LONGHORN LHD8003 User manual

Arm Away
2 0 / 1 2 / 2 0 1 0
1 5 : 3 0
MGE Entreprise
Av. Kouwait - 8050 Hammamet
Tunisie
Tel.1: 00216 72 278 663
Tel.2: 00216 22 645 120
Email: [email protected]
www.mge-security.com/

CREATING SECURITY SOLUTION

User Name
User Address
Installer Name
Installation Company
Installation Date
Phone of Installation Company
Fax of Installation Company
Control Panel ID
Control Panel Phone NO.
CMS 1
CMS 1 Address
CMS 1 Phone NO.
CMS 2
CMS 2 Address
CMS 2 Phone NO.
SMS Center 1
SMS Center 1 Address
SMS Center 1 Phone NO.
SMS Center 2
SMS Center 2 Address
SMS Center 2 Phone NO.
INSTALLATION INFORMATION

Zone NO.
Installation Position
Type
Bypass or not
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
Item
Description
Quantity
1
Control Panel
1
2
Keyfob
2
3
Wireless PIR Detector
1
4
Wireless Magnetic Switch
1
5
Power Adaptor
1
6
Installation Manual
1
7
Accessory Bag
1
8
Installing Hole Drawing
1
Appendix 5: Zone Type Setting Figure
PACKING LIST
Note : It should include screws (4pcs ), EOL resistance (2.2K, 4pcs) and dowels (4pcs) in the accessory bag .
-59-

TABLE OF CONTENTS
Chapter 1 : Introduction ------------------------------------------------------------------------ 3
Chapter 2 : Specifications --------------------------------------------------------------------- 3
Chapter 3 : Hardware Layout ------------------------------------------------------------------ 4
3.1. Main Board ---------------------------------------------------------------------------------------------------- 4
3.2. Power Supply Board ----------------------------------------------------------------------------------------- 5
Appendix 4: Ter m Definitions
◆Detector: A facility that detects intrusion and abnormal state automatically via some electric or
physical methods and output switch signals or wireless signals to the system for disposal, then output
alarm signals, such as infrared detector, smoke detector, etc.
◆Zone: An area of the detection range of one or one group detectors.
3.3. GSM Module -------------------------------------------------------------------------------------------------- 5 ◆Bypass: Close one of the zones temporarily, so that it can not alarm while act in the zone.
Chapter 4 : System Installation --------------------------------------------------------------- 6
4.1. Pre-installation Planning ------------------------------------------------------------------------------------
4.2. Wireless Installation Guidelines ---------------------------------------------------------------------------
4.3. Installation Procedure ---------------------------------------------------------------------------------------
4.3.1. Open the Housing ------------------------------------------------------------------------------------
4.3.2. Power off and Insert SIM Card ---------------------------------------------------------------------
4.3.3. External Devices Connection ----------------------------------------------------------------------
4.3.4. Power Connection ------------------------------------------------------------------------------------
4.3.5. Register Transmitters --------------------------------------------------------------------------------
4.3.6. Testing the Chosen Mounting Location -----------------------------------------------------------
4.3.7. Installing the Control Panel -------------------------------------------------------------------------
6
6
7
7
8
8
10
11
11
11
◆Arm Away: The armed status while going out. All the zones without bypass are in armed status.
◆Arm Stay: The armed status at night. All the zones are in armed status except active zones.
◆Disarm: Close the entry/exit zones, active zones, perimeter zones. Other zones are still in arm status.
◆24 hour zone: No matter armed or disarmed, it is in valid detecting status. It is usually used in fire
alarm, duress alarm and other emergent alarm which can be cancelled only by password holder.
◆CMS: It is an alarm receiving station, to which the alarm controller sends out alarm information via
Chapter 5 : Operations ------------------------------------------------------------------------- 12 telephone line when alarm occurs. The station will take corresponding actions after receiving the alarm.
5.1. Front Panel Layout -------------------------------------------------------------------------------------------
5.1.1. Status LED ---------------------------------------------------------------------------------------------
5.1.2. Front Panel Keypad -----------------------------------------------------------------------------------
5.2. LCD Display ----------------------------------------------------------------------------------------------------
5.2.1. Standby Mode -----------------------------------------------------------------------------------------
5.2.2. Display Interface -------------------------------------------------------------------------------------
5.3. Alarm Type and Way ------------------------------------------------------------------------------------------
5.4. Keypad Lock and Unlock ------------------------------------------------------------------------------------
5.5. Codes Access -------------------------------------------------------------------------------------------------
5.6. System Trouble Query ---------------------------------------------------------------------------------------
12
13
13
13
13
14
16
17
17
18
◆Entry Delay: A period for user to enter detection area, activate the delay zone and disarm before the
system alarms. During the period, user can activate several specified zones (entry zone) without alarm
immediately. While exceeding the time, the system alarms if not disarmed. Zones with entry delay are the
exit/entry zone and active zone.
◆Exit Delay: A period for user to leave detecting area once the system armed. Zones with exit delay will
not alarm during this period. The zones with exit delay are the exit/entry zone and the active zone.
◆Supplementary Entry Delay: The Supplementary Entry Delay is a pre-alarm feature that is
employed in the event that the system is not disarmed during the entry delay.
Chapter 6 : Zone Descriptions ----------------------------------------------------------------- 19
6.1. Zone Type ----------------------------------------------------------------------------------------------------- 20
6.2. Zone Number -------------------------------------------------------------------------------------------------- 20
6.3. Chime Zone ---------------------------------------------------------------------------------------------------- 20
Chapter 7 : Arm/Disarm Operation ----------------------------------------------------------- 21
7.1. Arm/Disarm via Keypad or Keyfob -------------------------------------------------------------------------- 21
7.1.1. Arm Away ----------------------------------------------------------------------------------------------- 21
7.1.2. Arm Stay ------------------------------------------------------------------------------------------------ 22
◆Panel ID: ID address can be set for each control panel so that the CMS can identify. Different ID must
be set for different control panels, which is 4-8 digits utmost with default as 1234.
◆Duress Code: When user is forced to disarm the control panel by burglar, user inputs duress
password, the control panel is disarmed but sends alarm information to the center stations or receiver. The
duress password can be used to disarm but set parameters.
◆Chime Zone: During disarm, while the zone is triggered, the panel will sound “Welcome to intelligent
alarm system!”
58

