Level Pro 300 Series User manual

INSTALLATION MANUAL
SUBMERSIBLE PRESSURE SENSORS
Chemical Resistant Industrial Level Sensors + Displays
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
TVL Series
300 SERIES
AL R1 R2
MENU
ESC
ENTER

DANGER! – dangerous situation, which may result in death or serious injuries
WARNING! – potentially dangerous situation, which may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may result in minor injuries
CAUTION! – potentially dangerous situation, which may result in physical damage
1. GENERAL INFORMATION
1.1 Information on the operating manual
This operating manual contains important information on proper usage of the device. Read this
operating manual carefully before installing and starting up the pressure measuring device.
Adhere to the safety notes and operating instructions which are given in the operating manual.
Additionally applicable regulations regarding occupational safety, accident preven-tion as well as
national installation standards and engineer-ing rules must be complied with!
This operating manual is part of the device, and should be kept nearest its location, always
accessible to all employees.
This operating manual is copyrighted. The contents of this operating manual reflect the version
available at the time of printing. It has been issued to our best knowledge. Levelpro is not liable for
any incorrect statements and their effects.
1.2 Symbols used
WARNING!To avoid operator hazards and damage to the the device, the
following instructions need to be followed and installed by qualified technical personnel.
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
2
1.3 Limitation of liability
By non observance of the operating manual, inappropriate use, modification or damage, no liability is
assumed and warranty claims will be excluded.
1.4 Intended Use
The Levelpro Level Sensors have been developed for continuous level measurement. It is the
operator's responsibility to check and verify the suitability of the device for the intended application. If
any doubts remain, please contact our technical department in order to ensure proper usage and
compatibility . Levelpro is not liable for any incorrect selections and their effects!

Permissible media are liquids (no solids or frozen media), specified in the data sheet. In addition it
has to be ensured, that this medium is compatible with the any wetted parts of the level sensor.
The technical data listed in the current data sheet are engaging and must be complied with. If the
data sheet is not available, please order or download it from our homepage.
(http://www.iconprocon.com)
Please verify that all listed parts are undamaged included in the delivery and check for consistency
specified in your order:
1.5 Package Contents
The device can be identified by its
manufacturing label.
Fig. 1 Manufacturing Label
Series :
300S-10105-11
SN: 0143693
300S
Range : 0-
Max Pressure:
Connector Pinout:
Supply :
Output Signal :
Acc
| PSI | KPa
Nominal
Pressure Range
Accuracy
Wiring
Serial Number
Ordering
code
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
3
WARNING! – Danger through improper usage!
Probe
Mounting instructions
2. PRODUCT IDENTIFICATION
WARNING! Install the device only when depressurized and not connected to power source!
WARNING! This device may only be installed by qualified technical personnel who has read
and under stood the operating manual!
Handle this high sensitive electronic precision measuring device with care, both in packed and
unpacked condition!
There are no modifications/changes to be made on the device.
3. MECHANICAL INSTALLATION
3.1 Mounting and safety instructions
Level Transmitter
O Ring Seal:
1/ RED : +
2/ Blu : -
3/ Yellow : Signal Output

Do not throw the package | device!
To avoid damaging the diaphragm, remove packaging and protective cap directly
before starting assembly. The delivered protective cap has to be stored!
Place the protective cap on the pressure port again immediately after disassembling.
Handle the unprotected diaphragm very carefully - it is very sensitive and may be easily
damaged.
Do not use any force when installing the device to prevent damage of the device
When placing the device into operation or after maintenance work, the probe has to be
submerged slowly into the medium! A rough immersion into the medium can damage or
destroy the diaphragm.
If there is any danger of damage by lightning or overpressure when the device is installed
outdoor, we suggest putting a sufficiently Sized overpressure protection device between the
supply or switch cabinet and the device
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
4
Carefully remove the pressure measuring device from the package and dispose of the
package properly.
Mount the device according to your demands.
If the probe has been delivered without mounting accessories. Please contact Icon Process
Controls for tank connection LP100 Junction Box
3.2 Installation Steps
If it is necessary for your application to remove the protection cap, this has to be done with
utmost care. To prevent damage of the diaphragm, please follow these instructions.
3.3 Removing the protection cap
For the protection of the diaphragm, some of the probes have a protection device. The device
must be removed before installation

