LBS DRAGON POWER PLUS 15 User manual

DRAGON POWER PLUS 15
15 KVA - 60 KVA
UPS USER MANUAL

1
Preface
Usage
The manual contains information on installation, use, operation and maintenance of UPS. Please
carefully read this manual prior to installation.
Users
Authorized Person
Note
●Our company is providing a full range of technical support and service. Customers can contact
our local office or customer service center for help.
●The manual will update irregularly, due to the product upgrading or other reasons.
●Unless otherwise agreed, the manual is only used as the guide for users and any statements or
information contained in this manual make no warranty expressed or implied.
●The product shouldn’t be used for any life sustaining system.

2
Safety Precautions
This manual contains information concerning the installation and operation of UPS. Please carefully
read this manual prior to installation.
The UPS cannot be put into operation until it is commissioned by engineers approved by the
manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment
malfunction and invalidation of warranty.
Safety Message Definition
Danger: Serious human injury or even death may be caused, if this requirement is ignored.
Warning: Human injury or equipment damage may be caused, if this is requirement is ignored.
Attention: Equipment damage, loss of data or poor performance may be caused, if this requirement
is ignored.
Commissioning Engineer: The engineer who installs or operates the equipment should be well
trained in electricity and safety, and familiar with the operation, debug, and maintenance of the
equipment.
Warning Label
The warning label indicates the possibility of human injury or equipment damage, and advised the
proper step to avoid the danger. In this manual, there are three types of warning labels as below.
Labels Description
Serious human injury or even death may be caused, if this requirement
is ignored.
Human injury or equipment damage may be caused, if this requirement is
ignored.
Equipment damage, loss of data or poor performance may be caused, if
this requirement is ignored.
Safety Instruction
⟡Performed only by commissioning engineers.
⟡This UPS is designd for commercial and industrial applications
only, and is not intended for any use in life-support devices or
system.
⟡Read all the warning labels carafully before operation, and follow
the instructions.

3
⟡When the system is running , do not touch the surface with this
label, to avoid any hurt of scald.
⟡ESD sensitive components inside the UPS, anti-ESD measure
should be taken before handling.
Move & Installation
⟡Keep the equipment away from heat source or air outlets.
⟡In case of fire, use dry powder extinguisher only, any liquid
extinguisher can result in electric shock.
⟡Don’t start the system if any damage or abnormal parts founded.
⟡Contacting the UPS with wet material or hands may be subject to
electric shock.
⟡Use proper facilities to handle and install the UPS. Shielding shoes,
protective clithes and other protective facilities are necessary to
aviod injury.
⟡During positioning, keep the UPS way from shock or vibration.
⟡Install the UPS in proper environment, more detail in section 2.3.
Debug & Operate
⟡Make sure the grounding cable is well connected before
connecting the power cables, the grounding cable and neutral
cable must be in accordance with the local and national codes
practice.
⟡Before moving or re-connecting the cables, make sure to cut off
all the input power sources, and wait for at least 10 minutes for
internal discharge. Use a multi-meter to measure the voltage on
terminals and ensure the voltage is lower than 36V before
operation.
⟡The earth leakage current of load will be carried by RCCB OR
RCD.
⟡Initial check and inspection should be performed after long time
storing of UPS.
Maintenance & Replacement
⟡All the equipment maintenance and servicing procedures
involving internal access need special tools and should be carried
out only by trained personnel. The components that can be
accessed by opening the protective cover with tools cannot be
maintenance by user.

