LG LRE30451S User manual

Installation Manual
Electric Range
LRE30451S / LRE30755S
Please read these instructions thoroughly before
installing and operating the range.
P/No.: 3828W5U0512
Website: http://us.lge.com

2
PARTS PROVIDED
1BEFORE YOU BEGIN
Remove all tape and packing materials before using
the range. Dispose all plastic bags after unpacking the
range. Never allow children to play with packing
materials.
IMPORTANT SAFETY INSTRUCTIONS
WARNING If the information in this manual is
not followed exactly, a fire or electrical shock may
result causing property damage, personal injury or
death.
WARNING
• ALL RANGES CAN TIP
• INJURY TO PERSONS COULD
RESULT
• INSTALL ANTI-TIP BRACKET
PACKED WITH RANGE
• SEE INSTALLATION
INSTRUCTIONS
Important Notes to the Installer
• Read all instructions contained in these installation
instructions before installing range.
• Remove all packing materials from the oven
compartments before connecting the electrical
supply to the range.
• Observe all governing codes and ordinances.
•
Be sure to leave these instructions with the consumer.
Important Note to the Consumer
Keep these instructions with your owner’s manual for
future reference.
• As when using any appliance generating heat, there
are certain safety precautions you should follow.
• Be sure your range is installed and grounded
properly by a qualified installer or service technician.
• Make sure the wall coverings around the range can
withstand the heat generated by the range.
• To eliminate the need to reach over the surface
elements, cabinet storage space above the elements
should be avoided.
TOOLS NEEDED
Part 1 SAFETY
PREPARE TO INSTALL THE RANGE
PARTS NOT PROVIDED

3
INSTALLATION DRAWINGS
IMPORTANT
SAVE FOR THE USE OF THE LOCAL ELECTRICAL INSPECTOR.
CLEARANCES AND DIMENSIONS (Figure 1)
To install range refer to the following Figure 1.
For installation in CANADA, a Free-standing range is not to be installed closer than 12 mm from any
adjacent surface.
MINIMUM DIMENSIONS (Figure 2)
* 30”(76.2 cm) minimum clearance between the top of the cooking surface and the bottom of an
unprotected wood or metal cabinet; or 24”(60.9 cm) minimum when bottom of wood or metal cabinet is
protected by not less than 1/4”(6.4 cm) flame retardant millboard covered with not less than no. 28 MSG
sheet steel, 0.015”(0.381 mm) stainless steel, 0.024”(0.610 mm) aluminum or 0.020”(0.508 mm) copper.
** 15”(38.1 cm) minimum between countertop and adjacent cabinet bottom.
2
FIGURE 1 FIGURE 2
A = 30”(76.2 cm) For U.S.A
= 30”(76.2 cm) ~ 31”(78.7 cm) For CANADA
Part 2 PREPARE TO INSTALL THE RANGE
CAUTION
This range has been designed to
comply with the maximum allowable wood cabinet
temperatures of 194°F. Make sure the wall
covering, countertop and cabinets around the range
can withstand the heat (up to 194°F) generated by the
range. If not discoloration, delamination or melting
may occur.
IMPORTANT
To eliminate the risk of burns
or fire by reaching over heated surface units,
cabinet storage space located above the surface
units should be avoided. If cabinet storage is to be
provided, the risk can be reduced by installing a
range hood that projects horizontally a minimum of
5 inches beyond the bottom of the cabinets.

