
P
PP
Pa
aa
ag
gg
ge
ee
e
1
11
1
OPERATION AND INSTALLATION INSTRUCTION
WOK TABLE: LKK-D SERIES (Duckbill burner)
LKK-C SERIES (Chimney Burner)
OPERATION INSTRUCTIONS:
These instructions should be read carefully prior to operating your Wok table
LIGHTING UP OF APPLIANCE: (AW20 Valve)
1Ensure the gas valve lever is in the horizontal position as indicated on the panel "OFF"
2. Turn pilot control knob to "ON" position (HIGH)
3. Depress round D-3 button and light pilot, hold button in for at least 20 sec. (on new
installations you may have to hold the button longer to allow air in pipes to purge out for several
minutes)
4. Release button when pilot light is established
5. Turn the main burner on by moving lever to “ON” position. (If pilot fails to remain alight when
main burner ignites turn main burner lever to the OFF position, wait 30 seconds and repeat step 3
(check aeration for correct flame setting)
6. To shut down appliance, turn pilot control knob to off position
LIGHTING UP OF APPLIANCE: (A63C Valve)
1Ensure the gas valve lever is in the horizontal position as indicated on the panel "OFF"
2. Depress the main gas valve and light the pilot. Hold lever in for at least 20 sec. (on new
installations you may have to hold the button longer to allow air in pipes to purge out for several
minutes)
3. Release lever when pilot light is established
4. Turn the main burner on by moving lever to “ON” position. (If pilot fails to remain alight when
main burner ignites turn main burner lever to the OFF position, wait 30 seconds and repeat step 2
(check aeration for correct flame setting)
5. To shut down appliance, push the lever in half way and turn handle clockwise approximately
30 degrees. Once off return the lever back to the off position.
INSTALLATION: (By authorised personnel only)
Gas point entry is 520mm above floor and located on the right hand side of the appliance at the rear
of the unit. A regulator is supplied with the unit for each burner
Bromic/Oara 980L AGA#5862 (Natural Gas)
Bromic/Oara 986L AGA#5862 (L.P.G)
Maxitrol, RV48 AGA#3088 (Natural Gas)
Maxitrol, RV48 AGA#3088 (L.P.G)
The installer must fit an isolating gas valve to the appliance for ease of servicing.
Check alignment of burner injector to pilot flame to insure burner ignition prior to use.
The appliance installation must comply with the installation requirements of AG 601, AS 5601,
Australian Standard, “Gas Installations” any local Authority regulation and the Manufacturer’s
installation instructions.
Warning: Please do not install LKK woks in marine environment. Some examples include on a boat
or outdoor in the sea breeze. Doing so will result in unnecessary rust.
*Please remove all packaging prior to installation*’
CLEARANCES AND PROTECTION AROUND COMMERCAIL CATERING EQUIPMENT
The clearance to combustible surfaces from commercial catering equipment shall comply with the
requirements of the appliance manufacturer
- From a cooking surface area having an open flame and no means of preventing cooking vessels
from overhanging the edge of the appliance 250mm
- From the side of an open flame appliance where the combustible surface is at least 100mm
below a cooking surface area
- From an appliance flue way or rear of an appliance with a ‘splash back’ 50mm