4
⟡This UPS full complies with “IEC62040-1-1-General and safety
requirements for use in operator access area UPS”. Dangerous
voltages are present within the battery box.
However, the risk of contact with these high voltages is minimized
for non-service personnel. Since the component with dangerous
voltage can only be touched by opening the protective cover with
a tool, the possibility of touching high voltage component is
minimized. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended
operating procedures in this manual.
Battery Safety
⟡All the battery maintenance and servicing procedures
involving internal access need special tools or keys and
should be carried out only by trained personnel.
⟡When connected together, the battery terminal voltage will
exceed 200Vdc and is potentially lethal.
⟡Battery manufacturers supply details of the necessary
precautions to be observed when working on, or in the
vicinity of a large bank of battery cells. These precautions
should be followed implicitly at all times. Particular attention
should be paid to the recommendations concerning local
environmental conditions and the provision of protective
clothing, first aid and fire-fighting facilities.
⟡Ambient temperature is a major factor in determining the
battery capacity and life. The nominal operating temperature
of battery is 20℃. Operating above this temperature will
reduce the battery life. Periodically change the battery
according to the battery user manuals to ensure the back-up
time of UPS.
⟡Replace the batteries only with the same type and the same
number, or it may cause explosion or poor performance.
⟡When connecting the battery, follow the precautions for high-
voltage operation before accepting and using the battery,
check the appearance of the batteries. If the package is
damaged, or the battery terminal is dirty, corroded or rusted
or the shell is broken, deformed or has leakage, replace it
with new product. Otherwise, battery capacity reduction,
electric leakage or fire may be caused.
⟡Before operating the battery, remove the finger ring, watch,
necklace, bracelet and any other metal jewelry.
⟡Wear rubber gloves.
⟡Eye protection should be worn to prevent injury from

5
accidental electrical arcs.
⟡Only use tools (e.g. wrench) with insulated handles.
⟡The batteries are very heavy. Please handle and lift the
battery with proper method to prevent any human injury or
damage to the battery terminal.
⟡Don’t decompose, modify or damage the battery. Otherwise,
battery short circuit, leakage or even human injury may be
caused.
⟡The battery contains sulfuric acid. In normal operation, all
the sulfuric acid is attached to the separation board and plate
in the battery. However, when the battery case is broken, the
acid will leak from the battery. Therefore, be sure to wear a
pair of protective glasses, rubber gloves and skirt when
operating the battery. Otherwise, you may become blind if
acid enters your eyes and your skin may be damaged by the
acid.
⟡At the end of battery life, the battery may have internal short
circuit, drain of electrolytic and erosion of positive/negative
plates. If this condition continues, the battery may have
temperature out of control, swell or leak. Be sure to replace
the battery before these phenomena happen.
⟡If a battery leaks electrolyte, or is otherwise physically
damaged, it must be replaced, stored in a container resistant
to sulfuric acid and disposed of in accordance with local
regulations.
⟡If electrolyte comes into contact with the skin, the affected
area should be washed immediately with water.
Disposal
⟡Dispose of used battery according to the local instructions.

6
1 UPS Structure and Introduction
1.1 UPS Structure
1.1.1 UPS Configuration
The UPS configurations are provided in Table 1-1.
Table 1-1 UPS Configuration
Item Components Quantity Remark
10-15kVA
Circuit Breakers 4 Optional
Dual Input 1 Standard
Parallel Card 1 Optional
Dry Contact Card 1 Optional
Cold start 1 Standard
1.1.2 UPS Outlook
The UPS outlooks are shown as figure 1-1.

7
Figure 1-1 UPS Outlook (Unit: mm)
1.1.3 Details of UPS front and rear views
The UPS front views are shown as Figure 1-1.
Rear panel:
As shown in Figure 1-2, the UPS rear panel offers the following components:
SNMP (Optional) Parallel(Optional)RS485
RS232 USB(Optional)Connector
Dry Contact LBS(Optional, only available for 20k and 25k)

8
Rear View for 10k
Rear View for 15k
Figure 1-2 Details of the views
1.2 Product Introduction
1.2.1 UPS System Description
The Rack UPS is configured by the following part: Rectifier, Charger, Inverter, Static bypass switch.
One or several battery strings should be installed to provide backup energy once the utility fails.
The UPS structures are shown in Figure 1-3.
Figure 1-3 UPS Block Diagram