3, 4 - Wire electrical wall Receptacle types
Conduit connection plate is used for the installation of
power cord or conduit. For power cord, install it with
conduit connection plate as manufacturer supplied.
For conduit cord, remove the conduit connection plate
located below the rear of the drawer body and use the
conduit hole (11/8”) instead of power cord hole (13/8”).
(Refer to Figure 8.)
4
3
CONNECT RANGE CORD
The Rear Access cover must be removed. Loosen the
three screws with a screwdriver. The terminal block
will then be accessible.
4
FIGURE 3
FIGURE 4
Range rating, watts
Specified rating
of power-supply-
cord kit, amperes
120/240 volts
3-wire
8,750 - 16,500
16,501 - 22,500
120/208 volts
3-wire
7,801 - 12,500
12,501 - 18,500
40 or 50A
50
Diameter (inches) of Range
connection Opening
Conduit
11/8”
11/8”
Power cord
13/8”
13/8”
Specified power-supply-cord kit rating
Part 3 ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTION
REQUIREMENTS
This appliance must be installed and grounded on a
branch circuit by a qualified technician in accordance
with the National Electrical code ANSI/NFPA NO. 70 -
latest edition.
All wiring should conform to Local and NEC. This
range requires a single-phase, 3 wire, A.C 120/208V or
120/240V 60Hz electrical system. Use only a 3-conductor
or a 4-conductor UL-listed range cord with closed-
loop terminals, open-end spade lugs with upturned
ends or similar terminations. Cord must have the
strain relief properly installed.
A range cord rated at 40 amps with 120/240 minimum
volt range is required. If a 50 amp range cord is used,
it should be marked for use with 13⁄8” diameter
connection openings.
This appliance may be connected by means of conduit
or power cord. If conduit is being used, go to page 6
3 wire conduit connections or page 7 for 4 wire
conduit connections.
WARNING
New branch-circuit installations (1996 NEC), mobile
homes, recreational vehicles, and installations
where local codes do not allow grounding through
neutral require a 4-conductor UL listed range cord
or 4 wire conduit connection.
4 Wire receptacle (14-50R)
3 Wire receptacle (10-50R)

5
Install the power cord as follows:
For power cord installations, Hook the strain relief
over the power cord hole (13/8”) located below the rear
of drawer body. Insert the power cord through the
strain relief and tighten it. (Refer to Figure 5.)
You must install the power cord with a strain relief.
1. Remove the lower 3 screws from the terminal block
and retain them. (Refer to Figure 6.)
2. Insert the 3 screws through each power cord
terminal ring and into the lower terminals of the
terminal block.
Make sure that the center wire (white/neutral) is
connected to the center lower position of the
terminal block.
3. Tighten 3 screws securely into the terminal block.
Do not remove the ground strap connections.
4. Go to page 8.
Part 3 ELECTRICAL CONNECTIONS
WARNING
The middle (neutral or ground) wire of the power cord or
3-wire conduit has to be connected to the middle post of
the main terminal block. The remaining two wires of the
power cord or conduit have to be connected to the
outside posts of the main terminal connection block.
WARNING
Only a 4-conductor power-supply cord kit rated
120/240 volts, 50 amperes and marked for use with
ranges with closed-loop connectors, open-end spade
lugs with upturned ends shall be used. The middle
(neutral) wire of the power cord or 4-wire conduit has
to be connected to the middle post of the main terminal
block. Other two wires of the power cord or conduit
have to be connected to the outside posts of the main
terminal connection block. The 4th ground wire must
be connected to the frame of the range with the ground
screw.
FIGURE 5
FIGURE 6
3-wire connection
Assemble the strain relief
to the 1
3/8” opening in
Conduit connection plate
Separate Strain Relief
before installation
3-wire connection with a power supply cord
4-wire connection with a power supply cord

