LBS DRAGON POWER 1-L User manual

DRAGON POWER 1-L
1 KVA - 3 KVA
USER MANUAL

Safety precautions
Operation
1. Before usingthis product, please read "safety precautions" carefully to ensure correct and
safe use, and please keepthe manual properly.
2. Duringoperation, please pay attention to all warning signsand operate as required.
3. Donot use the device in direct sunlight,rain or the humid environment.
4. Thisequipment should not be installed near the heat source area or similar equipment such
aselectric heater andhot stove.
5. Asafedistanceandventilation shouldbe reservedaroundthe UPS. Please refer to the manual
for installation.
6. Please use dry cleaningtools for wipingor cleaning the UPS.
7. In caseoffire, please usethe drypowderextinguishercorrectly. Thereisariskof electric shock
if a liquid fire extinguisheris used.
Electrical safety
1. The battery life is shortened with the increase of ambient temperature. Regular battery
replacement can ensurethe UPS to work normallyand provide sufficient backuptime.
2. Battery maintenancecanonly becarried out by personnelwith battery expertise.
3. There is a risk of electric shock and short circuit in the batteries. Toavoid personal injury
causedby electric shock,please observe the following warningswhen replacingbatteries:
A. Do not wear watches, ringsor similar metal objects;
B. Use insulatedtools;
C. Wear rubber shoes andgloves;
D. Donot place metal tools or similarparts on the battery.
E. Disconnectthe load fromthe batteries before removingthe battery connectionterminal.
4. Please do not expose the battery to the fire for avoiding explosion and endangering the
safety of life.
5. Non-professionalsshould not open or damage the battery, because the electrolyte in the
battery contains dangerous substances such as strong acid, which can cause harm to the skin
andeyes.If youaccidentally touchthe electrolyte, immediatelywashit with plenty ofwater and
goto the hospital for examination.
6. Please do not short-circuitthe positive and negative poles of the battery, which may cause
electric shockor fire.
Use andmaintenance
1. The useenvironment andpreservation method have influence on the service life and
reliability of this product.Please do not useit in the following workingenvironment:
A. High,low temperature and humidplaces exceedingthe technical specifications(temperature
0-40℃, relative humidity 20%-90%).
B. Places with vibration andvulnerable to collision.
C. Places with metal dust, corrosive substance, salt andcombustible gas.
2. If it is not usedfor a longtime, the UPS(without battery) mustbe storedin a dry
environmentat the temperature range:-15-60℃.Before starting UPS, the ambient
temperature mustbe warmedto 0℃above andmaintainedfor morethan 3hours.

Content
1.Introduction ...............................................................................................................................1
1.1Symbol.............................................................................................................................1
1.2Rear view .........................................................................................................................2
1.3Specification ....................................................................................................................3
1.4Electromagneticcompatibility .........................................................................................4
2.Installation ..................................................................................................................................5
3.ControlPanel...............................................................................................................................5
3.1Panel display.................................................................................................................... 6
3.2Functionof button...........................................................................................................7
3.3UPS workingstatustable of LCDdisplay...........................................................................8
3.4Parameter query............................................................................................................. 9
3.5Functionsetting.............................................................................................................10
4.Warningcode/faultcodeandsolution ..................................................................................... 13
4.1Warningcodeandsolution............................................................................................13
4.2Fault codeandsolution .................................................................................................14
4.3Commonfaultsandtrouble shooting.............................................................................16
5.Controlandcommunication......................................................................................................17
5.1SNMP Card.................................................................................................................... 17
5.2DryContact.....................................................................................................................17
5.3EPO................................................................................................................................ 18
6.Battery Maintenance & Repair .................................................................................................19

