
SA101NX3-E - 5 / 8 - 07-01-25
CONNECTION OF RELAY UNIT RZ 071-D
The contacts for the terminals 1 to 28 must be connected to [L-] potential. Terminal 29 is provided to be
connected to terminal D+ of the charging dynamo. The "running" signal is active when the voltage exceeds
about 8 volts DC. An AC-dynamo receives the pre-excitation via this terminal.
The functions of several relays may be different, according to their programming. Therefore, the individual
printed status report is valid for a specific control unit.
The stated contact rating of the relays must not be exceeded. Basically is valid, that all operated coils and
inductivities must be provided with reverse diodes (on DC) or with suppressor components matching the
inductivity of the coil.
Terminals 1–14: Input for alarms signals.
Terminal 15: Feed back signal: MAINS IS OFF.
An auxiliary contact (NC) of the mains CB (or contactor) is connected to this terminal. It shows the
position of the breaker. The control unit is fitted with an interlocking circuit which prevents the generator
from switching on as long as the mains is supply on.
Terminal 16: Feed back signal: GENERATOR IS OFF.
An auxiliary contact (NC) of the generator CB (or contactor) is connected to this terminal. It shows the
position of the breaker. The control unit is fitted with an interlocking circuit that prevents the mains from
switching on as long as the generator is supply on.
Terminal 17: Operation mode selection is locked.
The selection of the operation modes by the push-buttons will be locked if a signal is applied at this
terminal. A key-operated switch, to prevent the selected mode from being changed by unauthorised
persons or by mistake, could perform this.
Terminal 18: Remote start with load transfer.
There are two programmable modes for this input: input always active or input only active along with a
mains voltage failure.
If an active command is stated, the start of genset will be initiated and the load will be transferred from
mains to generator supply in the operation mode AUTO.
If the genset is already running in TEST or AUTO mode or was started by the signal REMOTE START
WITHOUT LOAD TRANSFER, the generator will also take over the load.
The load will be switched back to mains supply after the re-connection delay and the genset will be
shutdown (in AUTO) after cooling down period when the signal to this terminal is disconnected (the signal
for REMOTE START WITHOUT LOAD TRANSFER may not be present).
Terminal 19: IMMEDIATE STOP.
The genset will be immediately shut down if a signal is applied to this terminal. The control unit will be
locked for any further starting attempts. To reset the control unit, the operation mode has to be set to OFF.
Resetting is only possible if the signal is no longer connected, otherwise the indicator AUTOMATIC
LOCKED would remain on
Terminal 20: Not used.
This terminal can be used as an alarm input.
Terminal 21: Not used.
This terminal can be used as an alarm input.
Terminal 22: Not used.
This terminal can be used as an alarm input.
Terminal 23: Sprinkler mode.
When a [L-] signal is connected to this terminal the genset starts without changing over to generator
supply and all alarms serve only as a warning ones. If mains fails, the consumers are also switched to
generator supply.
Terminal 24: Start enable input.
Any starting attempt emitted manually or automatically, will be interlocked as long as there is no [L-]
potential connected to terminal no. 24. It is therefore possible to incorporate relevant pre-start conditions
before a signal is given to the starter motor for cranking. If this function is not used, a wire jumper from
[L-] to terminal no. 24 has to be connected.
Changes without further notice reserved.