9
1.2.2 Operation Mode
The tower UPS is an on-line, double-conversion UPS that permits operation in the following modes:
⚫Normal mode
⚫Battery mode
⚫Bypass mode
⚫Maintenance mode(manual bypass)
⚫ECO mode
⚫Auto-restart mode
⚫Frequency Converter mode
1.2.2.1 Normal Mode
The inverter of UPS continuously supply the critical AC load. The rectifier/charger derives power
from the AC main input source and supplies DC power to the inverter while simultaneously
FLOAT or BOOST charging its associated backup battery. The Normal mode structure is shown in
Fig.1-4.
Figure 1-4 Normal mode operation diagram
1.2.2.2 Battery Mode
Upon failure of the AC main input power, the inverter of UPS, which obtains power from the battery,
supply the critical AC load. There is no interruption in power to the critical load upon failure. After
restoration of the AC mains input power, the” Normal mode” operation will continue automatically
without the necessity of user intervention. The Battery mode structure is shown in Fig.1-5.

10
Figure 1-5 Battery Mode operation diagram
Note: With the function of “Battery Cold Start”, the UPS could start without utility. See more detail
in section5.1.2.
1.2.2.3 Bypass Mode
If the overload capacity of the inverter is exceeded under Normal mode, or if the inverter becomes
unavailable for any reason, the static transfer switch will perform a transfer of the load from the
inverter to the bypass source, with no interruption in power to the critical AC load. Should the
inverter be asynchronous with the bypass, the static switch will perform a transfer of the load from
the inverter to the bypass with power interruption to the load. This is to avoid large cross currents
due to the paralleling of unsynchronized AC sources. This interruption is programmable but
typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms
(60Hz). The action of transfer/re-transfer can also be done by the command through monitor. The
Bypass mode structure is shown in Fig.1-6.
Figure 1-6 Bypass mode operation diagram

11
1.2.2.4 Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS
becomes unavailable e.g. during a maintenance procedure. The Maintenance mode structure is
shown in Fig.1-7.
Figure 1-7 Maintenance mode operation diagram
Danger
During Maintenance mode, dangerous voltages are present on the terminal of input, output and
neutral, even with all the modules and the LCD turned off.
1.2.2.5 ECO Mode
To improve system efficiency, UPS system works in Bypass Mode at normal time, and the inverter
is standby, when the utility from the bypass fails, the UPS will transfer to Battery Mode and the
inverter powers the load. The ECO mode structure is shown in Fig.2-8.
Figure 1-8 ECO Mode operation diagram

12
Note
There is a short interruption time (less than 10ms) when transferring from ECO mode to battery
mode, it must be sure that the interruption has no effect on loads.
1.2.2.6 Auto-restart Mode
The battery may become exhausted following an extended AC mains failure. The inverter shuts
down when the battery reaches the End of Discharge Voltage (EOD). The UPS may be programmed
to “System Auto Start Mode after EOD”. The system starts after a delay time when the AC mains
recover. The mode and the delay time are programmed by the commissioning engineer.
1.2.2.7 Frequency Converter Mode
By setting the UPS to “Frequency Converter Mode”, the UPS could present a stable output of fixed
frequency (50 or 60HZ), and the bypass static switch is not available.