1
1. Introduction
This series of UPS is an online sine wave uninterruptible power supply system with bypass
maintenance switch, which can provide reliable and high-quality ACpower for your precision
equipment. It can be used in a wide range, from computer equipment, communication system
to industrial automatic control equipment. Because of its online design, it is different from the
backup ups. It continuously adjusts and filters the input voltage. When the power supply is
interrupted, itwill providethe backuppowerfromthe backupbattery without timeinterruption.
In case of overload or inverter failure, the UPS switches to the bypassstate and be powered by
the mains.If theoverloadiscleared,the UPS willautomaticallyswitchbackto the inverterpower
supplystate.
1.1 Symbol
Symbolsand Meanings
Symbols Meanings
Attention
Danger
AC(alternating current)
DC(direct current)
Protective earth conductor
Protective connectingconductor
Loop
Donot place with sundries
Overload
Battery
ON/OFFSwitch

2
1.2 Rear view
Computerinterface
Smart slot(optional)
Externalbattery connection
USB
Input over currentprotection
ACINPUT
Output socket
EPO
Battery interface
Battery breaker(optional)
⑪Maintenance bypassswitch (optional)
⑫Output breaker(optional)

3
1.3 Specification
Model DP1OL-3KTRL-120
Capacity 3kVA/3kW
Input
Nominal Voltage 100/110/115/120/127VAC, L+N+PE
Voltage Range 55-150VAC
Frequency 40-70Hz
Power Factor 0.99
THDi ≤4% (linear load); ≤5% (non-linearload)
Output
Nominal Voltage 100/110/115/120/127VAC, L+N+PE
Voltage Regulation ±1%
Frequency 50/60Hz±0.1%
CrestRatio 3:1
Voltage HarmonicDistortion ≤2% (linear load); ≤4%non-linear load
Transfer Time Line modeto battery mode,0ms;inverter to bypass,4ms(typical)
Waveform Pure sine wave
Overload time
Line mode:
10min@102%-110% load
1min@110-130%load
10s@130%-150%load
Battery mode:
1min@102%-110% load
10s@110-130%load
30s@130%-150%load
Efficiency
Line Mode 94%
Battery Mode 93%
ECOMode 98%
Battery
Type Sealed lead acid maintenancefree
Voltage 96VDC
Battery Number 12V 9Ah*8pcs
ChargingCurrent 1A
ChargingMode Two/Threeperiod charging
Management
Intelligent port RS232/USBport/SNMP card (optional)/Dry contact kit (optional)
Environment
Operation Temperature 0-40℃
Relative Humidity 0-95%(non-condensing)
Audible Noise 40dB@1 meter
Altitude The altitude shouldnotexceed 1000m,and the height above 1000m
should be reduced to amaximumof4000m.Refer to IEC62040

4
Loadat highaltitude=Rated power *Derating factor (correspondingto altitude)
Altitude(m) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating factor 100% 95% 91% 86% 82% 78% 74% 70% 67%
Notice: If the machine is used at above 1000m,diminishing ratings output must be used,
please refer to above table for derating factor.
1.4 Electromagneticcompatibility
Safety
IEC/EN 62040-1-1
EMI
ConductedEmission……IEC/EN 62040-2 ClassA
Radiated Emission..........IEC/EN 62040-2 ClassA
EMS
ESD...................................IEC/EN 6100-4-2 Level 4
RS.....................................IEC/EN 6100-4-3 Level 3
EFT....................................IEC/EN 6100-4-4 Level 4
SURGE..............................IEC/EN 6100-4-5 Level 4
Low FrequencySignals……IEC/EN 6100-2-2
Warning:Thisis aproduct for commercialand industrial application in the second
environment-installationrestriction or additional measuresmaybe needed to prevent
disturbances.
NOTICE:
Thisis aproductfor restricted sales distribution to informedpartners. Installation restrictions
or additional measuresmaybe needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40℃
(32-104℉). Install it in a clean environment, free from moisture,flammableliquids, gasesand
corrosive substance.
ThisUPS contains nouser-serviceableparts exceptthe internal battery pack.The UPS ON/OFF
pushbuttons donot electrically isolate internal parts. Under no circumstanceattempt to gain
accessinternally, due to the riskof electric shockor burn.
Donot continue to usethe UPS if the panel indicationsare not accordancewith these
operatinginstructionsor the UPS performancealters in use. Reflect all faults to your dealer.
Servicing of batteries shouldbe performed or supervised bypersonnel knowledgeableof
batteries andthe precautions.
Keepunauthorizedpersonnel awayfrom the batteries. Proper disposalof batteries is required.
Refer to your local laws andregulations for disposalrequirement.
DONOTCONNECTequipmentthat could overload the UPS ordemandDCcurrent fromthe
UPS, for example:electric drills, vacuumcleaners, laser printers, hair dryer or any appliance
usinghalf-waverectification.
Storing magneticmedia ontop of the UPS mayresult in data lossor corruption.
Turnoff and isolate the UPS before cleaningit. Use only a dry cloth, never liquid or aerosol
cleaners.