The default for the Input 1 is 4mA | 0.5V and this will not change.
Typically, the Empty setting will be the tank is empty (example. 000.0 Gallons, 000.0 inches,
000.0 feet etc.).
20mA | 4.5V typically reflects the Full setting will be when the tank is full (example: 500.0
Gallons,120.0 inches,10.0 feet,etc.)
Shielded cable is recommended for control loop wiring.
Use the Red wire as the (+) and the Black wire as the (-)
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
5
WiringtotheLevelproSeriesTankLevelController
Source for
Relays output, depends
on the instalation
Load no.1
Power supply
85.280V
External
Display
-
-
+
+
+
Transmitter
Levelpro Level Sensor
4-20
Output
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
ProAlert 1000
ViewSonic Alerm
NORMAL
TEST SILENCE
Examples : Pump Shut-Off
Valve Shut-Off
Display Provides
24VDC Power
to Levelpro Sensor
AL R1 R2
MENU
ESC
ENTER
ProAlert
Alarm
Relay
Relay
Contactor/
Valve
LP 100
Examples :
Remote Location Office, Fill Station
Audible /Vesual
Pump
WIRING DIAGRAM
Wiring to a Loop Powered Display :

Establish the electrical connection of the device according to the technical data shown on the
manufacturing label, the following table and the wiring diagram.
4. ELECTRICAL INSTALLATION
Prevent the damage or removal of the PTFE filter which is fixed over the end of the air tube on
devices with cable outlet and integrated air tube.
Gauge / relative devices are equipped with cable with integrated air tube for atmospheric pressure
reference. Install cable end in a control cabinet or suitable terminal box in dry area which is free of
aggressive gasses to avoid damages.
For the electrical connection a shielded and twisted multicore cable is recommended.
Source for
Relays output, depends
on the instalation
Load no.1
Power supply
85.280V
External
Display
-
-
-
-
++
+
+
Transmitter
Levelpro Level Sensor
4-20
Output
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
J3 J4 4
5
GND
IN
V+
SENTINEL
VDC
DC
24V 24V
DC
VDC
Display
Provides
24VDC Power
to Sensor
AL R1 R2
MENU
ESC
ENTER
4-20mA
PSupply + +
Supply -
Vs
I
Red
Blue
A
24VDC
0.5-4.5VDC
Supply +
Supply -
P+
I
5VDC
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
6
Wiring Diagram Levelpro Wiring Diagram
WARNING! Install the device only when the unit is not connected!
100 Series with SentinelTelemetry Device
Signal
Red
Blue
Yellow

If the device came in contact with hazardous substances, certain precautions have to be
complied with for purification!
6. SERVICE | REPAIR
6.1 Return
Before every return of your device, whether for recalibration, decalcification, modifications or repair, it
has to be cleaned carefully. You have to enclose a notice of return with detailed defect description
when sending the device. If your device came in contact with harmful substances, a declaration of
decontamination is additionally required. Appropriate forms can be downloaded from our homepage
(http://www.iconprocon.com).Should you dispatchadevicewithoutadeclaration of
decontamination and if there are any doubts in our service department regarding the used medium,
repair will not be started until an acceptable declaration is sent.
7. DISPOSAL
8. WARRANTY CONDITIONS
The device must be disposed according to the European Directives 2002/96/EG and
2003/108/EG (on waste electrical and electronic equipment) Waste of electrical and
electronic equipment may not be disposed by domestic refuse!
WARNING! Depending on the measuring medium, deposit on the device may cause danger
for the user and the environment. Comply with adequate precau-tions for purification and
dispose of it properly.
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
7
The warranty conditions are subject to the legal warranty period of 12 months from the date of
delivery. In case of improper use, modifications of or damages to the device, we do not accept
warranty claims. Damaged diaphragms will also not be accepted. Furthermore, defects due to normal
wear are not subject to warranty services.
TECHNOLOGY
The Levelpro pressure transmitter is placed near or on the bottom of the tank. A ceramic pressure
diaphragm within the pressure transmitter is exposed on one side to the application liquid. The other
side is exposed to the reference pressure via a small ventilation tube located inside of the cable. The
difference in pressure between liquid and reference pressures will slightly deflect the diaphragm.
The deflection of the diaphragm is measure by a built-in microprocessor located inside the ceramic
diaphragm.which is converted into a 4-20mA two wire current signal proportional the height of the
liquid.
Make sure that Levelpro Transmitter is compatible with the application liquid media.

