Installation and Maintenance Service Manual
Besides preventive maintenance inspection, the following operations should be performed:
1. Rotary Heat Exchanger Check. Inspection of the rotary heat exchanger is performed once per year. Free
rotation of the rotary heat exchanger, continuity of the rotating belt, absence of damages of the rotor drums
and the seal gasket are checked. It is necessary to check the stretch of belt. Free belt will slide and the
efciency of rotary heat exchanger will fall down. To reach maximal efciency, rotor must turn at least 8
times per minute. Polluted heat exchanger will decrease efciency. Clean heat exchanger with an air blast
or wash with tepid water. Check out water falling on the electric motor.
Heat Exchanger Washing. If rotor cleaning by compressed air is not effective, it can be washed with soap-
suds (11 Picture), or if needed – use degreasing soak for metal (aluminum) cleaning. Check out water falling
on the rotor’s electric motor and other automatics’ elements. In case if water got into details, they must be
urgently dry up. Leave rotor to dry in a warm place. Rotor can be connected only when it is absolutely dry.
Heat Exchanger Washing
2. Fans Check (once per year). Polluted fans decrease efciency.
Before performing any inspection work, check whether the unit is switched off from the
electric power supply.
Fans should be carefully cleaned with textile or soft brush. Do not use water. Do not break balance. Check
if direction of fan turns is right, because wrong direction of turns gives only 30% of rating. Check if fan freely
rotates and is not mechanically damaged, if impeller does not touch suction nozzles, fan does not spread
noise, the pressure tubes are connected to the nozzle (if required), mounting bolts are screwed.
3. Air heater check. Recommended to perform periodical inspection and cleaning of heater. Check the
plates of water air heater. The air heater is cleaned with hoover from supply air side or with air blast from
exhaust air side. If it is very dirty, wash with tepid water, which will not make corrosion of aluminium. Check
if position of return water temperature sensor is right. Check if electric air heater is properly xed, wires
connections are not damaged and heating elements are not bent. They can be damaged or bent due to
uneven heat or uneven and turbulent air direction. Check if electric air heater is clear of unnecessary
things and heating elements are not clogged, because this can cause unpleasant smell or in the worst
case – dust can start burning. Air ow through the air heater should be greater than 1,5 m/s. Heating
elements can be cleaned with hoover or wet textile.
4. Air Filter Clogging Check. Change air lters when air lter clogging is indicated. We recommend to
change lters at least twice per year: before and after heating season, or more*. If air handling unit is work-
ing in small speed, the lters must be checked on unit maximum speed. Filters are one time used. We do
not recommend cleaning them. Stop the air handling unit before changing lters.
* Clogged lters unbalance ventilation system, air handling unit uses more power.