5
2. Installation
2.1 Setup the UPS
Sep 1: UPS inputconnection
Plug the UPS into a two-pole,three-wire, groundedreceptacle only. Avoidusingextensioncords.
Step 2: UPS output connection
For socket-typeoutputs, simply connect devices to the outlets. For terminal-type input or
outputs, please follow below stepsfor the wiring configuration:
a) Removethe smallcover of the terminal block.
b) Suggest usingAWG14 or 2.1mm²power cords.
c) Upon completion of the wiring configuration, please check whether the wires are securely
affixed.
d) Put the smallcover backto the rear panel.
Step 3: Communicationconnection
Communicationport:
RS232port Intelligent slot USB port
Toallow for unattended UPS shutdown/start-upandstatus monitoring, connect the
communicationcable one end to the USB/RS232port and the other to the communicationport
of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up
and monitor UPS status throughPC.
TheUPS isequippedwith intelligent slotperfect foreither SNMP or AS400card.When installing
either SNMP or AS400cardin the UPS, it will provide advancedcommunicationandmonitoring
options.
PS.USB portandRS-232portcant workat thesame time.
Step 4: Turnon the UPS
Press the ONcombinationbuttons onthe front panel for two secondsto power on the UPS.
Note: The battery chargesfully duringthe first five hoursof normaloperation. Donot expectfull
battery run capability duringthis initial chargeperiod.
Step 5: External batteryconnection
ThisUPS doesnot include batteries.
Please connect external batteries asthe below drawing.
RS232interface on UPS:
3. ControlPanel

6
3.1 Panel display
Display Function
Error message
FAULT Failure occurred
Warnings
Fault code
Mute
Mute function
Input and outputvoltage, DCvoltage, UPS internal temperature
VAC:input and output voltage; VDC:DCvoltage
℃: UPS internaltemperature; Hz:Frequency
Loadinformation
The loadvolume(0-25%,26%-50%,51%-75%, 76%-100%) isshownhere,
andthe overload icon flasheswhen the battery is low or notconnected
Battery information
The battery capacity(0-25%, 26%-50%,51%-75%, 76%-100%)is displayed
separately,andthe battery iconflasheswhen the battery is low or not
connected
Other information
AC
Battery
Bypass
Inverter
Output working
Fan status: LEDwill always be onwhen the fan is normal, andflashes when
the fan fails
Setting icon: when entering the setting menu,the icon will light up, and
the icon isnot shownin the other cases
ECOfunction: the icon light upwhen ECOfunction is used,otherwise the
icon is not displayed
Maintenance icon: when the maintenanceswitch isturned on, the icon
lightsup, in the other cases, the icon isnot displayed

7
3.2 Function of button
Button Functional Description
Combokey for turningon the UPS ACMode: pressthe two buttons at the sametime for 1
secondabove to start UPS.
Battery Mode: pleasepress confirmation button first,
after turningon the screen,please pressthe two buttons
at the same time for1secondabove to start UPS.
Combokey forturningoff the UPS
ACMode: pressthe two buttons at the sametime for 1
secondabove to turn off the inverter, the systemwill turn
to BypassMode.
Battery Mode: pressthe two buttonsat the sametime for
1secondabove to turn off the inverter, and after 1
minute, the systemwill shut down, andthe screen will
turn off.
Combokeyfor self-checkingand
mute function
Testing:in ACMode, pressthe two buttons at the same
time for 2secondsabove to test the battery.
Mute: in Battery Mode/Alarm/TestingMode, presstwo
buttons at the sametime for 2 secondsabove to erase
alarms, press two buttons again for 2 secondsabove to
recover alarms.
Function setting/confirmation key
Functionsetting: press the key more than 2 secondsto
enter the function setting page,after completingthe
setting, press the key more than 2secondsagainto return
to the main page.
Confirmation:in the function setting page, pressthe
confirmation key 1to 2 secondsto confirm the setting
options.
Page turning/query key
Pageturning: press or key 1to 2 secondsto turn
to left or right page.
PollingMode: press the key more than 2secondsto
enter Polling Mode, circularly displayeach pagecontent
for 2seconds, press morethan 2 secondsagain to
return to the main page.

