Labkotec LID-3300IP User manual

Labkotec Oy
Myllyhaantie 6
FI-33960 Pirkkala, FINLAND
Tel. +358 29 006 260 28.5.2020
Fax +358 29 006 1260 DOC001181-EN-3
Internet: www.labkotec.fi 47 pages
Copyright © 2020 Labkotec Oy All rights reserved
LID-3300IP Type 2 Ice Detector
Ice Detector for Wind Turbines and
Meteorological Stations
Installation and Operating Instructions

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 2/47
TABLE OF CONTENTS
ABOUT THIS MANUAL ............................................................................................ 4
SUMMARY OF CHANGES AND NEW FUNCTIONALITY....................................... 4
1PRODUCT OVERVIEW....................................................................................... 5
2INSTALLATION ................................................................................................... 6
2.1 Installation and interfaces of LID-3300IP Type 2 Control Unit..................... 6
2.2 Installation of LID/ISD Type 2 ice sensor..................................................... 6
2.3 Lightning protection...................................................................................... 8
3ELECTRICAL CONNECTIONS........................................................................... 9
3.1 Power supply.............................................................................................. 10
3.2 Connections between ice sensor and control unit ..................................... 10
3.3 Relay outputs............................................................................................. 11
3.3.1 Three-wire relay connection........................................................... 12
3.3.2 Two-wire relay connection............................................................. 13
3.4 Analog outputs........................................................................................... 14
3.5 Serial interfaces: RS-232 maintenance and optical fiber interface............ 14
3.5.1 RS-232 Terminal Settings.............................................................. 14
3.5.2 Serial Output - Streaming Mode Format........................................ 16
3.5.3 Serial Output –Measurement and Configuration Menu ................ 16
3.6 Ethernet interface....................................................................................... 19
4COMMISSIONING AND SYSTEM VALIDATION.............................................. 19
5LID-3300IP TYPE 2 ICE DETECTOR IN OPERATION .................................... 20
5.1 Operating modes........................................................................................ 20
5.2 Manual Ice alarm test................................................................................. 21
5.3 Manual sensor heating............................................................................... 21
5.4 LID-3300IP Type 2 Front Panel................................................................. 22
5.5 Use of different parameter settings............................................................ 22
6INTERNET WEB ACCESS................................................................................ 23
6.1 Web UI - Header........................................................................................ 24
6.2 Web UI –Status......................................................................................... 24
6.3 Web UI - Raw command input................................................................... 24
6.4 Web UI - Settings....................................................................................... 24
6.5 Direct Web Access between PC and LID .................................................. 27
7TECHNICAL SPECIFICATION.......................................................................... 29
8REPAIR AND SERVICE.................................................................................... 30
9MAINTENANCE................................................................................................. 30
10 FAULT STATES ................................................................................................ 32
11 INSTALLATION MODIFICATION...................................................................... 32
12 REPLACEMENT................................................................................................ 32
13 RECYCLING...................................................................................................... 32

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 3/47
APPENDIX A. STREAMING MODE OF SERIAL OUTPUT................................... 33
APPENDIX B. PARAMETERS ............................................................................... 36
APPENDIX C. TERMINAL COMMANDS ............................................................... 39
APPENDIX D. SYSTEM CONNECTION DIAGRAM.............................................. 42
APPENDIX E. EVENT LOG MESSAGES .............................................................. 43
APPENDIX F. FUNCTIONAL SAFETY DATA SHEET........................................... 46
APPENDIX G. DECLARATION OF CONFORMITY............................................... 47
Symbols in this document
Caution, hot surface
Caution, risk of danger

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 4/47
ABOUT THIS MANUAL
This manual includes instructions for the installation, commissioning
and operating of Type 2 of the LID-3300IP Ice Detector system.
Labkotec products are designed to be safe when operated in the
manner described in this manual. The safety of this product cannot be
guaranteed if the product is used in any other way than is specified in
this manual.
SUMMARY OF CHANGES AND NEW FUNCTIONALITY
The following table describes the latest changes and major new
functionality in LID-3300IP Type 2 Ice Detector and this user manual.
Changes in this user manual
More information in chapters
Function of serial interfaces has changed. RS-232 serial communica-
tion interface is for maintenance and optical fiber serial communication
interface is for SCADA systems.
Chapter 3.5 “Serial interfaces: RS-
232 maintenance and optical fiber
interface”