SAFETY PRECAUTIONS
About this Manual : PLEASE READ THE ENTIRE MANUAL PRIOR TO INSTALLING OR
USING THIS PRODUCT. This manual includes information on all versions of the Levelpro
Pressure Level Transmitters Please refer to the part number located on the transmitter label to
verify the exact model which you have purchased.
User's Responsibility for Safety : Levelpro offers a wide range of liquid level sensors and
technologies. While each of these technologies are designed to operate in a wide variety of
applications, it is the user's responsibility to select a technology that is appropriate for the
application, install it properly, perform tests of the installed system, and maintain all
components. The failure to do so could result in property damage or serious injury.
Proper Installation and Handling : Only properly-trained staff should install and/or repair this
product.
Wiring and Electrical : CAUTION - Do not exceed specified supply voltage rating of 30 VDC.
Permanent damage not covered by warranty will result. This device is not designed for 120
or 240 volt AC operation. Use only the specified voltage found in the specification sections.
Temperature and Pressure : The Levelpro series are designed for use in the specified
application temperatures referred to in the specification section.
Material Compatibility : Make sure that the model which you have selected is chemically
compatible with the application liquids.
Make a Fail-Safe System : Design a fail-safe system that accommodates the possibility of
transmitter failure or battery power loss. In critical applications, Levelpro recommends the use
of redundant backup systems and alarms in addition to the primary system.
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
8
GETTING STARTED
Pressure transmitters are designed to be completely
submersed within the application fluid. The transmitters
can either rest along the bottom of the tank or be
suspended at any desired level within the tank. Please
note that the physical location of the level transmitter
will indicate the lowest level of measurement within the
tank. For example: mounting the transmitter 2 feet from
the bottom of the tank, then the lowest reading of liquid
will be 2 feet from the bottom.

How to convert Pressure into Liquid Height?
Pressure transmitters are all defined by the pressure range or
distance range. To convert pressure to Liquid Height, use the
following ratio:
1 psi = 2.31 feet of water
or
1 psi = 0.704 meters of water
10 psi x 2.31'/psi = 23.1'
or
23.1'/2.31 = 10 psi
Therefore,a 10 psi transmitter will have a
Liquid Height = 23.1 feet
With the above ratio, you can always find the Liquid Height or
Water Column (wc) of any Levelpro pressure transmitter
1 psi
2.31 Feet (S.G.)
4-20mA | 0.5-4.5V
Output
H2
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
9
Water has a SG = 1.0.
A SG <1.0 required more liquid (a taller water column) to equal the same pressure or height as with water.
A SG >1.0 requires less liquid (shorter water column) to equal the same pressure or height as with water.
SG = .0
Water H20 SG = 1.2SG = 0.9
How does Specified Gravity affect pressure transmitters?
The Specific Gravity (SG) of a liquid will not change the pressure of the transmitter, but will affect how
the transmitter reads the liquid height. Remember, liquids with a SG < 1.0 are lighter than water
ex.Oil and liquids with a SG > 1.0 are heavier than water ex. Sulphuric Acid