6
Part 3 ELECTRICAL CONNECTIONS
Follow the instructions under “Install the power cord as
follows” on page 5 to correctly install the strain relief.
1. Remove the lower 3 screws from the terminal block
and retain them. (Refer to Figure 7.)
Remove the ground screw and retain it.
2. Remove ground strap and discard as shown
in Figure 7.
Do not discard any screws.
3. Insert the ground screw into the power cord ground
wire terminal ring and secure it to the range frame.
4. Insert the 3 screws through each power cord
terminal ring and into the lower terminals of the
terminal block. Make sure that the center wire
(white/neutral) is connected to the center lower
position of the terminal block.
Tighten 3 screws securely into the terminal block.
5. Go to page 8.
Install the conduit as follows:
Remove the Conduit connection plate from the rear of
drawer body and rotate it as shown in Figure 8. The
conduit hole (11/8”) must be used.
First, prepare conduit wires as shown in Figure 9.
Second, install conduit as shown in Figure 10.
For conduit installations, after purchasing a strain
relief, insert it in the conduit hole (11/8”). Then install
the conduit through the body of strain relief and
fasten the strain relief with its ring. Reinstall the
bracket.
For conduit connections :
If the wire in the conduit is copper it must be 8 or 10
AWG wiring.
If the wire in the conduit is aluminum it must be 6 or 8
AWG wiring.
FIGURE 9
FIGURE 8
FIGURE 10
Remove the Conduit connection plate
Assemble the
strain relief hole
3-wire connection: conduit
or
3 wire 4 wire
Reinstall the
Conduit connection plate
FIGURE 7
4-wire connection

7
Part 3 ELECTRICAL CONNECTIONS
1. Loosen the lower 3 screws from the terminal block.
(Refer to Figure 11.)
2. Insert the bare wire (white/neutral) end through the
center terminal block opening.
Do not remove ground strap connections.
3. Insert the two side bare wire ends into the lower left
and the lower right terminal block opening.
Tighten the 3 screws securely into the terminal block.
(approximately 35 - 50 IN-LB)
4. Go to page 8.
1. Follow the instructions under “Install the conduit as
follows” on page 6 to correctly install the strain
relief.
You must install the conduit with a strain relief.
2. Loosen the 2 lower left and right screws from the
terminal block. (Refer to Figure 12.)
Remove the lower 2 center screws.
3. Remove ground strap and discard as shown
in Figure 12.
Do not discard any screws.
4. Attach the ground bare wire end to range frame
and secure it in place with the ground screw (Refer
to figure 12.)
5. Insert the bare wire (white/neutral) end through the
center terminal block opening.
6. Insert the two side bare wire ends into the left and
the right terminal block opening.
Tighten the 3 screws securely into the terminal
block. (approximately 35 - 50 IN-LB)
7. Go to page 8.
FIGURE 11
3-wire connection
FIGURE 12
4-wire connection
4-wire connection: conduit

Replace the access cover on the range back. To
replace the wire cover, insert double projections in the
pockets located below the opening and tighten the
three screws.
ANTI-TIP DEVICE INSTALLATION
Note
To install Anti-tip bracket, release the leveling leg. A
minimum clearance of 0.65”(16.5mm) is required
between the range bottom and the kitchen floor.
1. Locate the bracket using the template
An Anti-tip bracket is packaged with template. The
instructions include necessary information to
complete the installation.
Read and follow range installation instruction sheet
(template).
2. Level the range
Level the range by adjusting the leveling legs with a
wrench.
WARNING
• To reduce the risk of tipping, the appliance must be
secured by properly installed anti-tip devices packed
with the appliance.
• See instructions to install (supplied with bracket).
• Unless properly installed, the range could be tipped
by stepping or sitting on the door. Injury may result
from spilled hot liquids or from the range itself.
8
Use a spirit level to check your adjustments. Place the
level diagonally on the oven rack, and check each
direction for level.
First check direction 1.
After check direction 2.
If the spirit level doesn’t show
level on the rack, adjust the
leveling legs with a wrench.
FINAL INSTALLATION
• Move range close enough to the opening to plug
into the receptacle.
• Slide range into position insuring that the left back
leg slides under the anti-tip bracket. Range will sit 0”
away from the back wall when properly installed.
• Carefully tip range forward to insure that the anti-tip
bracket engages the range back brace and prevents
tip-over.
• Turn on electrical power. Check range for proper
operation as described in owner’s manual.
5
6
Part 4 INSTALL THE RANGE
Other manuals for LRE30451S
1
This manual suits for next models
1
Table of contents
Other LG Range manuals