
Digital Countertop Service Manual
14
breaker is not open and still no secondary voltage
then replace transformer.
Solid State Relay
Check for 24VAC at terminals A1 and A2 of the
Solid State Relay(SSR). If no voltage is present
then perform thermocouple checks(Thermocouple
type j testing). If thermocouple checks good and
still no voltage at terminals A1 and A2 then
replace control board.
Heating Element
If 24VAC is present at output of SSR but no heat
check for 208/240 at element terminals. Check
amp draws at each supply line.
208V oven is rated at 29 amps. Element is 5600W
with a cold ohms reading between 8.51 to 7.36.
240V oven is rated at 24 amps. Element is 5600W
with a cold ohms reading between 11.33 to 9.81.
If voltage is present but no amp draw replace
element.
208V Red,240V Blue,220V Yellow,200V
Orange, 380V Violet,400V 1 PH Brown,415V
Green, 200V 3 PH Orange,380V 3 PH Violet,
400V 3 PH Brown, 415V 3 PH Green
Oven will not heat
Thermocouple type j testing
WITH POWER ON AND THERMOCOUPLE
ATTACHED TO THE OVEN CONTROL:
Measure the DC millivolt output of the
thermocouple. Refer to the chart below for
readings. If these are not achieved, replace
thermocouple.
TEMP.°F (°C) D.C. MILLIVOLTS (APPX)
200 (93) 3.4
250 (121) 4.9
300 (149) 6.5
350 (177) 8.0
400 (204) 9.5
450 (232) 11.1
500 (260) 12.6
550 (288) 14.2
600 (316) 15.7
Temperature Probe
Placement
To verify the oven cavity temperature, insert your
temperature meter probe tip under the conveyor
and approximately 3/8“(10mm) into the bottom
finger #4, 3rd row from outside edge, 3rd hole from
the rear.
This process is also used when calibrating the
oven temperature. Allow temperature in oven to
stabilize for 30 minutes before calibrating.
Note: For best result, we recommend
disconnecting the conveyor drive coupling to stop
the conveyor from moving.
Conveyor will not run
Control Transformer
With the Main Fan Switch(S) on, check for
208/240VAC at the primary of the transformer.
If no voltage is present, check for voltage at the