CID Code
Definition
100
Panic Alarm
110
Fire Alarm
121
Duress Alarm
131
Perimeter Alarm
132
Active Alarm
134
Entry/Exit Alarm
137
Panel anti-tamper alarm or tamper zone alarm
151
Gas Alarm
301
AC Power Failure
302
Low Battery
311
Reset as Default
351
Line Loss
381
Detector Loss
384
Low Battery for Detector
401
Arm/Disarm
406
Cancel Alarm
441
Arm Stay
455
Auto Arm/Disarm Failure
521
Mute Siren
570
Zone bypass operation, Bypass all or cancel bypass for User 99
602
Test Report
627
Programming
CID Code
Definition
00
Operation using keypad without user code, such as arm-away, from disarm to arm-stay
01
Arm/disarm using master code, by keypad, phone or SMS
02
Program with installer code
03
Duress alarm by user 98,with “Disarm” indication on-site
04
Arm/disarm using temporary code, by keypad, phone or SMS
05~08
Arm/disarm using the correspondent user code, by keypad, phone or SMS
11~16
Arm/disarm by keyfob
21~24
Arm/disarm by phone number 1-4 during alarm
30
Auto arm/disarm
Appendix 3: Communication Protocol and Codes
Table 1: Contact ID Event Code
7.1.3. Disarm --------------------------------------------------------------------------------------------------- 23
7.2. Arm/Disarm via Phone ------------------------------------------------------------------------------------------- 24
7.3. Arm/Disarm via SMS ---------------------------------------------------------------------------------------------- 24
7.4. Trigger Alarm via Keypad ---------------------------------------------------------------------------------------- 24
Chapter 8 : Programming ------------------------------------------------------------------------- 25
8.1. Access Programming ------------------------------------------------------------------------------------------- 25
8.2. Quit Programming -----------------------------------------------------------------------------------------------
8.3. Programming -----------------------------------------------------------------------------------------------------
8.3.1. Cancel Alarm ---------------------------------------------------------------------------------------------
8.3.2. Stop Communication ------------------------------------------------------------------------------------
8.3.3. Code Set --------------------------------------------------------------------------------------------------
8.3.4 Zone Bypass ----------------------------------------------------------------------------------------------
8.3.5. Phone Set -------------------------------------------------------------------------------------------------
8.3.6. Event Log --------------------------------------------------------------------------------------------------
25
25
25
26
26
28
29
30
8.3.7. Service Option --------------------------------------------------------------------------------------------- 31
8.3.8. Programming Set ----------------------------------------------------------------------------------------- 34
8.3.8.1. Device ------------------------------------------------------------------------------------------- 34
8.3.8.2. Communication -------------------------------------------------------------------------------- 37
8.3.8.3. System Option ---------------------------------------------------------------------------------
8.3.8.4. Initialization ------------------------------------------------------------------------------------ 41
44
Chapter 9 : Telecontrol via Phone or SMS ----------------------------------------------------- 45
9.1. Telecontrol via Phone --------------------------------------------------------------------------------------------- 45
9.2. Dial to Alarm via Panel ------------------------------------------------------------------------------------------- 46
9.3. Telecontrol via SMS ---------------------------------------------------------------------------------------------- 46
9.4. Send SMS for Alarm ---------------------------------------------------------------------------------------------- 48
Chapter 10 : Parameters -------------------------------------------------------------------------- 49
10.1. Specifications ---------------------------------------------------------------------------------------------------- 49
Table 2: Contact ID Table of Event Codes 10.2. Electric Parameters ---------------------------------------------------------------------------------------------
10.3. GSM Module ------------------------------------------------------------------------------------------------------ 49
50
Chapter 11: Troubleshooting --------------------------------------------------------------------- 50
Chapter 12: Warranty and Limitations----------------------------------------------------------- 51
Appendix 1: System Default Parameters ------------------------------------------------------ 52
Appendix 2: Menu Structure --------------------------------------------------------------------- 53
Appendix 3: Communication Protocol and Codes ------------------------------------------- 57
Appendix 4: Term Definitions ------------------------------------------------------------------- 58
Appendix 5: Zone Type Setting Figure --------------------------------------------------------- 59
57
02