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 5/47
1 PRODUCT OVERVIEW
LID-3300IP Type 2 is an ice detector for wind turbines and
meteorological stations. LID-3300IP Type 2 ice detector system
consists of LID-3300IP Type 2 control unit (later referred to also as LID)
and LID/ISD Type 2 ice sensor (later referred to also as ice sensor).
LID-3300IP Ice Detector system, Type 2, is the latest version of the
product, which fullfills the requirements of PLd according to ISO 13849-
1. The safety function is validated through relay outputs.
LID monitors the icing weather conditions on-line and reports icing
events through various interfaces. Ice alarm and other measurement
information are available via 2 relay outputs, 2 analog outputs, front
panel or optical fiber interface and TCP/IP Web user interface or
Modbus.
Ice detection of the ice sensor is based on an ultrasonic principle.
Ultrasonic signal attenuates when ice is accumulated on the sensor
wire.
By default, LID starts to heat itself after an ice detection to get rid of the
accumulated ice.
Alarm levels and ice sensor heating, among other functions, can be
controlled by user-configurable parameters. Certain factory parameters
have been defined by the manufacturer, which allow start-up and
operation without any additional configuration.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 6/47
2 INSTALLATION
Mounting, installation, commissioning, operation, maintenance and
disassembly of the system may only be carried out by trained, qualified
personnel. The instruction manual must be read and understood.
2.1 Installation and interfaces of LID-3300IP Type 2 Control Unit
The enclosure of LID is wall-mounted. Mounting holes are located in
the base plate of the enclosure, beneath the mounting holes of the front
cover.
2.2 Installation of LID/ISD Type 2 ice sensor
The ice sensor is designed for mounting on a weather mast. The
preferred place for installation in a wind turbine is on top of the nacelle.
The correct installation position is marked with an upwards-pointing
arrow label.
The ice sensor should be mounted against the wind so that there is free
airflow in front of the ice sensor. See the below figure for the preferred
installation direction. Free air distance must be minimum 500 mm.
Avoid installations where there is a possibility that the ice which
accumulates to surrounding structures might reach the ice sensor.
A standard delivery includes a mounting kit for installing the ice sensor
on the weather mast. See the figure below. Other mounting options are
also available on request.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 7/47
Flammable materials or materials that may melt are not allowed to
locate close to the ice sensor.
The ice sensor body includes a 350W heating resistor. A temperature
sensor T1 (ice sensor temperature) is located in the centre part of the
ice sensor and temperature sensor T2 (ambient temperature) inside the
connector of the ice sensor cable. A safety thermostat is also mounted
inside the body of the ice sensor to break the heating circuit if the ice
sensor temperature rises above +65 °C.
NOTE! Ice sensor shall be placed in a way that it is not influenced by
the warm air from the exhaust of the turbine cooling system.
NOTE! Ice sensor shall be placed in a way that it is within LPZ0B (see
next chapter “Lightning protection”)

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 8/47
2.3 Lightning protection
Lightning protection for LID-3300IP control unit and LID/ISD ice sensor
shall be done according to standard IEC 61400-24 “Wind turbines –
Part 4: Lightning protection” when installed into a wind turbine.
General principles for protecting ice detector system against
overvoltage in case of lightning strike is presented in the above picture.
Components in the picture are:
1. LID-3300IP Type 2 control unit
2. Surge protection device
3. Automation cabinet
4. Metal tubes
5. LID/ISD Type 2 ice sensor
6. Holder for ice sensor
7. Air termination rod

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 9/47
3 ELECTRICAL CONNECTIONS
Interfaces and other important components of LID are described in the
below list and picture.
1. Main fuse
2. Fuse for sensor heating
3. Fuse for sensor heating
4. Connector for front panel flat cable
5. Optical fiber converter module (RS2O).
Tx connector (left), Rx connector (right)
6. Not in use
7. RS-232 D -connector (maintenance)
8. Connector for RS2O module and
firmware download (alternative)
9. Jumper for manual firmware download
10. Ethernet RJ-45 connector for Internet
Web access and Modbus TCP/IP
11. Analog outputs (source)
Active current output 1
11 = Iout1+
12 = Iout1-
Active current output 2
13 = Iout2+
14 = Iout2-
12. Analog signal cable shield connector
13. Relay outputs
Fault relay (normally energized =
no fault)
5= normally closed (NC)
6= common contact (CC)
7= normally open (NO)
Ice Alarm relay (normally de-energized =
no ice alarm)
8= normally open (NO)
9= common contact (CC)
10 = normally closed (NC)
14. Ice sensor signal
15. Ice sensor cable shield connector
16. Sensor heating
17. Power