8
3.3 UPS workingstatustable ofLCDdisplay
ACMode
LCDdisplaycontent Instruction
UPS can provide stable ACoutput when ACinput in the
permissible range.In ACMode, batteries will also be chargedby
the UPS.
Battery Mode
LCDdisplaycontent Instruction
When the ACinput isout of limited rangeor shutoff, the UPS will
turn to Battery Mode. Thebatteries supplythe inverter and have
beep every 4seconds.
BypassMode
LCDdisplaycontent Instruction
When the ACinput keepsnormal, start the bypassmode and
closethe UPS on the panel. TheUPS will turn to BypassMode,
and have beep every 2 minutes.
Error Condition
LCDdisplaycontent Instruction
When the UPS hasfaults or alarms,LCDdisplaywill show the
information.

9
3.4 Parameter query
Normally the LCDdisplay can show 8pagestotally. Pressing the query button or for
0.1-2seccan enter into the different pageswhich show all information, suchas input, battery,
output, load, software version, temperature, and etc. If alarms occur,the display will add one
morepageto showthe alarm information.If the UPS hasfaults, the default displaywill turn to
the Fault code pageautomatically, the home pagewill show the fault or alarm information by
default. When UPS keepsnormal working,the homepagedefault display will show the output
voltage and frequency information.
Press (right button) more than 2sec, LCDwill turn to the pollingmode. Every 2 secthe
shown displaywill turn pages.Press longtime, LCDwill exit the polling mode.
LCDDisplay1: UPS input & output voltage LCDDisplay2: UPS input & output frequency
LCDDisplay3: Battery voltage and capacity LCDDisplay 4: Output voltage and output
active power
LCDDisplay 5:Output voltage and output
apparent power
LCDDisplay 6:Output voltage and load
percentage
LCDDisplay7: UPS systemsoftware version LCDDisplay8: connected battery quantity

10
3.5 Function setting
●01: Outputvoltage
LCDDisplay Setting
1. Press the function setting button over 2 sec, then goto
the setting page.Press the pageturning buttonstill the setting
pageof output voltage, and the word "OPU" flashing.
2. Press confirmation button 0.5-2sec,then go to the
setting pageof output voltage OPU.The "OPU" wordslight on,
and the numbers by left side of OPU keepsflashing. Press page
turning buttons or 0.5-2secto choose different output
voltage value, the optional voltage values are 110V,115V,120V
and 127V.The default output voltage is 120V.Please save after
setting.
3. Turnto the voltage value which you need, and press
confirmation button 0.5-2sec,then finish the OPU setting.
The numberby left side of OPUwill keep lightingon, no
flashing.
4. Press functional setting button over 2 sec,quit the
setting pageand backto the home page.( Or no operation,
waiting more than 30sec, the page will come backto home
pageautomatically).
Note: When the output voltage settingwith 110V,the output
needsto decrease to 90% of ratedpower.
●02: Otherfunctionalsetting
02-1:Expert Mode(EP)
LCDDisplay Setting
The expertmodesetting with ON, then goto the functional
setting pageagain.Thefunctional setting will show battery
QTY(PCS), EPO, chargingcurrent and other items can be
selected. When the expert modesetting with OFF,functional
setting pagewill show only the general options.
Note: The expertmodedefault to OFF.When setting asONthen
re-connectedthe ACpower, the EP can be recovered as OFF.