Chapter 1: Introduction
(To) 1. Devices
1. Zone
1. WL. Register
1. By Code Learn
2. By Code Input
Introduction:
Nowadays, homeowners want much more than a monitored security system. They prefer an alert system.
This wireless alarm kit offers an innovative all-in-one solution with all aspects of security and
connectivity covering a full range of wireless accessories.
Activating periodic supervision for accessories, it ensures system safety. Featuring PSTN, GSM dialing
or SMS send optional, it offers multiple performance options and the flexibility. With upload and
download software, you can load the data and remote program the system. It meets different ranges of
demand to personal phones or central station by easy programming and simple menu-operation with
2. Keyfobs
2. Clear WL.
3. Set zone Type
4. Zone Siren Set
5. Chime Zone Set
1. Keyfob Register.
2. Clear Keyfob
1. Clear Single
2. Clear All
1. By Code Learn
2. By Code Input
1. Clear Single
2. Clear All
voice guide.
Chapter 2: Specifications
3 Siren 1. WL. Siren Reg
2. Del. WL. Siren
3. Activate/Mute
4. Siren Cut-off(M)
1. By code Input
1. Del. Single
2. Del All
1. For Built-in
2. For Wired
Specifications : 4. WL. Superv. 1. SV. ON/OFF 3. For Wireless
2. Superv. Time
(Hr)
◆16 wireless zones and 2 wired zones
◆TFT LCD with menu display, intelligent voice-guide operation
◆Periodic supervision for wireless PIR and magnetic switch
◆PSTN or GSM dialing, or SMS message send for alarm optional
(To) 2. Communication
1. Comm. Account
1. CMS 1
2. CMS 2
1. Phone No.
2. Protocol
◆Upload and download function optional
◆255 event log with time indication
◆Built-in front and rear tamper for control panel
◆Compatible with built-in siren(85dB), wired external siren and 3 wireless sirens
◆1 PGM and AUX power output
◆2 central stations working selectable
3. SMS Center 1
4. SMS Center 2
5. Panel ID
3. Event Option
4. Interface
1. Phone No.
2. Event Option
1. Send for Alarm
2. Send for Arm/Disarm
3. Send for Sys. Trb.
4. Send for Service
1. Send for Alarm
2. Send for Arm/Disarm
◆6 phone numbers: 2 for CMS and 4 for personal phones(or mobiles)
◆8 codes: 1 for installer, 1 for master, 1 for temporary, 1 for duress and 4 for users 2. Comm. Option 1. Line Monitor
2. Test Interval
1. CMS 1
2. CMS 2
3. Send for Sys. Trb.
4. Send for Service
◆Available with utmost 6 keyfobs 3. First Test
◆Compatible with Contact ID protocol
◆Wireless frequency: 433MHZ/868MHZ 4. Call Attempts
5. Ring Attempts
6. GSM Option
7. CMS Coopertion
-56-
1. SMS Center
2. SMS Ack
3. SMS Confirm

7. Service
1. Set Time/Date
2. Auto Arm/Disarm
3.Call back when arm/dis.
1. Auto Time 1
2. Auto Time 2
3. Auto Time 3
Chapter 3: Hardware Layout
The aim of this section is to acquaint you with the various circuit boards that make up the system.
4. Auto ON/OFF
4. Siren Test
5. Walk Test
6. Transmitter
7. GSM Test
8. Audio
9. Version
1. Wired Test
2. WL. Test
3. Built-in test
1. Volume
3.1 Main Board
The main board is the brain of the system. It includes all interfaces for devices, such as wired zones, wired
siren, PGM output, AUX power output, built-in siren, external siren and telephone interface.
8. Programming
1. Device(To)
2. Comm.(To)
3. System Option
To 1. Zone
To 1. Comm. Account
To 2. Comm. Option
To 3. Remote Program
1. Entry Delay(S)
2. Exit Delay(S)
3. Supp. Ent. Delay
1. Dial BacK
2. RP Password
3. RP Interface
4. RP Permission
4. PGM
5. Zone Trb. Ind.
6. AC Power off Delay
(M)
7. Line Loss Delay(S)
1. Output Trigger
2. PGM Cut-off
Front tamper switch 1
Wireless RX module
Figure -1-
Cable interface for power, connect with power supply board
Audio speaker interface
Require for installer code
Requred for master code
4. Initialization
-55-
1. Initialize All
2. Load Defaults
3. Clear Users
4. Reset Zone Type
5. Clear WL.
Built-in siren interface
PGM, telephone line interface, for details pls refer to Figure 8
2 wired zones, 1 wired siren, 1 AUX power
output, for details pls refer to Figure 8
Jumper for codes reset: While to Default:
master code, installer code and duress
code will be reset, with temporary code
and user code deleted. Pls jump to USE for normal working.
Flat-cable interface connector to LCD
-04-

