Start Temperature: specifies the minimum temperature value of the collector from which the
control starts. The unit of measurement is degrees Celsius.
Differential Temperature: specifies how many degrees the water in the collector must be
warmer compared to the tank in order for the rotary pump to start. The unit of measurement
is degrees Celsius.
Motor Overrun Sec: we can set the pump running time after the temperatures have
equalized so that the hot water does not get stuck in the pipes. The unit is seconds.
Display Time Internal Temp Sec: the value measured by the two sensors alternates on the
display and with this parameter we can set how many seconds the temperature in the tank is
displayed. At this value, a dot appears on the display. The unit is defined in seconds.
Display Time External Temp Sec: the value measured by the two sensors alternates on
the display and with this parameter we can set how many seconds the temperature in the
solar collector is displayed. The unit is defined in seconds.
Low Temperature (Filled with antifreeze): if the temperature in the solar collector falls below
this value, the controller starts the pump to circulate the liquid to prevent freezing. This value
is taken into account if the system is loaded with antifreeze and the “Without antifreeze”
mode is not checked in the parameters.
Low Temperature Hysteresis(Filled with antifreeze): this value determines by how many
degrees the system must warm back up from the value specified in the Low temperature
parameter, in order for the freezing error signal to disappear.
Temperature Without Antifreeze (Without antifreeze): the same as the Low temperature
parameter, only in this case the system is not filled with antifreeze, because of this there is
already a risk of freezing below 0 degrees. Even with the value set here, we receive an error
message and the pump will run continuously until the specified value plus its hysteresis
value is reached.
Temperature Hysteresis Without Antifreeze (Without antifreeze): in the case that the
system is not filled with antifreeze liquid, the temperature of the Without Antifreeze mode
and its sum will be the value that, if the temperature of the solar collector is reached, the
pump will turn off.
Dangerously High Temperature: is the value that, when the temperature of the solar
collector is reached, the controller sounds an alarm and the Error LED lights up. Together
with these, the pump also comes into operation. Furthermore, if the email notification is
enabled and set, the controller will send the error signal to the specified email address. Its
unit is degrees Celsius.
Dangerously High Temperature Hysteresis: the Dangerously High Temperature and the
difference of this value gives the value where the sound signal stops, but the Error LED and
the pump still work.