Listec SCU 800 User manual

SCU 800
d-LIST Control Unit
The sensor control unit SCU 800 is the central
supervisory element for the d-LIST-system. It provides
up to two d-LIST sensor cables with power performs
the cyclic addressing of the connected sensors every
10 seconds acquires the temperature values
measured by each sensor and evaluates the data with
reference to various criteria.
A fire alarm is generated if either a given maximum
threshold is exceeded or if an increase in temperature
takes place within a certain time (differential
evaluation). The two thresholds (set-points) can be set
individually for each of the attached sensor cables.
The measurement resolution of 0 1° gives the system a high sensitivity. The tried and tested algorithms used in
the evaluation eliminate false alarms due to natural temperature variations.
Alarms are indicated by LEDs on the front-panel and via floating contacts to a fire terminal station (fire control
panel) host computers or other transmission systems. Hereby alarms generated by the two sensor cables are
signalled individually.
Resetting takes place via an external signal from the fire terminal station or by pressing the front-panel mounted
reset button.
The serial RS-232 interface can be used for programming and setting of system parameters. LISTEC® GmbH
offers the terminal software LISTterm 8 for this purpose.
For the visualisation of the system status message- and temperature-lists as well as a graphic display of the
temperature and alarm data LISTgraph II and the Data Management Unit DMU 600 is available.
A LIST®controller can be used to connect and control several SCU 800 from a central point via a RS-485
interface.
1/2 60V041-06/ 02.12.13
General:
Collective display (LED's) or
Fire cable A
Fire cable B
Fault
Operation
Temperature measurement
Data transmission
Alarm criteria
Alarming due to the exceeding of an absolute- or a
differential-threshold (set-point). All thresholds are
individually settable for each sensor cable.
For both alarm criteria a pre-alarm can be set in the
range between 10 to 90% of the alarm thresholds.
Fault recognition
Sensor cable faults such as the malfunctioning of a
sensor or a cable break are recognised and
indicated within one measuring cycle generally
within 10 seconds. Faults in the control unit are
registered in the internal message list and are
signalled immediately.
Inter ace
RS-232 Serial-interface for programming
parameters and interrogation of system data.
Optionally a RS-485 interface.
Connections
All connections take place inside the unit via
terminals.
The RS-232 interface 9 pin D-Sub female is
accessible once the unit is opened.
System speci ications:
Number o measuring points
Max. 99 sensors per cable connection
Sensor cable length
Max. overall length of the sensor cable including
connection cables is 250 m.
The sensor cable may consist of separate cable
pieces
Delivery extent:
CD with data sheet operation manual description
of commands and system messages installation
guidelines
Serie 800
SCU800/3 Item number: G00231 SCU800/16 Item number: G00233
Continuous operating temperature: -10°C .. +60°C
Dimensions: 260 x 150 x 90 mm
Power supply: 21 – 29 VDC
Housing material: aluminium
Power consumption: 21 – 29 VDC
Weight: 1 9 kg Weight: 2 3 kg
Power consumption: (normal use) 1 9 W Power consumption: (normal use) 2 7 W
Outputs:
Floating change-over contacts with space for user defined supervisory
resistors:
Fire alarm 2 relays (1 per cable)
Fault alarm 1 relay (fail safe)
Outputs:
Floating change-over contacts with space for user defined supervisory
resistors:
Fire alarm 16 zonal relays
Fault alarm 1 relay (fail safe)
Switching voltage: 48 VDC / 32 VAC max.
Switching current: 250 mA max. (ohmsche Last)
Input: 5 VDC reset input galvanically isolated
2/2 60V041-06/ 02.12.13

This manual suits for next models

2

Popular Control Unit manuals by other brands

Zator DLK22S User and maintenance manual

Zator

Zator DLK22S User and maintenance manual

CALEFFI 359 Series manual

CALEFFI

CALEFFI 359 Series manual

Vega VEGAKON 66 operating instructions

Vega

Vega VEGAKON 66 operating instructions

Linear Technology LTM8021 manual

Linear Technology

Linear Technology LTM8021 manual

A.R.I. Eliptix R-20 MF Installation operation & maintenance

A.R.I.

A.R.I. Eliptix R-20 MF Installation operation & maintenance

Johnson Controls Y20EBD Series Technical bulletin

Johnson Controls

Johnson Controls Y20EBD Series Technical bulletin

Viessmann 5205 Operation manual

Viessmann

Viessmann 5205 Operation manual

LG LGSBWAC03 user manual

LG

LG LGSBWAC03 user manual

PERSTA 808 GJ operating instructions

PERSTA

PERSTA 808 GJ operating instructions

VIPA System SLIO IM 053DN manual

VIPA

VIPA System SLIO IM 053DN manual

GDH Air Series user guide

GDH

GDH Air Series user guide

Perry Electric Smartbox Wi-Fi user manual

Perry Electric

Perry Electric Smartbox Wi-Fi user manual

Bosch Rexroth M-2SMM6 SO711 Series operating instructions

Bosch

Bosch Rexroth M-2SMM6 SO711 Series operating instructions

IMET B014 Technical manual

IMET

IMET B014 Technical manual

Wilo Wilo-Control EC-Drain PD1 Installation and operating instructions

Wilo

Wilo Wilo-Control EC-Drain PD1 Installation and operating instructions

Linksys WM821-M-LS user manual

Linksys

Linksys WM821-M-LS user manual

BHI NEDSP1061-KBD Installation and operating manual

BHI

BHI NEDSP1061-KBD Installation and operating manual

Beckhoff TwinSAFE EJ Series Operation manual

Beckhoff

Beckhoff TwinSAFE EJ Series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.