3.2 Power Supply Board
It supplies power for main board and GSM module. Pls cut off the power, with both AC and DC power off
Cable interface for power, connect with power supply board
Flat-cable interface for GSM module
1. Cancel Alarm
2. Stop. Comm.
3. Code Set
1. Master Code
2. Installer Code
3. Duress Code
Require for installer code
Requre for master code
4. Temp. Code
5. User Code 1
1. Edit
2. Delete
6. User Code 2 1. Edit
Backup battery socket 7. User Code 3
8. User Code 4 2. Delete
Socket for power adaptor
4. Zone Bypass
1. Bypass one by one
Figure -2- 2. Bypass All 1. Bypass All
2. Unbypass All
Note: AC power must be connected for normal use. If only with battery, the wired siren can not be driven. 5. Phone Set 1. Voice Phone Set 1. Voice Phone 1
2. Voice Phone 2
3. Voice Phone 3
3.3 GSM Module 4. Voice Phone 4
It enables the system to support GSM or SMS alarm. SIM card must be inserted with both AC and DC
Flat-cable interface for GSM module
GSM module
Status LED
6. Event Log
2. SMS Phone Set
3. SMS Option
1. SMS Phone 1
2. SMS Phone 2
3. SMS Phone 3
4. SMS Phone 4
1. Send for Alarm
2. Send for Arm/Dis.
3. Send for Trb.
SIM card slot
7. Service
Figure -3-
-05- -54-

Abbreviation
Description
Temp.
Temporary
Trb.
Trouble
Auto Time
Auto Arm/DisarmTime
WL.
Wireless
Comm.
Communication
Supp. Ent. Delay
Supplementary Entry Delay (See Appendix 4)
Output Trigger
Conditions for PGM Output
PGM Cut-off
PGM Output Time
Clear Users
Clear User Codes
Del.
Delete
Superv.
Supervision
SV.
Supervision
CMS
Central Monitor Station
SMS
Message
Zone Trb. Ind.
Zone Trouble Indication
Call Back
Siren Call Back for Confirm
Dis
Disarm
Reg.
Register
En/Ex.
Entry/Exit
Per.
Perimeter
Line Loss
Telephone Line Loss
TX
Transmitter
Interface
Dialing or SMS Interface like PSTN or GSM
Auto ON/OFF
Auto Arm/Disarm ON/OFF
Wired Test
Wired Siren Test
WL. Test
Wireless Siren Test
Built-in Test
Built-in Siren Test
Clear WL.
Clear Wireless Transmitters
Clear Single
Clear Single Transmitter
Clear All
Clear All Transmitters
Load Defaults
Reset as Default
Call Back
Siren Call Back for Confirm
Appendix 2:Menu Structure
Chapter 4: System Installation
4.1 Pre-installation Planning
Before starting the installation procedure, it is worthwhile to draw a rough sketch of the building and
determine the required position for the control panel and each wireless device. When deciding on the
placement for installation, consider the following:
1. Mount the control panel in a location with easy access to telephone and power connections.
2. The control panel should be mounted in a position where the GSM signal is strong.
3. Refer to the following section in order to choose the optimal location for wireless devices in relation to
the control panel.
4.2 Wireless Installation Guidelines
In order to optimize wireless communication, consider the following guidelines:
1. Whenever possible, mount the panel centrally in relation to wireless sensors.
2. Avoid installation in close proximity to sources of high noise or radio frequency interference, for
example, air conditioner, heater or circuit breaker boxes.
3. Minimize the distance between the panel and transmitters.
4. Minimize the number of obstacles between the panel and transmitters.
5. Metal based construction materials, such as steel reinforced concrete walls, will reduce the range of
radio transmissions.
TX
2 obstacle
s
RX
-53-
TX
Figure -4-
-06-
3 obstacle s

TX
steel reinforced
concrete wall
Appendix 1:System Default Parameters
No. Setting Item Parameter
Default
1 Master Code 4-6 digits 0808
RX 2
3
4
Installer Code
Duress Code
Zone Bypass
4-6 digits
4-6 digits 1234
0809
Wired zone 21&22 bypass
TX brick wall 5
6
7
8
Send SMS option
Auto Arm/Disarm
Bell call Back
Audio Volume
Send for alarm only
OFF
OFF
Volume 3
Figure -5-
The reduction of the RF signals’ strength is directly proportional to the thickness of the 9
10 Exit Delay
Entry Delay
0-300s
0-300s 100s
100s
Note obstacle, assuming that the obstacles are of identical material. 11
12
13
Zone Type
Siren
Chime Zone
Zone No.1-16 as panic, No.21-22 as entry/exit
ON
OFF
4.3 Installation Procedure 14
15 Built-in Siren
Wired Siren ON
ON
After unpacking the kit and making sure that you have all the necessary equipments, it is recommended
that you install the system as following:
Step 1: Open the housing.
Step 2: Make sure power is cut off, and insert the SIM card.
Step 3: Connect external devices.
Step 4: Power the control panel.
Step 5: Register the transmitters(wireless detector, magnetic switch, siren and keyfobs, etc.
Step 6: Test the communication signal of chosen mounting location..
Step 7: Permanently install the control panel and transmitters.
4.3.1 Open the Housing
Open the housing, press the control
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
WL. Siren
Siren Cut-off
WL. Zone SV.
Superv.Time
CMS Event
SMS Event
Panel ID
Line Superv.
Periodic Test
1st Test
Call Attempts
Ring Attempts
SMS Ack
SMS Confirm
Supp. Ent. Delay
PGM Trigger
PGM Cut-off
Zone Trouble
CMS Cooperation
Load Password
Load Interface
Load Permission
0-30minutes
1~99hours
1~30times
0-9times
0-300s
ON
10minutes
OFF
24hours
ALL ON
ALL ON
1234
ON
No Send
30minutes
7 times
6 times
ON
ON
ON
No use
50s
ON
OFF
888888
PSTN
Any time
Note panel buckle lightly to open it. 38
39
AC Loss Delay
Line Loss Delay 0-300minutes
0-300s 30minutes
30s
Figure -6-
-07-
-52-

