Kyongbo GD16-L05A User manual

1Class Earth Leakage Detector
User’s manual
TYPE : GD16-L05A
GD16-L05R
2017. 02. 13
Version 1.00
Kyongbo Electric Co., Ltd.

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
2/17 Kyongbo Electric Co., Ltd
This document is for the safety of the user, and to prevent property damage.
Be sure to read the user manual carefully, and use the product accordingly.
The user manual must be kept in a place where it can be easily seen by the product
user.
WARNING
CAUTION
SYMBOLS
Safety Precautions
This symbol indicates the
possibility of death or serious
injury.
This symbol indicates the
possibility of injury or damage
to properties only.
Be sure not to do.
Be sure to follow the instruction.

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
3/17 Kyongbo Electric Co., Ltd
WARNING
• Do not perform any wiring work while the power is on or
the product is in operation.
It may cause an electric shock.
• Must verify the status of the grounding connection before
starting the operation.
Otherwise, it may cause an electric shock, damage, or a fire.
• Do not operate the product with wet hands.
It may cause an electric shock.
• Do not use if the clothing of the cable is damaged.
It may cause an electric shock.
• Do not perform any wiring work when the main cable is live.
It may cause an electric shock, and a damage or a fire by the
charged voltage of the converter.
• Do not disassemble the product even if the power is not
on, except for wiring or maintenance.
It may cause an electric shock by the charged current in the product.
• Let the electrical technician to perform wiring, test run,
and maintenance.
Otherwise, it may cause an electric shock or a fire by a wrongful operation.
• Perform terminal work when cutting a cable.
Otherwise, it may cause an electric shock from the naked part of the cable.
• Place the terminal cover on the terminal in the back after
the wiring work.
Otherwise, it may cause an electric shock.

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
4/17 Kyongbo Electric Co., Ltd
CAUTION
• Apply the rated power to the power source terminal.
Otherwise, it may cause a damage to the product or a fire.
•P+, P-, F.G terminals enclose surge protection circuit inside the
ELD, so do not withstand voltage test.
• Prevent screws, metal parts, water, or oil from entering
the product.
It may cause a damage to the product or a fire.
• Extract and insert Case on a leveled surface.
Otherwise, it may cause a damage to the product.
• Do not store the product in a humid or a dusty area.
It may cause a damage to the product.

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
5/17 Kyongbo Electric Co., Ltd
CONTENTS
1. General Features -------------------------------------------------------------------
2. Technical Data ----------------------------------------------------------------------
2.1 Rated Control Source Voltage ------------------------------------------------
2.2 Rated Frequency ---------------------------------------------------------------
2.3 Output Contacts ----------------------------------------------------------------
2.4 Case------------------------------------------------------------------------------
2.5 Ground Element----------------------------------------------------------------
2.6 Insulation Tests ----------------------------------------------------------------
2.7 Mechanical Tests --------------------------------------------------------------
2.8 Temperature Tests -------------------------------------------------------------
2.9 Other Operating Conditions ------------------------------------------------
2.10 ZCT ----------------------------------------------------------------------------
3. Functional Description --------------------------------------------------------------
3.1 Construction --------------------------------------------------------------------
3.2 Functions ------------------------------------------------------------------------
3.3 Product Structure --------------------------------------------------------------
Appended 1. Dimensioned Drawings ----------------------------------------------
Appended 2. Internal Block Diagram ----------------------------------------------
Appended 3. External Connection --------------------------------------------------
Appended 4. ZCT Dimensioned Drawings ----------------------------------------
6
6
6
6
7
7
7
8
8
8
8
9
10
10
10
11
13
14
15
16

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
6/17 Kyongbo Electric Co., Ltd
1. General Features
This Earth Leakage Detector (GD16-L05A, GD16-L05R) is used protect to leakage fault of
less than AC600V line.
Operation produces earth fault to ZCT Primary line flowing earth current do detection through
ZCT and is digital arithmetic type earth leakage detector that is used to check fault's extension
breeding alarm.
Features
16 Circuit Digital Total arithmetric type Earth Leakage Detector
The Earth Leakage Detector and ZCT are convenient handling through compatibility.
Display the measured values and leakage line ( 7-Segment )
Each circuit setting : Current detect sensitivity
Malfunction Prevented through over input protection and filter circuit
Inspect the equipment of leakage circuit conveniently, because can be select the restore
method.
Can control for more Buzzer installation or Display through output contact.
(GD16-L05R Type only)
Convenience of the ZCT selection by various ZCT types for equipment capacity
Enhanced EMC / EMI performance.
Non Drawing - out Type
2. Technical Data
2.1 Rated Voltage & Current
AC/DC 110~ 220V, 20VA
2.2 Rated Frequency
60Hz (Sine Waveform)

