
7
INSTALLATION — SYSTEM PIPING
The near boiler piping, that is the piping around
the boiler must be considered as part of the boiler
for proper water level control, and to produce dry
steam. Correct near boiler piping is crucial to the
proper operation of the boiler and the heating sys-
tem. Follow these recommendations carefully.
1. Place boiler in selected location, as near chimney
as possible.
2. Install the pop safety valve, using the furnished
¾” coupling, into the ¾” pipe nipple on the top
of the boiler. Make a discharge pipe, using ¾”
pipe (not furnished) to carry the water or steam
to a nearby drain. Do not connect the discharge
pipe directly to a drain but leave an air gap. The
downstream end of the discharge pipe must be
unthreaded. No shutoff of any description shall
be placed between the pop safety valve and
the boiler, or on discharge pipes between such
safety valves and the atmosphere. Installation
of the pop valve shall conform to the require-
ments of the ANSI/ASME Boiler and Pressure
Vessel Code, Section IV. The manufacturer is
not responsible for any water damage.
3. This boiler is equipped with two 2 ½” supply
connections and two 2 ½” return connections,
one each on both the left and right sides of the
boiler. Unused connections must be plugged
with the 2 ½” plugs (furnished).
4. Recommended near boiler piping for gravity
return systems is shown in Figure 5. This
FRESH AIR DUCT CAPACITIES (Btuh)
1 Square Inch per 4,000 Btuh
100% Free
Area
75% Free
Area
25% Free
Area
Fresh Air
Duct Size
¼” Wire
Mesh
Metal
Louvers
Wood
Louvers
3” x 12” 144,000 108,000 36,000
8” x 8” 256,000 192,000 64,000
8” x 12” 384,000 288,000 96,000
8½” x 16” 512,000 384,000 128,000
Figure #3A
FRESH AIR DUCT CAPACITIES (Btuh)
1 Square Inch per 2,000 Btuh
100% Free
Area
75% Free
Area
25% Free
Area
Fresh Air
Duct Size
¼” Wire
Mesh
Metal
Louvers
Wood
Louvers
3” x 12” 72,000 54,000 18,000
8” x 8” 128,000 96,000 32,000
8” x 12” 192,000 144,000 48,000
8½” x 16” 256,000 192,000 64,000
Figure #3B
FRESH AIR DUCT CAPACITIES (Btuh)
1 Square Inch per 3,000 Btuh
100% Free
Area
75% Free
Area
25% Free
Area
Fresh Air
Duct Size
¼” Wire
Mesh
Metal
Louvers
Wood
Louvers
3” x 12” 108,000 81,000 27,000
8” x 8” 192,000 144,000 48,000
8” x 12” 288,000 216,000 72,000
8½” x 16” 384,000 288,000 96,000
Figure #4
FRESH AIR FOR COMBUSTION
2. One permanent opening commencing with
12 inches of the top of the enclosure, shall
be permitted where the equipment has clear-
ance of at least 1 inch from the sides and back
and 6 inches from the front of the appliance.
The opening shall directly communicate with
the outdoors or shall communicate through
a vertical or horizontal duct to the outdoors
or spaces (crawl or attic) that freely com-
municate with the outdoors, and shall have a
minimum free area of:
a) 1 sq. inch per 3000 Btu per hour of the
total input of all equipment located in the
enclosure (See Figure 4), and
b) Not less than the sum of the areas of all
vent connectors in the conned space.