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 10/47
3.1 Power supply
The device does not have a mains switch. During maintenance and
service operations it has to be possible to switch off the main supply.
Only an authorized electrician is allowed to install power supply cable
to LID-3300IP control unit.
The installation of power supply can be done by two alternative ways:
- Permanent wiring: using a two pole mains switch (250 Vac,
minimum 5 A), which isolates both lines (L1, N). Switch must be
installed in the main power supply lines in the vicinity of control unit.
Switch must be in accordance with IEC 60947-1. Copper wires 1.5
- 2.5 mm2(AWG 16 - 13) can be connected to the power supply
terminal of the control unit.
- Plug connection: using supply cable with plug that can be
disconnected from socket outlet when necessary. Remember to
tighten the strain relief of the cable gland.
Control unit must always be connected to protective earth (PE).
3.2 Connections between ice sensor and control unit
The cables connecting the ice sensor and LID are included in the
delivery. The standard length of the cables is 10 m.
Only an authorized electrician is allowed to install heating cable
between ice sensor and LID.
The connections between LID-3300IP Type 2 control unit and LID/ISD
Type 2 ice sensor are shown in the following figure. Optional
temperature sensor extension cable improves ambient temperature
accuracy. Included Heat shrink tube is recommended to be added
around the extension cable connectors for extra protection against
possible water leakage.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 11/47
NOTE! Additional measures regarding lightning protection might be
needed according to IEC 61400-24. See also chapter 2.3 Lightning
protection.
NOTE! Make sure that high voltage cabling and equipment will not
interfere ice detector system or cabling of ice detector.
NOTE! Do not coil cables because inductive coupling can cause
harmful interferences.
Instructions for proper use of ice sensor cable connectors are shown in
picture below. A narrow gap around 1 mm will remain, when the
connector is perfectly connected. This applies for both cables, signal
cable and heating supply cable.
More information is available in document D80359_E “Instructions for
proper use of LID/ISD ice sensor cable connectors”.
3.3 Relay outputs
LID-3300IP has two relays with potential free relay outputs. Both relays
have NC (normally closed), CC (common contact) and NO (normally
open) connections available at the connectors.
Ice alarm relay is de-energized during normal operation. Ice alarm relay
is energized when ice is detected.
Fault relay is energized during normal operation. Fault relay is de-
energized when fault is detected.
The safety function of the ice detector is validated through relay outputs.
See the table below:
Signal
Ice alarm relay
State
Ice detected
8 (NO) –9 (CC) = connected
9 (CC) –10 (NC) = open
energized
Ice not detected
8 (NO) –9 (CC) = open
9 (CC) –10 (NC) = connected
de-energized
Signal
Fault relay
Fault detected
5 (NC) –6 (CC) = open
6 (CC) –7 (NO) = connected
de-energized
No faults
5 (NC) –6 (CC) = connected
6 (CC) –7 (NO) =open
energized
The following chapters present the two alternative ways to utilize the
relay outputs.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 12/47
3.3.1 Three-wire relay connection
If there is adequate amount of I/O in the automation, it is recommended
to use the three-wire connection for LID-3300IP Type 2 installation, as
shown in the figure below.
With this connection, the automation can detect if the cabling is properly
connected. In case there is an alarm state, the Ice alarm relay
connector pin 10 is Low and pin 8 is High. With no alarm, pin 10 is High
and pin 8 is Low (the situation in the figure below). If pins 8 and 10 are
Low or High simultaneously, the cable is faulty.
The same connection principle goes also for the Fault relay. However,
the pins are reversed. This is shown in figure below.
With this connection, the automation can detect if the cabling is properly
connected. In case there is a fault state, for the fault relay connector pin
5 is Low and pin 7 is High. With no fault, pin 5 is High and pin 7 is Low
(the situation in the figure below). If pins 5 and 7 are Low or High
simultaneously, the cable is faulty.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 13/47
3.3.2 Two-wire relay connection
Two-wire connection is recommended only for old installations where
LID-3300IP Type 2 is used to replace a LID-3300IP. The connection
can be made:
a) See the figure below. Pin 9 (ice alarm relay) is used for the relay com-
mon contact, and pin 8 is connected to the automation system. The fig-
ure represents normal operating status, where no ice has been de-
tected. When ice is detected relay state changes to NO.
b) In case the automation can be reprogrammed, it is recommended to
use pin 9 (CC) for the common contact and pin 10 (NC) is connected to
the automation system. Thus, ice detection is activated if the control
unit or cable is faulty.
In two-wire mode, fault relay should always be connected from pins 5
and 6. Pin 5 is the input to automation, and pin 6 is the output from
automation. When connected this way, fault signal is activated e.g.
when cable is removed. See the figure below. The figure represents
normal operating status, where there are no faults active. If a fault
occurs, relay state changes to NC.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 14/47
3.4 Analog outputs
Ice level can be read from the analog output, but this configuration is
not validated as Safety function. See connections from chapter 3 or
Appendix D.
3.5 Serial interfaces: RS-232 maintenance and optical fiber interface
LID is equipped by default with an RS-232 serial communication
interface for configuration and maintenance connection.
Also, an optical fiber serial interface is available as an option for
configuration and connection to SCADA systems. This requires an
additional RS2O Converter module to be installed inside LID (item 5 in
the picture in chapter 3).
Connection of RS-232:
1. Connect cable:
•RS-232 cable to RS-232 D-connector (item 7 in the
picture in chapter 3)
2. Connect RS-232 cable to system.
Connection of optical fiber interface:
1. Switch off the power from LID
2. Open the cover of LID
3. Connect cable:
•Optical fibers to RS2O Converter module through the
right-side cable gland on LID
4. Close the cover of LID
5. Connect optical fibre to system
6. Switch on the mains power.
3.5.1 RS-232 Terminal Settings
Ice signal value, eventual alarms and fault diagnostics can be obtained
by using a PC equipped with an ordinary terminal program e.g. Tera
Term. It’s also possible to change operational parameters with the
terminal program. The following procedure describes serial port setting
using freeware ‘Tera Term’ - terminal program.
1. Connect the RS-232 port of your PC to the RS-output D-connector
on the LID-3300IP control unit. Use USB-to-RS converter if your PC
is not equipped with an RS-232 port.
2. Start the terminal program and select Setup >Serial Port. Select
the RS-232 (COM) port of your PC where the serial cable is
connected.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 15/47
3. Make port settings as below and press OK.
4. Select Setup >Terminal and set Local echo and New-line
settings as described below. Press OK.
LID should start communicating with your PC as seen below.
Finally change the terminal font from menu: Setup > Font.
Choose e.g Courier New, regular, Size 9, to view as much text as
possible in one window at a time.
Now all the settings are ready for communication.
5. You can save the session for further use. Select Setup > Save
setup… TERATERM.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 16/47
3.5.2 Serial Output - Streaming Mode Format
Right after the connection to RS-232 serial output has been
established, Ice Detector starts to send a data format through the
connection. New values are reported once every 4 seconds.
Example (variable length format with two temperature sensors):
08 -5.0 -5.5 *100
08 -5.5 -5.5 *100
08 -6.0 -6.0 *100
…
There are three different output formats:
- Variable length format (RSFORMAT 0)
- Constant length format (RSFORMAT 1)
- LID-3210 format (RSFORMAT 2)
The output format is read with command RSFORMAT and set with
command RSFORMAT <x>.
In case parameter 4 (Number of temperature sensors) has been set to
1, ambient temperature value is not visible in the RS output.
More detailed definitions of the output formats are presented in
Appendix A.
3.5.3 Serial Output –Measurement and Configuration Menu
RS-232 streaming mode can be interrupted at any time by pressing the
Enter key. The following menu structure opens with self-explaining
instructions.
RS-232 output returns to streaming mode either by pressing ‘q’ or
automatically after 60 seconds.
ENTERING COMMANDS
All commands in the menus can be given in capital or small letters.
In addition to the commands listed in the menus, e.g. the following
commands are available. They can be entered in any menu view.
- TEST
The test command starts a manual ice alarm test.
- HEAT
The heat command starts manual heating.
See Appendix C for a complete list of terminal commands.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 17/47
MAIN MENU
MENU 1. MEASUREMENTS AND STATUS
MENU 2. PARAMETERS
The complete list of parameters is presented in Appendix B.
Parameters.
To read a parameter, type: RP<param nbr>
Example: RP0
To change a parameter, type: SP<param nbr> <value> and press
Enter.
Example: SP0 50