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
7/17 Kyongbo Electric Co., Ltd
2.3 Output Contacts
Signal contacts (Ta, Tc)
Continuous Flow
Electricity Capacity 10A at AC 250V
Closing Capacity 1200VA
Material Silver Alloy
Trip contacts (1a ~ 16a)
Continuous Flow
Electricity Capacity 5A at AC 250V
Closing Capacity 750VA
Material Gold-clad Silver Alloy
Trip contacts (1a~16a) is only GD16-L05R Type
2.4 Case
Structure Non Drawing-out Type
Color Munsell No. N1.5 (black)
Material
ABS Resin
2.5 Ground Element
Operation Current •0.2 - 0.5 - 1A (3 level setting)
•Operation to 53 ~ 75%
Operation Time •Operate within 1.0 sec by 75% nominal operation
current

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
8/17 Kyongbo Electric Co., Ltd
2.6 Insulation Tests
Insulation Resistance Over 5M, 500Vdc
Commercial Frequency
Withstand Voltage 2.2kV, 50/60Hz, 1min
Impulse Withstand
Voltage
6kV, 1.250s
2.7 Mechanical Tests
Vibration
Applying
Status 10~150 ㎐, 0.981 ㎨, axis 3, 1 octave/min, axis per 1
Non
Applying
Statsus
10~150 ㎐, 4.950 ㎨, axis 3, 1 octave/min, axis oper 20
Shock
Applying
Status 500g, 15 Times
Non
Applying
Statsus
50g(Shock acceleration), 5 times, In any direction
2.8 Temperature Tests
Temperature Range -10 oC ~ +50 oC
2.9 Other Operating Conditions
Altitude 1000m or less
Condition where there is no abnormal vibration, shock, slope or influence
of the magnetic field.
Place where there is no explosive dust, flammable dust, or flammable
/ rusty gas, or salt

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
9/17 Kyongbo Electric Co., Ltd
2.10 ZCT Specifications
Type
ZL02 ZL03 ZL05 ZL06 ZL08 ZL10 ZL12 ZL15 ZL20 ZL16 ZL21 ZL26
Cable Winding Type
(The Inside Type)
Bus-Bar Winding
Type
(The Inside Type)
Type
Approval
Number
누변 01-1 누변 01-3 누변 01-2
누변 01-1-1 누변 01-1-2 누변 01-3-1 누변 01-2-1
Rated
primary
current
80A
less
100A
less
250A
less
400A
less
600A
less
800A
less
1000A
less
1500A
less
2000A
less
400A
less
500A
less
600A
less
Bore
(mm) Φ25 Φ30 Φ50 Φ65 Φ80 Φ100 Φ120 Φ150 Φ200 160
×30
210
×30
250
×30
Temp. -10℃~ +60℃
Rated
Output
When Zero sequence primary current 200mA, Rated output voltage is 100mV
(Load Resistance 1.2 ㏀)
Insulation
Resistance Between secondary coil and case, over DC500V, 5 ㏁
Insulation
Withstand
Test
Between secondary coil and case, Input AC2200V, 60Hz, during 1min
Shock
wave
Withstand
voltage
Between primary and case, 1.2 × 50 ㎲, 6kV, positive pole, negative pole each 1times
Vibration 10~150 ㎐, 10 ㎨, axis 3, 1 octave/min, axis per 20
Shock
50g shock, 5times
Steel wire of Length 300mm, Thickness 3mm hang the 1kg pendulum. 15times drop to ZCT
mounting board
Weight(㎏) 0.3 0.4 0.5 0.6 0.8 1.0 1.5 4.5 7.5 2.5 3.5 4.5
Case
Matarial Flame-resisting ABS resin Epoxy resin Flame-resisting
ABS resin

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
10/17 Kyongbo Electric Co., Ltd
3. Functional Description
3.1 Construction
This ELD(GD16-L05A, GD16-L05R) is arithmetic type earth leakage detector, This have
been manufactured for the alarm activated when setting-current over detection.
Leakage detector input current signal(see appended 2) been the digitalization of current signal
through the 12 sampling after go through such as over input protection circuit, sample & hold,
multiplexer, and it measured the RMS current of fundamental frequency element through the
DFT(Discrete Fourier Transform), and it has no effect by harmonic and DC-offset.
3.2 Functions
Earth Dectecting Function
This element can be fire accident spread minimization through alarm on expectation
situation of fire accident when earth leakage occured on power system line of AC 600V or
less.
Metering Function
Displayed value display ZCT primary zero sequence current value input to ELD as a
current RMS display function.
Measurement Range •0 ~ 5A
•Over 5A Current display 7-Segment as “HHH”
Measurement Accuracy •±10%

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
11/17 Kyongbo Electric Co., Ltd
3.3 Product Structure
Front has the 7-segment, 7 LEDs, 5 Push button S/W and 16 of 3 level S/W, such as
【Figure 1.】. And rear is see the【Figure 2.】.
【Figure 1】
【Figure 2】

