
Page 18
Options 1 and 2 Jumper Selections
These two jumper settings are used with optional safety
devices (with a normally closed switch) such as a low
ambient control. Unless an optional kit is being used
with the HP21, the jumper setting for options 1 and 2
must be on NO. Placing the jumper on YES without an op-
tional kit will cause a lockout condition.
Option 1 − This jumper assists an optional safety kit and will
lock out the compressor after the third occurrence of a
problem (open contacts) with the optional safety de-
vice. To reset the control, remove the power or the
cycle thermostat demand.
Option 2 − This jumper assists an optional safety device
and will only display and store the code for kit related
problems (open contacts). The control will not lockout
the compressor through Option 2.
Diagnostic LEDs
Diagnostic troubleshooting lights (LEDs) and operational
lights are located on the two−speed control.
Y1 and Y2 LEDs are connected directly to the inputs from
the thermostat. These two lights indicate the room
thermostat demands.
HI and LO LEDs are connected directly across the contac-
tor coils and indicate if the high or low speed contactors
are energized.
HB LED (also called HeartBeat) is connected to the brains
of the two−speed control to indicate that the control itself
is functioning properly. The light also indicates if the
control is in a delay (such as the 1 or 5 minute delay).
During normal operation, the HB light will blink four
times a second. If the control is in delay, the light will
blink once every two seconds. If the HB light is continu-
ously on or off (when power is on), the control is not
functioning properly and should be replaced.
1, 2, 4, and 8 LEDs are used to display diagnostic codes in-
dicating a lockout, problem, or condition. Each problem
code is numbered. To convert the row of lights to code
numbers, add the display numbers together for all the
lights that are on. For example, if lights 2 and 8 are on,
the display code is 10: (2 + 8 = 10). If lights 1, 2, and 4
are on, the display code is 7: (1 + 2 + 4 = 7). See table 6
for each problem code and the corresponding number.
Test Mode Procedure
The TSC6 two−speed control test mode allows you to test
the control as well as the HP21 contactors and compres-
sor.
To initiate the test mode, position the mode jumper on the
TEST jumper selection and press the manual override but-
ton. The override button starts the test sequence; if you do
not press the override button, the control will remain in the
last selected mode. Once the TEST procedure starts, Code
14 will be displayed until the jumper is moved. The control
will operate the compressor in low speed for ten seconds,
turn off for ten seconds, then operate in high speed for ten
seconds. If the test detects a problem condition, the code is
displayed. See table 6.
NOTE − The control will only go into TEST mode if there is
no thermostat demand, and five minutes have elapsed
since the last test. The TEST mode will only be allowed to
run once every five minutes so as not to damage the com-
pressor.
If the compressor is operating when the jumper is in the
TEST mode position, the control will not start the test until
the demand is met. If there is no demand, pressing the but-
ton to override the five minute delay will start the test opera-
tion immediately.
If the jumper is moved after the test sequence has started,
the control will continue with the test until completion. If the
jumper is left in the TEST position, the control will continue to
operate (at the next demand) in the previous mode until a
reset occurs. After a reset, the control defaults to NORMAL
mode operation.
Diagnostic Code Display
A problem code is normally displayed only for the duration of
the error. However, there is one exception. During a lockout,
the code for the problem that is causing the lockout flashes
once a second even if the problem condition no longer exists.
If other problems occur during a lockout condition, the codes
for those problems will be saved in memory, but not dis-
played. The stored problem codes are displayed by recalling
them from memory.
Not all codes cause lockouts or indicate problems. The
diagnostic lights tell the installer or service technician the
status of the entire system, not just the two−speed con-
trol. Some codes do indicate malfunctions or problems
with either the control or the HP21. Others inform the
technician of the unit’s status. All codes (with the excep-
tion of codes 2, 13 and 15) are stored in memory and may
be recalled.
Code 1 − Power Loss for Two Electrical Cycles
This code indicates that the unit’s power skipped two elec-
trical cycles (33−40 milliseconds), and it may suggest the
power to the unit is dirty" or is of low quality. Code 1 is
stored.
Code 2 − Input Indication
This code indicates that a change has been made and that
the control acknowledges the change. It does not indicate a
problem condition. A change could consist of moving jump-
er settings, pressing the override button to override a delay,
or adding an optional safety device to Option 1 or 2. Code 2
is not stored.
Code 3 − Unsteady Thermostat Input
Code 3 indicates intermittent inputs from the room thermo-
stat. Most likely, there is a loose connection at the thermo-
stat when this condition appears. Code 3 is stored.