13
2 Installation
This chapter introduces UPS installation, including unpacking and inspection, main Cabinet
Installation, cables connection.
2.1 Location
As each site has itself requirements, the installation instructions in this section are as a guide for the
general procedures and practices that should be observed by the installing engineer.
2.1.1 Installation Environment
The UPS is intended for indoor installation and uses forced convection cooling by internal fans.
Please make sure there is enough space for the UPS ventilation and cooling.
Keep the UPS far away from water, heat and inflammable and explosive corrosive material. Avoid
installing the UPS in the environment with direct sunlight, dust, volatile gases, corrosive material
and high salinity.
Avoid installing the UPS in the environment with conductive dirt.
The operatingenvironmenttemperaturefor batteriesis 20℃-25℃. Operating above 25℃will reduce
the battery life, and operation below 20℃will reduce the battery capacity.
The battery will generate a little amount of hydrogen and oxygen at the end of charging; ensure the
fresh air volume of the battery installation environment must meet EN50272-2001 requirements.
When external batteries are used, the battery circuit breakers (or fuses) must be mounted as close as
possible to the batteries, and the connecting cables should be as short as possible.
2.1.2 Site Selection
Ensure the ground or installation platform can bear the weight of the UPS cabinet, batteries and
battery racks.
No vibration and less than 5 degree inclination horizontally.
The equipment should be stored in a room so as to protect it against excessive humidity and heat
sources.
The battery needs to be stored in dry and cool place with good ventilation. The most suitable storage
temperatureis 20℃to 25℃.
2.1.3 Size and Weight
The dimension and weigh for the UPS cabinet is shown in Table 2-1
Table 2.1 Weight for the cabinet

14
Configuration Dimension(W*D*H)mm Weight
10kVA 488*945*130 25kg
15kVA 488*945*130 30kg
2.2 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
● 1 UPS
● 1 user manual
2) Inspect the appearance of the UPS to see if there is any damage during transportation. Do not
turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of
some parts.
3) If you need tower type installation, you need to find the support block and the middle seat in
advance. You need a support seat and 2 middle seats
2.3 Notes for Installation
(1) The UPS must be installed in a location with good ventilation, far away from water, inflammable
gas and corrosive agents.
(2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of
space on each side.
(3) Condensation to water drops may occur if the UPS is unpacked in a very low temperature
environment. In this case it is necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of electric shock.
NOTICE:UPS operation in sustained temperature outside the range of 15-25C(59-77F)
reduces battery life.
2.4 Main Cabinet Installation
Two installation modes are available: Tower installation and Rack installation, depending on
available space and user considerations. You can select an appropriate installation mode according
to the actual conditions.
2.4.1 Tower Installation
Various installation configurations are available: single UPS, single UPS with single or multiple
battery cabinets. Their installation methods are all the same.
Please prepare support bases and spacers before installation
(1) Take out the support bases and spacers and then assemble the spacer and the support bases,
shown as Fig.2-1.

15
Fig.2-1 Support bases and spacers assembly
(2) Place the UPS on the support bases, shown as Fig.2-2.
Fig.2-2 Tower installation
(3) Remove the LOGO in the upper right corner, turn it 90 degrees counterclockwise, and then insert
it.
2.4.2 Rack Installation
Battery cabinets must be installed firstly because battery cabinets are too heavy. And two or more
installation personnel are required to install them at the same time. Please install them from bottom
to top.
(1)Install the guide rail
(2)Put the UPS and battery cabinet on the guide rail, fix the units to the service rack, shown as Fig.2-
3.

16
Fig.2-3 Rack Mounted Installation
2.5 Battery
Three terminals (positive, neutral, negative) are drawn from the battery group and connected to
UPS system. The neutral line is draw from the middle of the batteries in series (See Figure 2-4)
Figure 2-4 Battery connection diagram
Danger
The battery terminal voltage is of more than 200Vdc, please follow the safety instructions to avoid
electric shock hazard.
Ensure the positive, negative, neutral electrode is correctly connected from the battery unit terminals
to the breaker and from the breaker to the UPS system.