11
02-2Battery low voltage shutdownpoint/End ofdischargevoltage(EOD)
LCDDisplay Setting
The options of EODsetting are dEF,9.8V,9.9V,10V,10.2V,10.5V.
By default, the EOD is dEF
(The EOD will be changed accordingto loading condition.
10.5V@load<25%,10.2V@25%<load<50%,10V@load>
50%).
02-3:EconomicOperation Mode
LCDDisplay Setting
ECOis OFF bydefault, can be set as ONto improve the efficiency
of systemoperation.
Note: For the modelswith PF <1, OFFbydefault, andunableto
set.
02-4:Emergency shutdown(EPO)
LCDDisplay Setting
When EP isset to ON, the EPOoption appearson the function
setting page. Emergencyshutdown can be set as closed or open
to trigger,the default is open to trigger.
Note: After EPO action, emergencyshutdown,closeall outputs
immediately.

12
02-5:Battery quantity(PCS)
LCDDisplay Setting
When EP is set to ON,the PCSoption appearson the function
setting page,will enter the passwordpage,enter the password
(the general passwordis 135),you can set the number of
batteries. Thedefault battery numberis 16pcs,whichcan be set
to 16/18/20pcs.
02-6:ChargerCurrent(CHG)
LCDDisplay Setting
When EP is set to ON,the CHGoption appearson the functional
setting page, the chargingcurrent can be set, 1-12Aoptional,
default 1A.Noted: if UPS built-inbatteries, the charger current
default 1A, andcant be changed.
02-7:Input Neutral and Livecable reverse alarm function
LCDDisplay Setting
The input neutral and live cable reverse alarm mode is closedby
default, can chooseto open to improve the safety of the system.
Note: Factory settingsdefault closed, pleaseopen if youneed.

13
4. Warning code/faultcodeandsolution
4.1 Warning code andsolution
When the " "symbolon the UPS LCDflashes,the UPS isin alarmstate. Press the pageturning
keyto the error state page(refer to 3.5), observe the alarm code andmakeappropriate
processingaccordingto the table below.
Alarm Indication Possible reasons Treatment measures
1Nobattery
connection
1. Nobattery connected
2. Battery damaged
1. Checkthe connection of batteries.
2. Changethe batteries.
2Battery low
voltage
Thebattery voltage is lessthan
the low voltage warningpoint.
The batteries dischargeto below
the alarm point.
After the battery has beensat fora
period of time, it canbe turned on
again. Thebuilt-inchargercan be
turned on to chargethe battery.
4
Input neutral
and live cables
are reversed
1. Input neutral and live cables
are reversed.
2. Input groundcable is not
connected.
3. Output groundcable is not
connected.
1. Reverse the neutral andthe live
cables.
2. Checkthe groundcable
connection.
8Battery over
voltage UPS detects highbattery voltage
Checkthat the battery quantity
setting isconsistentwith the actual
battery quantity.
9 Chargerfailure Abnormalcharger hardware Contact the supplier.
10
Over
temperature
alarm
1. Fan fault
2. Air ductof UPS rear panel is
blocked.
3. Overload
4. NTCsensorabnormal or
connection abnormal
5. Power componentIGBT is
damaged.
1. Checkthe rectifier fan.
2. Remove blockageson the rear
panelof the UPS.
3. Checkthe load.
4. If the above treatments do not
work, contact the supplier.
12 Fan fault 1. Fan wiring is loose.
2. Fan hardware abnormal Checkthe fan and connection
13 ACfuse open Fuse blown Contact the supplier.
14 EEPROM fault EEPROM chipdamages. Contact the supplier.
21 Overload The loadsexceedthe rated
power. Checkthe load.
22
3times
consecutive
overload locks
3times consecutive overload
locks Shut downandrestart UPS.
23 EPO action Press EPO button.
1. Release EPO button.
2. Checkthe wiring harness on EPO
button.
24 Maintenance
switch action
The maintenance switch is
pressed. Release maintenance switch.