Chapter 12: War ranty and Limitations
Although it is an advanced and reliable security system, it does not offer absolute guaranteed protection
against burglary, fire, or other troubles. The limitations are as follows:
1. Intruders may get access to unprotected openings or have technical sophistication to invalidate the
system.
2. The system will disable without power.
3. Alarm warning devices such as bells may not alert people if they are installed in an improper position.
If the alarm bell is installed outside, there are less likely to waken or alert people inside the bedrooms.
4.3.2 Power off and Inser t SIM Card
SIM card must be inserted for GSM or SMS alarm via GSM module. The AC power and battery must be cut-
off for safe operation.
Steps:
1. Plug the AC power adaptor and battery flat-cable.
2. Push off the SIM buckle lightly, see Figure 7.
3. Insert the SIM card.
4. Lock it.
4. Telephone line used to transmit alarm signals may be out of service for any reason, or can not
perform communication normally for vicious attack.
5. Unsuitable installation position of detectors. If smoke detector is installed in an improper position, it
is not easy for smoke to enter the detecting area. Because of doors or walls, it is hard for the detector
to detect fires in other rooms, e.g. the detector in the first floor can not sense fires in the second
floor.
6. Lack of maintenance may lead to the system disable. Weekly testing is necessary to ensure the
system work normally.
Figure -7-
4.3.3 Exter nal Devices Connection
1. Wired Siren Connection
The max drive of BELL terminal is 400mA/12VDC. Connect the bell power line to “BELL” and “GND”. The
siren will beep once after powering on. You can try to program via keypad to set if the siren beeps and how
Note: The wired siren is invalid with only backup battery on.
-51-
-08-

2. AUX Power Output Terminal
AUX supplies power output for wired detectors(AC Operated: 10-12V, Battery Operated: 6-8V, max
current: 100mA. It may cause abnormal working for wired detector under low battery).
10.3 GSM Module
●GSM working frequency: EGSM900/1800
●RX sensitivity: <-106dB
3. Telephone Line Connection
Connect the telephone line to the telephone line terminal block “LINE_IN” on the main board.
And connect the telephone or fax machine to the telephone line terminal block “LINE_OUT” .
●Current: Standby: <25mA
RX:
<
75mA
Chapter 11: Troubleshooting
Trouble
Potential Reasons
Solutions
N/O Detector
System trouble displays on LCD when standby See 5.6. System Trouble Query
See 5.6. System Trouble Query
N/C Detector
Siren
Detector
Device Under Control
External Power
Telephone
Telephone Line
No call for alarm
Telephone can not work normally
as the system is connected into
telephone network
Remote controller can not
operate the system
Wireless zones are out of supervision.
The indicator of power on
keypad does not work
User set the incorrect telephone number
User telephone is busy during alarm
Few ringing attempts lead the
system to hang up the phone
automatically
Battery is drained
Enroll remote controller without
programming
Remote controller is too far from the
controller or blocked by obstacles
Wireless detector is not enrolled
The control panel plug is not
inserted in AC socket, or it is
not connected well
The zone is bypassed
Set correct telephone number
Set more than two telephone numbers
Increase ringing attempts.
Refer to ringing attempts
adjustment
Replace it with a new battery
Enroll remote controller with
programming
Adjust the distance or angle between
the paner and remote controller
Enroll the detector again
Check the connection of the plug or
replace the socket
Cancel bypass of the zone
The system has no feedback
Figure -8-
4. PGM Connection
The max load of PGM output is DC50V/500mA. Boolean value is output with PGM connected with GND of
main board.
when the zone is triggered
False alarm for wireless zones
Abnormal work for PSTN
board using ADSL
When disarm, zone 1,2,3 do not alarm;
arm-stay zone 2 does not alarm
Different wireless zones use the
same code
Only analogue phone line is available.
ADSL means the communication line,
if connect ADSL directly to the control
Operate normally
Cancel this wireless zone;change the
code learn and try again
Connect the phone interface of PSTN board
to phone interface of ADSL segregator. If the
problem still can not be realized, please cha-
panel, message transmit will not be realized
nge a high-quality segregator.
5.Wired Devices Connection
The system supports different kinds of wired detectors with EOL resistance. Please connect as
following:
-09-
During walk test, re-trigger for
detector can not be realized after
1st trigger
LCD display is abnormal or dirty.
There is a sleep period of 5minutes
for detector to save battery between
2 triggers.
Pin connector for LCD is not stable.
-50-
Wait 5 minutes after the 1st trigger.
Re-connect the pin connector for LCD