17
2.6 Power Cables
2.6.1 Specifications
The UPS power cables are recommended in Table 2-2.
Table 2-2 Recommended cables for power cables
Contents Main Input Bypass Input Output Battery PE
15KVA(3/3)A B C N A B C N A B C N BAT+ N BAT- PE
Current(A)50 50 50 50 42 42 42 42 42 42 42 42 76 76 76 42
Size(mm²)10 10 10 10 10 10 10 10 10 10 10 10 16 16 16 10
10KVA(3/3)A B C N A B C N A B C N BAT+ N BAT- PE
Current(A)34 34 34 34 28 28 28 28 28 28 28 28 51 51 51 28
Size(mm²)10 10 10 10 6 6 6 6 6 6 6 6 10 10 10 6
Note
The recommended cable section for power cables are only for the situations described below:
⚫Ambienttemperature:30℃.
⚫AC loss less than 3%,DC loss less than1%,The length of the AC power cables are no longer
than 50 m and the length of the DC power cables are no longer than 30 m.
⚫Currents listed in the table are based on the 208V system (Line-to-line voltage).
⚫The size of neutral lines should be 1.5~1.7 times the value listed above when the predominant
loads non-linear.
2.6.2 Specifications for Power Cables Terminal
Specifications for power cables connector are listed as Table 2-3.
Table 2-3 Requirements for power terminal
Port Connection Bolt Bolt Torque
Mains input Cables crimped
OT terminal M6 7mm 4.9Nm
Bypass Input Cables crimped
OT terminal M6 7mm 4.9Nm
Battery Input Cables crimped
OT terminal M6 7mm 4.9Nm
Output Cables crimped
OT terminal M6 7mm 4.9Nm

18
PE Cables crimped
OT terminal M6 7mm 4.9Nm
2.6.3 Circuit Breaker
The external circuit breakers (CB) for the system are recommended in Table 2-4.
Table 2-4 Recommended CB
Model Input Bypass Output Battery
15KVA
(3 / 3)63A/3P 63A/3P 63A/4P DC 100A/3P
10KVA
(3 / 3)63A/3P 63A/3P 63A/4P DC 80A/3P
Attention
The CB with RCD (Residual Current Device) is not suggested for the system.
2.6.4 Connecting Power Cables
(1) Verify that all the switches of the UPS are completely open and the UPS internal maintenance
bypass switch is open. Attach necessary warning signs to these switches to prevent unauthorized
operation.
(2) Open the back door of the cabinet, remove the plastic cover. The input and output terminal,
battery terminal and protective earth terminal are shown in Fig.2-5
Fig.2-5 Connection terminals
(3) Connect the protective earth wire to protective earth terminal (PE).
(4) Connect the AC input supply cables to the main input terminal and AC output supply cables to
the output terminal.
(5) Connect the battery cables to the battery terminal.
(6) Check to ensure there is no mistake and re-install all the protective covers.
Note: mA, mB, mC standard for Main input phase A, B and C; bA, bB, bC standard for
Bypass Input phase A, B and C.
Attention

19
The operations described in this section must be performed by authorized electricians or qualified
technical personnel. If you have any difficulties, contact the manufacturer or agency.
Warning
⚫Tighten the connections terminals to enough torque moment, refer to Table 2-3, and please
ensure correct phase rotation.
⚫Before connection,ensure the input switch and the power supply are off,attach warnings label
to warn not to operate by others
⚫The grounding cable and neutral cable must be connected in accordance with local and national
codes.
⚫When the cable holes does not goes through by cables, it should be filled by the protective ring.
2.7 Control and Communication Cables
The rear panel of the cabinet provides dry contact interface(J2-J9) and communication interface
(RS232, RS485, SNMP, Parallel card interface and USB port),as it is shown in Fig.2-6.
Fig.2-6 Dry contact &communication interface
2.7.1 Dry Contact Interface
Dry contact interface includes port J2-J11 and the functions of the dry contact are shown in Table
2-5.
Table 2.5 Functions of ports
Port Name Function
J2-1 TEMP_BAT Detection of battery temperature
J2-2 TEMP_COM Common terminal for temperature detection
J3-1 ENV_TEMP Detection of environmental temperature
Table of contents
Other LBS UPS manuals
Popular UPS manuals by other brands

INFOSEC
INFOSEC Zenergy Station 2000 user guide

Eaton
Eaton Powerware 9135 manual

Huawei
Huawei UPS5000-A-200 Series quick guide

Atlantis Land
Atlantis Land OnePower Line Interactive UPS A03-S1001 user guide

CyberPower
CyberPower OLS6000ERT6UA user manual

Eaton
Eaton Power-Sure 700 Installation and user manual