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 18/47
MENU 3. DEFAULT PARAMETERS
The complete list of parameters is presented in Appendix B.
Parameters.
In case of problems, it might be useful to compare the actual parameter
values with the default parameter values.
Default parameter values can be restored with command SDF.
MENU 4. NETWORK SETUP
When LID is connected to Internet or Intranet, the following settings can
be done via this menu: IP-address, Default gateway and Subnet mask.
LID has a unique MAC address which is also visible through this menu.
MENU 5. VERSION INFORMATION
Version information of LID-and ice sensor can be seen from this menu.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 19/47
MENU 6. SITE INFORMATION
Site name can be changed through this menu. Site information is visible
in every menu and in the Web user interface.
3.6 Ethernet interface
Ethernet connection is used to monitor and control the device over the
web user interface. More information in the chapter 6. LID also has a
Modbus server for reading icing related measurements and diagnostic
data. More information in document DOC001735 LID-3300IP Type 2
ETHERNET MODBUS TCP/IP SPECIFICATION.
4 COMMISSIONING AND SYSTEM VALIDATION
LID is ready for operation when ice sensor and control unit are
connected together, the relay outputs are connected to the automation
systems and power is switched on in the control unit.
The following things shall be done right after the installation, in order to
validate the installation.
1) Check device parameters either via web or serial user interface
and make sure they are according to factory settings. Adjust
parameters if needed.
2) Define network settings for internet access via MENU 4 in serial
interface.
3) Set site name via web or serial interface.
4) Generate an ice alarm with test button or cooling spray, and
validate that the Ice alarm is generated
5) Power device off to validate that the Fault alarm is generated.