14
4.2 Fault code and solution
When the "FAULT"islongbright, and" "symbolon the UPS LCDflashes, the UPS is in fault
state. UPS automatically switchesto the error status page(refer to 3.5) to observe the fault
code and makeappropriate processingaccordingto the following table.
Fault
code Indication Possible reasons Treatment measures
1 Bus boosting soft-
starting fail
1. ACabnormal
2. Abnormal soft-starting
circuit of bus
Checkthe mains, if all normal,
please contact the supplier.
2 Bus over voltage 1. ACabnormal
2. Software processingerror
3. Bus capacitor failure
Checkthe mains, if all normal,
please contact the supplier.
3 Bus under voltage 1. Cityelectricity is too low.
2. Software processingerrors
3. Bus capacitor failure
1. Please checkthe rectifier fan.
2. Clean the obstacles onthe air
ductof the rear panelof the UPS.
3. Check theloads.
4. If all of above do not work, please
contact the supplier.
7 Over temperature 1. Fanfailure
2. Theair duct on the rear
panel of the UPS is blocked;
3. Overload
4. NTCsensor abnormality or
abnormalwiring
5. Power componentIGBT is
damaged.
1. Please checkthe rectifier fan;
2. Clean the obstacles onthe air
ductof the rear panelof the UPS;
3. Check theloads;
4. If all of above do not work, please
contact the supplier.
8 Battery relay
short circuit
Relay RL1/RL3hardware
damaged
Please contact the supplier
9 Bus relay soft-
starting fail
1. Cityelectricity abnormal
2. Bus soft-staringcircuit
abnormal
Please checkthe city electricity
power, if no abnormal, please
contact the supplier.
17 Inv soft-starting
fail
1. Some hardware of the
inverter is damaged;
2. The control panel fails.
Please contact the supplier.
18 Inv output over
voltage
1. Some hardware of the
inverter is damaged;
2. The control panel fail.
Please contact the supplier.
19 Inv output under
voltage
1. Some hardware of the
inverter is damaged;
2. The control panel fails.
Please contact the supplier.
20 Inv short circuit 1. Some hardware of the
inverter is damaged.
2. Output short circuit
1. Checkif the short circuit existson
the outputof UPS.
2. Checkif the load is short circuit.
3. If no abnormal,please contact
the supplier.

15
26 Negative power
protection(output
with ACinput fail)
1. Bypass reverses to the
inverter.
2. load abnormal
Checkthe loads and if no abnormal,
please contact the supplier.
33 Inv relay or SCR
open circuit
Relay RL8 is damaged. Please contact the supplier.
34 Inv relay or SCR
short circuit
35 Bypass relay or
SCR open circuit
Relay RL4/RL6isdamaged. Please contact the supplier.
36 Bypass relay or
SCRshort circuit
37 I/Oconnection
reversed
Reverse wiring on input and
output.
Please checkthe wiring harness of
input and output.
39 Charger short
circuit
1. Output of charger short
circuit
2. Charger hardware abnormal
Please contact the supplier.
66 Over load fault 1. Overload too much
2. The voltage reduction
causesthe system rated power
to decrease.
1. Checkif the load is within the
specified range;
2. Checkif the voltage has been
reduced.
67 Chargingover
voltageor battery
connection
reversed
1. Hardware error
2. Number of battery wrong;
3. Wiring wrong.
1. Checkwhether the battery wiring
or battery number meetsthe
requirements.
2. If no anyabnormal, please
contact the supplier.
68 Unknown
machine model
Software versionerror 1. Restart the machine;
2. If no anyabnormal, please
contact the supplier.
72 Chargerover
current
1. Hardware error;
2. Battery abnormal.
1. Checkwhether the battery wiring
or battery number meetsthe
requirements;
2. If no anyabnormal, please
contact the supplier.
73 No bootstrap Software versionerror 1. Restart the machine;
2. If no anyabnormal, please
contact the supplier.
81 Unknownbattery Numberof battery wrong
QTYsetting
1. Checkwhether the battery
numbermeets the requirement;
2. Checkif the configuration of the
battery jumper capis the sameas
the software setting.
82 Battery QTY
setting matching
error
Numberof battery setting
wrong andcan not be matched
with software setting.

