fault outside sensor 15°C 15°C
E03+E04 fault room sensor air duct sensor 22°C
E09+E10 fault air duct sensor room sensor 22°C
5. Maintenance / Service
Please arrange regular dates for maintenance works and services with a KONVEKTA service sta-
tion, as indicated in maintenance schedule bus no.: WP07050618.
- Only qualified staff is allowed to carry out these works! -
For general instructions on repair– and maintenance works please contact via email:
TKD@konvekta.com
Danger of accidents!
Qualified staff in charge of installation and maintenance have to be trained in accordance with EN
378-Part 4 and (EC) No.307/2008 and must strictly follow the legal provisions.
Any works or modifications at the air conditioner which are carried out improperly can lead to mal-
function and so endanger operational reliability. We recommend having all works and
modifications
carried out at an authorized KONVEKTA Service Station.
Before carrying out any maintenance works at your air conditioning unit, carefully read the
KONVEKTA safety provisions (TD00052A
) in order to avoid any dangers and accidents!
On our website www.konvekta.com in category >service< you will find a survey of contact details of all our service part-
ners close to your location
Source of supply: KONVEKTA AG, P.O. Box 2280, D-34607 Schwalmstadt
5.1. Troubleshooting
Only qualified staff is allowed to carry out these works!
Trouble Cause Repair by authorized Service Station only
a/c is not
running
thermostat open −check inside temperature
1
−re-adjust thermostat
1
electric connection disconnected −check electric connections at switchboard
relay defective −check relay, replace if necessary
defrost thermostat has switched off −check evaporator blower, replace if necessary
outside temperature too low (possible
icing of evaporator)
−switch on „ventilation“ only
evaporator coil dirty −clean evaporator coil with compressed air
magnetic clutch −check connections at magnetic clutch
compressor does not compress −check high and low pressure, replace compres-
sor if necessary
excess pressure (pressure too high) −check axial fans
−check fuses at switchboard
−clean condenser coil with compressed air
excess pressure caused by high outside
temperature
−run unit until pressure has stabilized
1
leakage in a/c unit, lack of refrigerant −check a/c unit for leakages
−refill refrigerant
low pressure, screen of expansion valve
clogged
−clean screen; replace dryer
Loud noise at
compressor
defective bearing at compressor −replace either bearing or entire compressor
slack V-belt −check V-belt at compressor drive
1
By operator