LID-3300IP Type 2 Ice Detector DOC001181-EN-3
Installation and Operating Instructions
Copyright © 2020 Labkotec Oy 20/47
5 LID-3300IP TYPE 2 ICE DETECTOR IN OPERATION
This chapter explains the basic operation of LID-3300IP Type 2 ice
detection system. Serial and Web user interfaces are explained in
different chapters.
5.1 Operating modes
LID-3300IP Type 2 ice detection system operates in different modes
which are explained below.
START MODE
When the Ice detection system is started, Fault relays are ON, until the
control unit receives reasonable data from the sensor. If the system is
working ok and the data is correct, Fault relays will be deactivated after
measurement data is correct.
SENSING MODE
LID continuously measures the signal level of the ice sensor. The
maximum signal amplitude value can be defined by the user by
parameter 2. By default, the signal value varies between 0 and 100.
Ice signal value is visible in serial and web user interfaces, and
available as continuous current message in the analog output.
In sensing mode, LID is asking the Ice sensor for measurement data.
Ice sensor is replying to this message by sending the measurement
data for ice, internal temperature and external temperature.
ICE DETECTED MODE
When ice signal goes below a defined alarm level (set by parameter 0),
LID goes to Ice detected –mode and gives an ice alarm. The delay of
an ice alarm can be set by parameter 3.
Ice alarm is visible in the Ice alarm LED of the front panel as well as
serial and web interfaces. Ice relay energizes and closes contacts 8 and
9.
Ice alarm and ice detected mode are active during the heating and
cooling phases that follow an ice alarm.
Parameter 22 can be used to set a delay for ice alarm deactivation. It
will keep the ice alarm active after the heating and cooling phase for the
duration of the time delay. This is to prevent repetitive alarms during a
long icing event.
HEATING PHASE
Right after the ice alarm is detected, ice sensor starts to heat itself to
get rid of the accumulated ice. It is also possible to disable heating by
parameter 12. The whole heating process can be controlled with
parameters 12 –18, 23 and 24. Default heating parameters shoud be
useful enough for most weather conditions.
Automatic heating is used to remove soft ice which has slowly
accumulated over the ice sensor in light icing conditions. It does not
generate an ice alarm. Automatic heating is controlled with parameters
23 and 24.
COOLING PHASE
When ice sensor is heated to the maximum heating temperature, LID
moves to cooling phase. Ice signal value is measured all the time and
it should be close to the maximum after the heating phase.
Other manuals for LID-3300IP
1
Table of contents
Other Labkotec Security Sensor manuals
Popular Security Sensor manuals by other brands

System Sensor
System Sensor SPECTRAlert CH24 Series Installation and maintenance instructions

Antec Scientific
Antec Scientific DECADE II SDC 174 user manual

PNI
PNI SafeHouse HS003 user manual

Trader
Trader SCORPION SCSPSENSORBK instructions

Monacor
Monacor SMILE-16 operating instructions

Velleman
Velleman DVMEMF user manual

Orno
Orno OR-CR-214 quick start guide

Pfeiffer Vacuum
Pfeiffer Vacuum ASM 310 operating instructions

Reer
Reer ADMIRAL AX BK Installation, use and maintenance

STEINEL
STEINEL HF 3360 Information

C.P. Electronics
C.P. Electronics MWS3A-DD Product guide

Air Specialties Express
Air Specialties Express LU-BELT Installation, operating and maintenance instructions