
6
Fan Coil ECM Control IOM
Program
E. Mode to 2–10 VDC Proportional Control
Analog
Hi/Max
Med
Lo/Min
2-10
O<2
Store
Run
Fxd Spd
0-10
Set
N
O
12345678
E - Mode to 2–10 VDC
Proportional Control
Program
F. Max Speed Adjust
Analog
Hi/Max
Med
Lo/Min
2-10
O<2
Store
Run
Fxd Spd
0-10
Set
N
O
12345678
F - Max Speed Adjust
Program
G. Min Speed Adjust
Analog
Hi/Max
Med
Lo/Min
2-10
O<2
Store
Run
Fxd Spd
0-10
Set
N
O
12345678
G - Min Speed Adjust
Program
H. Normal 2 – 10V DC Speed Control
Analog
Hi/Max
Med
Lo/Min
2-10
O<2
Store
Run
Fxd Spd
0-10
Set
N
O
12345678
H - Normal 2 – 10V DC Speed Control
4. Min Speed Adjust: Set configuration switches to LO/MIN
SPEED balancing mode. (See figure G below.) Switches to
ON-ON-OFF-OFF-ON-ON-OFF-OFF.
• Set switch 1 to ON (Program)
• Set switch 2 to ON (Analog)
• Set switches 3 and 4 to OFF
• Set switch 5 to ON (Lo/min)
• Set switch 6 to ON (2-10 V)
• Set switches 7 and 8 to OFF
• Refer to voltmeter connected to TP1 and TP3. Using
an insulated 1/8” flat bladed screwdriver, adjust speed
potentiometer to desired Min speed airflow.
• STORE: Set switch 8 to Store (ON), wait one second,
then to Set (OFF), to save the value.
5. Resume Normal 2 – 10 V DC Proportional Control:
Set configuration switches to OFF-ONOFF- OFF-OFF-
ON-OFF-OFF for normal proportional speed control, as
shown below in figure H.
• Set switch 2 to ON (Analog)
• Set switch 6 to ON (2 – 10)
• Set all other switches to OFF
2 – 10 VDC PROPORTIONAL MOTOR CONTROL
Speed range adjustment for Proportional Control operation.
Minimum (Min) and maximum (Max) speeds are programmed
at the factory for optimum operation. Changing factory Min
or Max speed defaults will change the motor effective speed
range and invalidate the voltage settings shown on the Fan
Calibration Curve. However, the speed range may still be
adjusted as long as the Min speed remains greater than 70
CFM/kW for units with electric heat.
NOTE: Thermostat must be set for either analog or single
(high) speed operation.
1. Connections. Connect or verify connection of remote
analog signal and common wires to 2-10 VDC Remote
Control Input terminals (refer to Figure 1.)
2. Set Mode to 2 – 10 VDC Proportional Control: Set
configuration switches to 2 – 10 ANALOG programming
mode. (See figure E at right.) Switches to ON-ON-OFF-
OFF-OFF-ON-OFF-OFF.
• Set switch 1 to ON (Program)
• Set switch 2 to ON (Analog)
• Set switches 3 – 5 to OFF
• Set switch 6 to ON (2-10 V)
• Set switches 7 and 8 to OFF
• Press RESET button. (NOTE: RESET button only needs
to be pressed once per programming session unless
board times out. Refer to Status LED.)
• STORE: Set switch 8 to Store (ON), wait one second,
then to Set (OFF), to save the value.
NOTE: If adjusting Min/Max CFM values, continue to step
3. Otherwise, skip to step 5.
3. Max Speed Adjust: Set configuration switches to HI/MAX
SPEED balancing mode. (See figure F at right.) Switches to
ON-ON-ON-OFF-OFF-ON-OFF-OFF.
• Set switch 1 to ON (Program)
• Set switch 2 to ON (Analog)
• Set switch 3 to ON (Hi/Max)
• Set switches 4 and 5 to OFF
• Set switch 6 to ON (2-10 V)
• Set switches 7 and 8 to OFF
• Refer to voltmeter connected to TP1 and TP3. Using
an insulated 1/8” flat bladed screwdriver, adjust speed
potentiometer to desired Max speed airflow.
• STORE: Set switch 8 to Store (ON), wait one second,
then to Set (OFF), to save the value