 5 seconds (See Fig. 1 c) and d)). This is extended
for 5 seconds with each push of the button.
If the area function in the ETS is disabled, the keys can be used normally at any time.
1.1. Scope of delivery
• Push button with mounting
• 4 screw anchors 4 × 20 mm, 4 flat head screws 3 × 25 mm
1.2. Technical data
The product is compliant with the provisions of EU Directives.
1.2.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter Ins-
tallation position) can be corrected in the ETS in order to ensure the specified accu-
racy of the sensor (offset).
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated by the software.
2. Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is
no longer guaranteed.
The device is only to be used for the intended purpose described in this manual. Any
improper modification or failure to follow the operating instructions voids any and
all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
Casing Genuine glass, plastic
Colours • similar to RAL 9003 signal white
• similar to RAL 9005 deep black
Installation on-wall (directly or with a socket Ø60 mm,
resp. cavity wall socket for hole Ø68 mm)
Degree of protection IP 10
Dimensions housing approx. 81,5 x 81,5 (W x H, mm),
mounting depth approx. 12 mm
Total weight approx. 70 g
Ambient temperature Operating 0…+55°C, storage -30…+85°C
Ambient humidity 5...95% RH, avoid condensation
Operating voltage KNX bus voltage
Bus current max. 15 mA
Data output KNX +/- Bus plug-in terminal
Group addresses max. 254
Allocations max. 254
Communication
objects
199
Temperature measu-
rement range
0…+55°C
Temperature resolu-
tion
0.1°C
Key function readiness
Key function readiness
Fig. 1
0s 0.2s 5.2s
Key Y
Key X
Key X
Design
FunctionY
Key function readiness
Area function
Examples of normal key functions
0.5 s block
Key X
Design
Area function
KeyY
Design
Function X
a)
b)
c)
d)
Key X
KeyY 0.5 s block
Design
Area function
Area function examples
readiness
KNX eTR MultiTouch Light/Sunblind push button 2
KNX eTR MultiTouch Light/Sunblind push button • Version: 05.02.2021 • from version 0.1.9 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.2. Installation location
The KNX eTR MultiTouch Light/Sunblind push button is made for wall moun-
ting. The device can be mounted directly on plaster or on a socket (Ø 60 mm).
May be installed and operated in dry interior rooms only.
Avoid condensation.
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interfe-
rence include:
• Direct sunlight
• Drafts from windows and doors
• Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected
in the ETS in order to ensure the specified accuracy of the sensor (offset).
2.3. Device structure
2.3.1. Casing
2.4. Mounting
Prepare the device
Remove the front panel from the mounting. Release the lock by moving the front pa-
nel a few millimetres upwards. The two parts can then be easily separated (Fig. 4).
Screw the mounting onto the wall or socket. The connecting wires (bus line +/-) are
led through the opening in the mounting.
Installation directly on the wall
The wires are pushed into the connection openings.
Installation on a socket
To avoid falsifying the temperature value, use a wind-proof socket and also seal the
inlet pipes against draughts.
Finish mounting
Snap the front panel into place on the mounting (see Fig. 4): Place it slightly above
the centre position, hook it in and slide it downwards.
3. Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electro-
nics. You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via
the bus.
3.1. Addressing of the device at the bus
The individual address is assigned via the ETS. A button and a control LED are loca-
ted on the unit for this purpose (Fig. 4, No. 8+9).
The programming button is located at the bottom outer side of the front panel of the
device and is recessed. Use a thin object to reach the button, e. g. a 1.5 mm² wire.
The equipment is delivered with the bus address 15.15.255. Another address can be
programmed using the ETS.
When programming mode is active, the programming LED lights up and in addition
the 6 white LEDs for temperature level display and all other active LEDs flash.
4. Maintenance and care
Fingerprints on the glass panel are best removed with a cloth moistened with water
or a microfiber cloth. Do not use an abrasive cleaning agent or aggressive cleansing
agents.
5. Disposal
After use, the device must be disposed of or recycled in accordance with the legal
regulations. Do not dispose of it with the household waste!
Fig. 2 Front
1 "Light" area with 3 touch surfaces
2 "Sun protection/drive" area with 3
touch surfaces
3 "Temperature" area with 3 touch sur-
faces
2
3
1
4
5
6
Fig. 3
Back view with mounting
4/5Screw holes for different sockets. Fas-
tening with 2 screws is sufficient. For
wall mounting, use a fixing material
suitable for the ground!
6 KNX bus terminal +/- for connection
when mounted on a socket
7 Spring-loaded terminals KNX bus for
mounting directly on the wall
4
44
55
5
7
Fig. 4
Back view without mounting
6 KNX bus terminal +/- for connection
when mounted on a socket
7 Spring-loaded terminals KNX bus for
mounting directly on the wall
8 Programming button (recessed) for
teaching device
9 Programming LED
10 Temperature sensor
PRG key is accessible from below/outside
when the device is mounted (see chapter
Addressing the device).
6 87 109
Fig. 5 Locking of front panel and mounting
Remove the red-black KNX bus terminal, it
is not required.
Connect the bus +/- connecting wires to the
spring-loaded terminals on the front panel.
Fig. 6 Spring-loaded terminals
To pull it out, press the spring down, e.g.
with a screwdriver.
If there is a cavity behind the device, e.g.
when using a socket, you can use the red/
black KNX bus terminal for connection.
PRG
Fig. 7
View from bottom
Temperature sensor

This manual suits for next models

1

Other KNX Security Sensor manuals

KNX GIRA User manual

KNX

KNX GIRA User manual

KNX DM KNT 002 User manual

KNX

KNX DM KNT 002 User manual

Popular Security Sensor manuals by other brands

Velleman BDET1 Firmware update

Velleman

Velleman BDET1 Firmware update

Bosch D-tect 150 SV Professional Original instructions

Bosch

Bosch D-tect 150 SV Professional Original instructions

CP EBDHS-PRM-LT30 Product guide

CP

CP EBDHS-PRM-LT30 Product guide

First Alert PIR 720 user manual

First Alert

First Alert PIR 720 user manual

AZ 7201 operating instructions

AZ

AZ 7201 operating instructions

Lutron Electronics LOS-W Series installation instructions

Lutron Electronics

Lutron Electronics LOS-W Series installation instructions

Trust SECURITY PLUS-LINE ALMST-2000 user manual

Trust

Trust SECURITY PLUS-LINE ALMST-2000 user manual

EnOcean O2LINE 10020051 Installation and operating manual

EnOcean

EnOcean O2LINE 10020051 Installation and operating manual

Surface Concept HVPS manual

Surface Concept

Surface Concept HVPS manual

Tecnoalarm TWINTEC 18 quick start guide

Tecnoalarm

Tecnoalarm TWINTEC 18 quick start guide

Teledyne 2240 manual 

Teledyne

Teledyne 2240 manual 

Pilz PSEN ml s 1.1 operating manual

Pilz

Pilz PSEN ml s 1.1 operating manual

Depot BST-HVD21 Operator's manual

Depot

Depot BST-HVD21 Operator's manual

MSA SingleLine SCOUT operating manual

MSA

MSA SingleLine SCOUT operating manual

Visonic Vi-motion installation instructions

Visonic

Visonic Vi-motion installation instructions

Zennio Presentia C v2 manual

Zennio

Zennio Presentia C v2 manual

Eagle L112F manual

Eagle

Eagle L112F manual

Servodan niko 41-700 user manual

Servodan

Servodan niko 41-700 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.