16
4.3 Commonfaultsandtrouble shooting
Number Problem or errors description Reason Solution
1 Connectto city electricity,
andno display on LCDdisplay
panel
No input power Checkif the input wiring
harnessof UPS is in well
connection.
Input voltage under
voltage oroverload
Use voltagemeter to check
the input voltage if in normal
or meets the requirement.
2 Cityelectricity in normal,no
ACinput indication, UPS is
still workingin battery mode
UPS power switchis
still off
PressUPS city electricity
power button on
The wiring harness is
loosen or in poor
connection.
Checkthe input wiring harness
whether in normal.
3 UPS not displayerror, but no
output voltage
The wiring harness is
loosen or in poor
connection
Make sure the wiring harness
in well connection.
4 Press button, UPS
doesnt start
Press buttontoo
shortly
Press over 5 seconds,
hear "Di" sound
Overload Remove all loadsand restart
the machine.
5 With city electricity,butno
city electricity indication
Mains voltage or
frequencyover UPS
input range
Use a multi-meterto check
whether the input voltageand
the input frequency meetsthe
requirements.
6 The battery dischargetime is
lower than the standard time
Thepower of batteries
has been used.
Changenew battery
Thebatteries were not Chargethe batteries more
be charged fully. than 8 hoursunder normal
city electricity,then retestit.
7 Abnormal sound orsmell
come out fromthe inside of
UPS
Inner of UPS maybe
damaged
Please immediatelyturn off
the UPS, cut offthe power
input andcontact the
customerservice center for
technical support.
8 Battery modedisplayyellow
light, longbuzzersounds,
battery capacity is
insufficient, ready to shut
down
Thepower of battery
is low,UPS is readyto
shut down, andthe
loadswill be cut off.
1. Save the data on the loads
immediately and complete
shutdown the important loads
to avoid data lossor damage.
2. Immediately connect the
UPS input terminalto the
standbyACpower supply.

17
5. Controland communication
UPS includesseveral communicationports: RS232,EPO, SNMP card, USB, and dry contact card.
NOTICE:OnlyoneofSNMP card, and drycontact cardcan beusedatthe sametime. Onlyone
ofRS232and USBis available at the sametime.
5.1 SNMP Card
SNMP card is usedto monitor the UPS via TCP/IPprotocol, users can checkthe UPS status and
data online. Please refer to the user manualof SNMP cardto get moredetailed information.
5.2 Dry Contact
There are two types of dry contact for option: DB9, phoenixterminal.
Maximumoutput current for dry contact is 1A.The function of dry contact islisted as below:
DB9 port phoenixterminal
Function DB9
Phoenix
Description
UPS fault 1 9 Open from commonconnection: UPS is abnormal.
Closed:UPS is normal.
General 2 7 Open fromcommonconnection: UPS is warning
Closed:UPS is normal.
GND 3 2 Internal GND,used to connect external power supply 12-24Vdc
Remoted
shutdown
4 4 Input port. Used with external power supply.If connected to
power supply,UPS transfer to bypass.UPS shutdownif bypassis
abnormal.
Common
connection
5 1 Commonconnection of output signal. Connected to power
supply for input signal.
Bypass mode 6 8 Closedto commonconnection: UPS is workingin bypassmode.
Open: UPS is not workingin bypassmode.
Battery low 7 6 Open fromcommonconnection: battery low alarm
Closed:battery capacity isnormal or not inbattery mode
Normal
mode
8 5 Closedfrom commonconnection: UPS is workingin normal
mode.
Utility failure 9 3 Open formcommonconnection: utility input fails.
This manual suits for next models
1
Table of contents
Other LBS UPS manuals
Popular UPS manuals by other brands

DirectUPS
DirectUPS vesta pro 1000 vac user manual

GE
GE Digital Energy SitePro 400 VAC CESeries 7 operating manual

MGE UPS Systems
MGE UPS Systems 40-150kVA Installation and user manual

LEGRAND
LEGRAND Keor MOD Series user manual

Eaton
Eaton Ellipse MAX 600 Installation and user manual

Njoy
Njoy Aira 600 user manual