
Page 6
Use the following procedures to congure the unit for hor-
izontal left-hand discharge operations:
1 - Before operating the unit, remove access panels 
and the horizontal drip shield (-060 model) and the 
corrugated padding between the blower and coil 
assembly. Discard the corrugated padding.
2 -  Pull  the  coil  assembly  from  unit.  Pull  o  the 
horizontal drain pan.
3 - Remove the drain plugs from back drain holes on 
horizontal drain pan and reinstall them on front 
holes.
 IMPORTANT
After removal of drain pan plug(s), check drain hole(s) 
to verify that drain opening is fully open and free of any 
debris. Also check to make sure that no debris has fallen 
into the drain pan during installation that may plug up the 
drain opening. 
4 - Rotate drain pan 180º front-to-back and install it on 
the opposite side of the coil.
5 - Remove screws from top cap. Remove horizontal 
drip shield screw located in the center of the back 
coil end seal as illustrated in gure 4 on page 5.
6 - Rotate horizontal drip shield 180º front-to-back.
7 - Remove plastic plug from left hole on coil front 
end seal and reinstall plug in back hole. Reinstall 
horizontal drip shield screw in front coil end seal. 
Drip shield should drain downward into horizontal 
drain pan inside coil.
HORIZONTAL DRIP SHIELD (-060 MODEL)
DOWN-FLOW RAIL FRONT EDGE OF HORIZONTAL 
FIGURE 5. Left-Hand Discharge Conguration 
8 - Rotate top cap 180º front-to-back and align with 
unused screw holes. Holes must align with front and 
back coil end plates. The top cap has a 45º bend on 
one side and a 90º bend on the other. The 90º bend 
must be on the same side as the horizontal drain 
pan as illustrated in gure 4 on page 5.
NOTE – Be very careful when reinstalling the screws into 
the coil end plate engaging holes. Misaligned screws may 
damage the coil.
9 -  From  the  upow  position,  ip  cabinet  90º  to  the 
left and set into place. Replace blower assembly. 
Secure coil in place by bending down the tab on the 
cabinet support rail as illustrated in gures 4 and 5.
10 - Install the horizontal shield (-060 model) on the 
front edge of the horizontal drain pan as illustrated 
in gure 5 on page 6.
NOTE – For  horizontal  applications  in  high  humidity  ar-
eas, remove the downow rail closest to the drain pan. To 
remove rail, remove screw from rail at back of unit and at 
cabinet  support  rail.  Remove  downow  rail then  replace 
screws. Also, seal around the exiting drain pipe, liquid and 
suction lines to prevent inltration of humid air.
11 - Knock out drain seal plate from access door. Secure 
plate to cabinet front ange with screw provided.
12 - Flip access door and replace it on the unit.
13 -  Set  unit  so  that  it  is  sloped  1/4ʺ  toward  the  drain 
pan end of the unit. Connect return and supply air 
plenums as required using sheet metal screws.
14 - If suspending the unit, it must be supported along the 
entire length of the cabinet. If using chain or strap, 
use a piece of angle iron or sheet metal attached 
to the unit (either above or below) so that the full 
length of the cabinet is supported. Use securing 
screws no longer than 1/2ʺ to avoid damage to coil 
or lter, as illustrated in gure 3 on page 5. Connect 
return and supply air plenums as required using 
sheet metal screws.
DOWNFLOW APPLICATION
NOTE – If  downow  application  is  required,  separately 
order kit number 83M57 and install per kit’s instructions. 
Also use metal or class I supply and return air plenums.
Use the installation instruction provided with the downow 
kit.
 IMPORTANT
If electric heat section with circuit breakers (ECB29/
ECB31) is installed in a CBA27UHE unit in a downow 
application, the circuit breakers must be rotated 180° 
to the UP position. See ECB29/ECB31 installation 
instructions for more details.
Brazing Connections 
 IMPORTANT
To prevent the build-up of high levels of nitrogen when 
purging, it must be done in a well-ventilated area. Purge 
low-pressure nitrogen (1 to 2 psig) through the refrigerant 
piping during brazing. This will help to prevent oxidation 
and the introduction of moisture into the system.
All coils are equipped with a factory-installed, internally 
mounted check/expansion valve.
The air handler’s coil line sizes are listed in table 2. Use 
Lennox L15 (sweat) series line sets (refer to the outdoor 
unit  Product  Specications  (EHB)  for  proper  size,  type 
and application). For eld-fabricated refrigerant lines, see 
the piping section of the Lennox Unit Information Service 
Manual.