Levelpro sensors are provided in distance measurement ranges i.e. 0-14 ft, 0-20 ft, 0-33 ft etc. To
calculate the maximum range or the liquid that a particular sensor will measure, use the following
Example : 0-14 ft transmitter installed in a liquid with a maximum height of 12 feet and a SG=0.9 will
have a Sensor Height with a range 0-14' = 14 feet /0.9 = 15.5'…so it can measure more liquid than
the 14' range due to the SG being below 1 (H20 water)
Example : Compare the Maximum Liquid Height of a liquid with a SG = 1.5.
SG = 1.5: 0-20' Range transmitter will have a Maximum Sensing Height (Liquid) = 20/1.5 = 15 ft
SG = 1.0: 0-20' Range transmitter will have a Maximum Sensing Height (Liquid) = 20/1 =20 ft
When the Specific Gravity is less than 1.0, the Maximum Liquid Height of the transmitter will
increase. The reverse is true by increasing the Specific Gravity. With a SG = 1.5, the Maximum
Sensing Height (Liquid) = 15' with a Transmitter with a Range of 0-20 ft Transmitter
Note: Identifying the correct specific gravity for the fluid is critical in understanding the
operational range of the pressure transmitter.
Maximum Liquid Height (feet) = Maximum Liquid Height of Liquid / SG
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
10
This method works with the Levelpro Series level displays & controllers . These panel meters are
configured using the linear SCALE function. The settings are as follows:
Remember, pressure transmitters are configured so 0 psi/ft = 4mA | 0.5V and the maximum psi/ft =
20mA | 4.5V. Levelpro pressure transmitter applications will not use the full range of the
transmitter. Therefore, a full tank will typically have a current less than 20mA | 4.5V.
Note: The values for empty and full represent what the display will show when the tank is
either Empty or Full. Empty and Full must be the same units ex: Gallons, Inches,
percent.
Settings Default Represents Typical Setting
20.0 | 4.5 Display Value @ FullDisplay 2 | Full
Input
4.0 | 0.5 Input Current @ Empty 4mA | 0.5V
Display 1 | Empty 4.0 | 0.5 Display Value @ Empty Empty Value
Input 2
20.0 | 4.5 Input Current @ Full 20mA | 4.5V
Full Value
How to configure a panel meter when a pressure transmitter is used?

Note: Use caution when sealing the cable at the top of the tank. There is a ventilation/reference tube located within
the cable. The purpose of this tube is provide a comparison between atmospheric pressure and the pressure that is
being exerted on the sensing diaphragm within the tank. The reference tube must be open and free to allow air to
flow back to the pressure diaphragm. Avoid blocking or bending the ventilation tube by compressing the
cable. Always keep the cable termination clean, dry and free of moisture and prevent liquid from entering the
vent tube. The LP100 Installation Junction Box comes with a Gortex breather to allow for air to pass but not
moisture. It also has the cable grip located at the bottom to secure the sensor.
INSTALLATION
The Levelpro Series is designed to operate while submerged in the actual application
liquid.Avoid installing the level transmitter along the bottom of the tank if materials such
as sludge will build up and coat/cover the transmitter.This also includes any debris that
will settle along the bottom of the tank. In these applications,it is best to suspend the
transmitter above the highest level of sludge/debris that will occur.
Location: Select a location where the temperature of the transmitter will be within
the specification of the sensor.
Position:The transmitter is not position sensitive.
Mounting:The transmitter can be mounted via several methods. It can be
suspended from the cable, it can be placed resting on the bottom of the tank in
either horizontal or vertical orientation,or it can be attached to a pipe or
hardwired using the LP100 | LCJB conduit box on the top of the housing.
Avoid installations where other tank requirements will cause the transmitter to move
or swing. Example: A mixer blade could cause the level transmitter to whip around
within the tank. An alternative would be to move the transmitter to a more stable
section of the tank or to install the Transmitter inside a still well/drop tube. This will
minimize the effects created by the mixer. Termination: The cable for the transmitter
is typically terminated at a junction box located on top of the tank. Since the vent
tube is contained within the cable, the pressure within the junction box must always
be the same as the reference (typically atmospheric) pressure for the liquid. The
inside of the function box must be clean, dry and free of moisture. (A descant can be
provided) Add the optional fitting LP100 | LCJB to complete the package. The
LP100 | LCJB features a 2" NPT thread for mounting and a liquid tight connector to
seal the cable interface, and a Gortex breather that allows for the transfer of air, but
not moisture.
1.
2.
3.
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
11
SLUDGE
Gortex Breather
Cable Grip
4-20mA | 0.5-4.5VDC
Output
LP100