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
12/17 Kyongbo Electric Co., Ltd
No Contents Description
1 Measurement
display
ZCT primary earth leakage current RMS of each power system line is displayed on 7-
segment.
2Circuit display
Applied power system line is displayed on 7-segment when ZCT connection test and
earth leakage detector operate test.
Applied power system line is displayed when Earth leakage fault occurred.
3 Circuit selection
Switch
Applied power system line selection when ZCT connection test and operation test.
The circuit switch for checking the earth leakage detector operated power system line after
occuring of earth leakage fault.
4 Connection status
LED
When press the test switch, turn on the LED(yellow), if connection of ZCT with earth
leakage detector was correct.
5 Test Switch The test switch that is tested the ZCT connection status and earth leakage detector
operation of each circuit.
6 Power LED Turn on the power LED(green) when earth leakage detector power supply voltage is
supplied.
7 Alarm LED Turn on the alarm LED(red) when earth leakage detector operated.
8 Reset Switch
The Auto/Manual switch set to manual, and even if the earth leakage of power system
line became to recover when the earth leakage detector operated, the operation status is
continuous. if you want to restore, use this switch.
9 Auto LED Turn on the Auto LED(green) when Auto/Manual switch be Auto.
10 Manual LED Turn on the Manual LED(yellow) when Auto/Manual switch be Manual.
11 Auto/Manual
Switch
Auto If earth leakage power system line is recover, earth leakage detector
operation status is recover automatically.
Manual Operation status is continuous even if earth leakage power system line
became recovered. If want to recover, must press the reset switch.
12 Buzzer ON LED Turn on the ON LED(green) when Buzzer ON/OFF switch be ON.
13 Buzzer OFF LED Turn on the OFF LED(yellow) when Buzzer ON/OFF switch be OFF.
14 Buzzer ON/OFF
Switch
Buzzer
ON
Alarm sound is operate when the earth leakage fault occurred on state of
Buzzer ON.
Buzzer
OFF
Alarm sound is not operate when the earth leakage fault occurred on state
of Buzzer OFF.
15 Detection
sensitive setting
Switch
The nominal operating current of each circuit can be control until 0.2-0.5-1.0A(3 level
control).
16 Fuse Holder Fuse for protection
17 Power ON/OFF
Switch Use when want to power ON/OFF of the earth leakage detector.
18 Buzzer Buzzer for alarm
19 External relay
contacts
The external Relay a contacts(1a~16a) and COM contacts of the each circuit.
(GD16-L05R only)
20 External
connection
contacts
· P+, P- : Power supply voltage connection contacts.
· Ta, Tc : Dry contacts for output.
· Z1~Z16 : ZCT secondary input contacts of each circuit.
· Zc : ZCT secondary circuit common contacts.
· F.G : Frame Ground

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
13/17 Kyongbo Electric Co., Ltd
Appended 1. Dimensioned Drawings
GD16-L05A/R

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
14/17 Kyongbo Electric Co., Ltd
Appended 2. Internal Block Diagram
GD16-L05A
GD16-L05R

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
15/17 Kyongbo Electric Co., Ltd
Appended 3. External Connection
GD16-L05A GD16-L05R
Caution) 1. This Connection is Example, User can set as needed
2. Dry contacts Ta, Tc, 1a~16a can be used if necessary
But, 1a ~16a is GD16-L05R Type only
3. If connection is 3p4w, 4wire penetrate to ZCT.
4. Fuse capacity is 0.5[A]
1, 1[A]
1.

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
16/17 Kyongbo Electric Co., Ltd
Appended 4. ZCT Dimensioned Drawings
ZCT( ZL02, 03, 05, 06, 08, 10, 12 )
unit:mm
Type
Size
ZL02
ZL03 ZL05 ZL06 ZL08 ZL10 ZL12
A Φ25 Φ30 Φ50 Φ65 Φ80 Φ100 Φ120
B 70 75 91 108 123 140 160
C 100 130 150 180
D 40 50
E 80 130 160
F 30 40
G 37.5 40 48 56.5 64 72.5 82.5

1Class Digital Earth Leakage Detector (GD16-L05A, GD16-L05R) User’s Manual(V1.00)
17/17 Kyongbo Electric Co., Ltd
ZCT(ZL15, 20 )
unit : mm
Type
Size
ZL 15
ZL 20
A150 200
B112 143
C 222 284
D 220 282
E 55 55
F 10 10
G 100 100
H 80 80
I 180 180
ZCT(ZL16, 21, 26 )
unit:mm
Type
Size
ZL16 ZL 21 ZL 26
A240 290 340
B160 210 260
C 110
D 30
E 50
This manual suits for next models
1
Table of contents
Popular Security Sensor manuals by other brands

REV Ritter
REV Ritter LED TRIANGLE SENSOR Assembly and operating instructions

Orno
Orno OR-MA-701 Operating and instalation instructions

Besam
Besam SR221-2 quick start guide

Satel
Satel SILVER user manual

Vanderbilt
Vanderbilt AGB800-AM Instruction and installation manual

Radiodetection
Radiodetection RD400PDL-2 user guide