◆Service info send to CMS by SMS
ID:1234
Zone: 002 362700002
Event: Service
2010/04/10 19:12:17
3627 means the CID exit PROG, 002 means the operator code.
For N/C detector:
N/C detector
Figure -9-
For N/O detector:
N/O detector
Figure -10-
Chapter 10: Parameters 4.3.4 Power Connection
10.1 Specifications:
◆Re-check the wiring and make sure all connection is correct.
●
●
Wireless zones: 16
Wired zones: 2
◆Connect the AC power adaptor and plug the backup battery. The control panel can not be initialized by only
battery.
● EOL resistance: 2.2K
● Wireless frequency:
433MHZ/868MHZ
● Wireless distance:
≥100m(with no obstacle)
● PSTN way: DTMF
● Communication protocol: Contact ID
AWAY
STAY
DISARM
PROG
◆Parameters of power adaptor: Input: 100V-240VAC 50/60HZ 0.5A, Output: 12VDC 1.5A.
Backup battery: 7.2V 1800mAh NimH rechargeable, 24hours is required for full recharge which can last
around 8 hours for this system under standby situation. After low battery warning, it can work for around
30 minutes.
◆The system will keep the time and date with time chirp powered. If the power of time chirp runs out, you
need to re-set the time manually. See the Figure:
● Dimension:250*150*45mm
1. Set Date
0 1 / 0 1 / 2 0 0 0
2. Set Time
10.2 Electric Parameters:
Figure - 16- 0 0 : 0 0
◆After powering up and initialization, it beeps shortly and requires to input time and date.
●
●
●
●
●
●
●
Power adaptor:Input 100V-240VAC 50/60HZ,Output:12VDC 1.5A
Backup battery capacity:7.2V/1800mAh
Working voltage: 12VDC
Static current: <90mA@12V(not including wired detectors and GSM module)
AUX power output: AC10-12V, DC6-8V, ≤100mA
Siren output: ≤400mA
PGM output max load: DC 50V/500mA
◆The icon will move to next automatically after each input. Press “*” to exit. After complete input, press “#”
to confirm. If the input is not finished, and meanwhile “*” is pressed, it will display on the LCD “Invalid
Set”. Please press “*” to re-input it.
◆With GSM module connected, time will set by itself by searching the network, which may take 1-2 minutes.
AC power must be connected for initialization. Or else it can not be initialized with just backup
●
Built-in siren: 85dB Note
battery.
●Working temperature: -10℃~+55℃
-49-
-10-

4.3.5 Register Transmitters
Transmitters refer to wireless devices such as detector, magnetic switch, siren and keyfob, etc. Only after
enrolling can transmitters be recognized by the control panel.
To register a device:
1. During disarm, press “PROG”. With voice guide “Enter password before setting parameters!”. Input the
installer code with “#”.
2. For specific register process, pls refer to “WL. Register, Keyfob Register and WL. Siren Reg.”.
◆“Arm/Disarm Query”:
Password0808Status
Please take off the battery before enrolling, and then enroll one by one with battery connected.
While you register with battery on for all devices, there may come wireless signal interference
Note and make enroll fail.
ID: 1234
Prog: Arm away
Act:OK
ID: 1234
Prog: Arm stay
Act:OK
ID: 1234
Prog: Disarm
Act:OK
4.3.6 Testing the Chosen Mounting Location
Once all of the transmitters are registered, it is recommended that you test the chosen mounting
locations before permanently mounting the control panel and wireless devices. You can test the
transmitter signal strength using the TX Test feature.
To test wireless transmitters:
1. During disarm, press “PROG”, with voice guide “Enter password before setting parameters!”. Input the
installer code with “#” to enter.
9.4 Send SMS for Alar m
It enables the control panel to send SMS message to the set phone number or SMS center for alarm, or
system trouble through Contact ID. For example, the control panel ID is 1234, when fire alarm, disarm, or
zone trouble occurs, it will send SMS as following:
2. Select “Service”
→
“#”
→
“WL. Test” →“#”.
◆
SMS Alarm
3. Trigger the desired devices, and the info about them will display on the LCD.
4. After all test, press “*” to exit.
ID:1234
Zone: 005 111000005
Test GSM Signal:
The communication signal strength should be tested to confirm if GSM module is connected.
To test the GSM signal:
1. During disarm, press “PROG” with voice guide “Enter password before setting parameters!”. Input the
installer code with “#” to enter.
2. Select “Service” →“#” →“GSM Test” →“#”.
0-31 means for the signal strength. 31 means the strongest. To make sure normal communication,
Event: Fire
2010/04/10 19:12:17
◆SMS message for non-Alarm
ID:1234
Zone: 000 140100001
Event: Disarm
2010/04/10 19:12:17
1110 is the CID event code for fire alarm, 00 means zone 0. And 005
means zone 5 alarm
1401 is the CID event code for disarm,001 means the operator.
please use over 12.
◆SMS message for zone trouble
4.3.7 Installing the Control Panel
ID:1234
Zone: 002 138400002
Having chosen and tested the mounting location of the control panel and each transmitter, you are now ready
to permanently install the system.
-11-
Event: Low battery
2010/04/10 19:12:17 1384 means the CID event code for wireless zone low battery.
002 means zone NO.
-48-