After final installation of the Levelpro transmitter and its companion receiver (TruVu), no routine
maintenance is required. A periodic check of system calibration is suggested. Be sure to include a
brief description of the problem plus any relevant application notes. Contact customer service to
receive a return goods authorization number before shipping.
Maintenance should consist of inspection to see that the transmitter is free from debris and not
coated with any substance, which would prevent liquid from freely entering and leaving the
transmitter. If this occurs, the transmitter should be cleaned.
If transmitter is not functioning properly, isolate the transmitter from the system and wire as
shown below. Be sure to remove the sensor from the classified area when preforming this
test. Multi Meter should read 4 mA with the transmitter out of liquid.
1. First, verify that the sensor is wired correctly.
2. Next, check if the power supply is providing the required power.
3. Finally confirm that the loop resistance is not exceeding the sensor's specification.
MAINTENANCE
Troubleshooting the Transmitter
mA com
4.0
VDC Power
Supply
Multimeter
Vent
Shld
(+)
(-)
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
12
V com
0.0
VDC Power
Supply
Multimeter
Vent
Shld
(+)
(-)
V Out

Products cannot be returned to Icon Process Controls without Icon's prior authorization.Toreturn a
product that is thought to be defective please submit a customer return (MRA) request form and follow the
instructions therein. All warranty and non-warranty product returns to Icon Process Controls must be
shipped prepaid and insured. Icon will not be responsible for any products lost or damaged in shipment.
For complete product documentation,video training,and technical support,go to
www.iconprocon.com or contact us at 905 469 9283
(Please make sure you have the Part and Serial number available)
WARRANTY, RETURNS & LIMITATIONS
Icon Process Controls warrants to the original purchaser of its products that such products will be free
from defects in materials and workmanship under normal use and service in accordance with instructions
furnished by Icon Process Controls for a period of one year from the date of sale of such products. Icon
Process Controls obligation under this warranty is solely and exclusively limited to the repair or
replacement, at Icon's option, of the products or components, which Icon determines after examination
to be defective in material or workmanship within the warranty period.
Icon Process Controls must be notified within thirty (30) days pursuant to the instructions below of any
claims of lack of conformity under this warranty . Any product repaired under this warranty will be
warranted only for the remainder of the original warranty period. Any product provided as a replacement
under this warranty will be warranted for the full 1 year from the data of sale.
Returns :
Limitations :
This warranty does not apply to products which :
1) Are beyond the warranty period or are products for which the original purchaser does not follow
the warranty procedures outlined above;
2) Have been subjected to electrical, mechanical or chemical damage due to improper, accidental or
negligent use;
3) Have been modified or altered.
4) Anyone other than service personnel authorized by Icon have attempted to repair;
5) Have been involved in accidents or natural disasters;or
6) Are damaged during return shipment to Icon.
Icon Process Controls reserves the right to unilaterally waive this warranty and dispose of any
product returned to Icon where :
1) There is evidence of a potentially hazardous material present with the product;or
2) The product has remained unclaimed at Icon for more than 30 days after Icon Process Controls has
dutifully requested disposition. This warranty contains the sole express warranty made by Icon in
connection with its products. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY
DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the
breach of this warranty. IN NO EVENT SHALL ICON PROCESSS CONTROLS LTD BE LIABLE FOR
ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL
PROPERTY OF FOR INJURY TO ANY PERSON.THISWARRANTY CONSTITURESTHE FINAL,COMPLETEAND
EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY
OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF ICON PROCESS CONTROLS LTD
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
13

Specification may be modified without notice in advance.
For More Information Visit www.iconprocon.com
Heavy Duty Industrial Level Transmitter
Levelpro-Sensors Manual
This manual suits for next models
2
Table of contents
Other Level Pro Accessories manuals
Popular Accessories manuals by other brands

Fozmula
Fozmula L13X Calibration instructions

Trio Datacom
Trio Datacom EB450 quick start guide

Parker Pneumatic
Parker Pneumatic MPS-1 Series Installation & service instructions

Philips
Philips CRP323 brochure

Lightolier
Lightolier Lytespan 24MHT4RS specification

Banner
Banner Registration Mark Sensor R58 Expert brochure

HBM
HBM T10FM Mounting instructions

KAPSULE
KAPSULE UV-C SANITIZER manual

HomeMatic
HomeMatic HM-WDS100-C6-O-2 Mounting instruction and operating manual

Crestron
Crestron AirBoard CCS-WB-1 Supplemental guide

Cardinal
Cardinal 205 Installation and technical manual

SKY-WATCHER
SKY-WATCHER Star Adventurer 2i instruction manual