◆“Arm away”:
ID: 1234
Prog: Arm away
At first, stick “Installing Hole Drawing” on the location for control panel. Drive 4 screws on the fixed position
(see Figure 11-1), and then hang the control panel directly on the screws(see Figure 11-2). While driving
Password0808Armaway
Su c
ces
s Act:OK the screws, please pay strict attention to the depth of screws to make sure easy hang and tamper switch
work normally. There are 2 tamper switches: front tamper and rear tamper. Compress the tamper switch
while installing. If the control panel is removed or opened, tamper alarm will be triggered.
Fai
lure
ID: 1234
Installing Hole Drawing
Prog: Arm away
Act:ERR
◆“Arm stay”:
ID: 1234
Prog: Arm stay Wall Wall
Password0808 Armstay
Su c
ces
s Act:OK
Figure -11-1
Figure -11-2
While hanging the control panel, please don’t shake the product to avoid breaking the tamper switch.
Fai
lure
ID: 1234
Prog: Arm stay
◆“Disarm”:
Act:ERR
ID: 1234
Prog: Disarm
5.1 Front Panel Layout
Chapter 5: Operations
Password0808Disarm
Su c
cess Act:OK AWAY
STAY
DISARM
PROG
Fai
lure
ID: 1234
Prog: Disarm
Act:ERR
Figure -12-
-47-
-12-

AWAY
For arm away
STAY
For arm stay
DISARM
For disarm, and also for fire alarm(press for 2s)
PROG
For programming, and also for panic alarm(press for 2s)
Figure or navigation key for up turn, for menu operation or query
Figure or navigation key for down turn, for menu operation or query
It means “delete” while inputting figures or quit for menu operation.
Power LED: Red means AC loss or low battery. Green means normal.
Arm LED: Red means armed. Green means disarm.
Alarm LED: Red means alarm. Slow flash means dialing the CMS.
Signal LED: Flash means normal GSM signal.
5.1.1 Status LED Pressing any key on control panel or phone during voice play may cause communication error. It
Note is suggest to operate after voice. If the system is under programming, remote programming is not
available. There should be no voice indication during remote program.
9.2 Dial to Alar m via Panel
The control panel will call the set phone numbers during alarm. You will hear the voice around 5s after pick-
up and will repeat after another 5s, which will last 5 times and then hangs up automatically. After hang up,
if no voice guide, or user can not wait, you can press “5”, then the panel will issue alarm indication.
5.1.2 Front Panel Keypad
Keypad backlight: press any key, the backlight will turn on, whatever, if no any keying within 30s, it will
disappear. During the backlight from ON to OFF, with any trouble, the control panel will warn “System
Before it hangs up, you can program by phone.
See following:
Disarm: press “3”.
Arm-away: press “3”to disarm and then “1”to arm away.
Arm-stay: press “3”to disarm and then “2”to arm stay.
Repeat alarm: press “5”to repeat the alarm.
Note:Alarm is not available to repeat after disarm.
Turn off siren: press “7”.
Turn on siren: press “6”,on-site siren will turn off after 10s.
Hang up: press “0”to hang up directly and the system will not dial any phone number.
Pressing any key on control panel or phone during voice play may cause communication error. It is
Note suggest to operate after voice. If the system is under programming, remote programming is not
available. There should be no voice indication during remote program.
trouble, please check!”
9.3 Telecontrol via SMS
5.2 LCD Display It enables you to arm, disarm or querystatus via SMS. For example, user code is 0808, and control panel
ID is 1234, operate as following:
The LCD display provides you with a detailed interface for operation and programming.
If program is successful, it means arm or disarm success;While program fails,it means arm or
5.2.1 Standby Mode
Standby mode can be defined as the state the system is in when it is disarmed and not in menu mode. In
-13-
Note disarm failure.Arm or disarm can not be available during programming. With zone alarm,
arm can not be realized. There must be no space before or between SMS words.
-46-

Clear Users
Clear User Codes deletes all programmed user codes and restores the default master and installer
codes and duress codes.
To clear users:
standby mode, system status, time and date, or
banner are displayed on LCD. If system status is
abnormal, it will displayed as:
Arm Away
2 0 / 1 2 / 2 0 1 0
1. From the main menu, select “Programming”→ “#”→”Initialization” →#→ “Clear Users”→ “#”.
2. It will display on LCD “Clear users?”, press “#” to confirm, or “*” to exit.
Clear Users by Hardware
Clearing user codes can be also realized by hardware jumper. There is a jumper on the control panel
board “J3”(See Figure 1-Main Board Schematic). If user codes are forgotten, pls power off, and put the
jumper to “ Default” and then restart the system, which will reset user codes as default. The “ Default”
jumper should be cut-off after the system initialization, or else, the action will repeat next power-on.
Reset Zones
This function resets all wireless zones into panic and all wired zones into entry/exit zones.
To reset zones:
1. From the main menu, select “ Programming” → “ #” → Initialization” → “ #” → “ Reset Zone Type” → “ #” .
2. It will display on LCD “Reset Zone Type?”, press “#” to confirm or “*” to exit.
5.2.2 Display Interface
You may meet following symbols or marks:
Selected for multiple-choice
Unselected for multiple-choice
Selected for single choice
Unselected for single choice
Counting down
15:30
System Trb.
Clear Wireless
Clear all wireless includes wireless zones, keyfobs and sirens.
To clear wireless:
1. From the main menu, select “Programming”→“#”→“Initialization”→“#”→“Clear Wireless” → “#”.
2. It will display on LCD “Clear Wireless?”,press “#” to confirm or “*” to exit.
Chapter 9: Telecontrol via Phone or SMS
System Trb.
Alarm List
Trb. List
Untreated
Treated
Confirm to enter for details
System trouble
Display of alarm events
Display of trouble
It means not disarmed after alarm.
It means disarmed after alarm.
6 telephone number and 6 SMS phone number can be set in this system. Regarding telephones,
System Trouble Display:
number 1 and 2 means for CMS and 3-6 means for common phone numbers. “System Trb.” will display on LCD if there is. See following, press to query:
9.1 Telecontrol via Phone
It enables you to remote program the control panel via telephone, such as arm-away, arm-stay, disarm,
repeat alarm voice, and active or mute site siren, etc. You can call the phone number set in the control
panel. After call attempts set, it will hang off with voice guide to input password ending with “#”: “For
arm- away, press 1, for arm-stay, press 2, for disarm, press 3, For alarm repeat, press 5, Turn-on site
siren, press 6, turn-off site siren, press 7, for hang up, please press 0”.
-45-
Arm Away
2 0 / 1 2 / 2 0 1 0
15:30
System Trb.
-14-
------ Trb. List------
1. Low Battery
2. Line Loss
3. Low GSM Signal
4.WL. Zone 1 Trb.>>>

Alarm Display:
The alarm will display with voice guide in the alarm List. Press the navigation key to select with “#” to
query the event. If there are multiple alarm events, press the navigation key directly to check other
events. Press “*” to quit.
AC Power off Delay(M)
The AC Loss Delayis the amount of time that has to elapse before an AC Loss report is sent to the central
station. If AC power is restored before the event message is sent, the event message is cancelled and will
not be sent. You can program an AC Loss Delay to be between 1 and 255 minutes after the system first
senses the AC loss condition. Alternatively you can program a random AC Loss Delay. The AC Restore
------ Alarm List------
Zone 17 Panic Untreated
Zone 21 En/Ex. Untreated
Zone 22 Peri. Untreated
Alarm ---------- Untreated
Zone: 17
Type: Panic
Time: 1 2 / 1 2 / 2 0 1 0
10:35
message is also sent using the same method described above. AC Restore is reported only if the AC Loss
report was sent. AC loss delay is mainly used when the power is cut off with many AC loss report sending,
which may cease the system.
To set AC loss delay:
1. From the main menu, select “Programming”→“#”→“System Option”→“#”→“AC Power off Delay(M)” → “#”.
2. Input the delay time(001-255minutes) or 000 for system random setting.
3. Press “#” to finish.
The voice guide will last for 10minutes without any operation. During disarm, after the voice
Note
finishes, any operation will trigger the voice replay.
If disarm by also clearing the alarm list, the event will disappear. If disarm by saving alarm list, then the
event will change into “Treated”. For specific operation, please refer to 7.1.3.
------ Alarm List------
Zone 17 Panic Treated
Zone 21 En/Ex. Treated
Zone 22 Peri. Treated
Programming:
During programming, it displays similar as following:
Line Loss Delay
It transmits message to center station while the telephone line is disconnected. While before the message
is sent to the station, and the telephone line recovers connected well, the message will be cancelled. Or if
the message for Line loss is sent to the station successfully before the connection recover, the line recover
message will be also sent.
To set line loss delay:
1. From the main menu, select “Programming”→“#”→“System Option”→“#”→“Line Loss Delay(S)” → “#”.
2. Input the delay time(001-255minutes) or 000 for system random setting.
3. Press “#” to finish.
8.3.8.4 Initialization
Initialize All
Init. All means initializing all. The Initialization function clears the entire system and resets factory
defaults, which will recover the control panel ID and delete all phone numbers and wireless devices.
4. Auto ON/OFF
ON
OFF
-15-
WL. Zone 3
Type: Entry/Exit
Activate Siren
Low Battery
TX Loss
To initialize all:
1. From the main menu, select “Programming”→“#”→ “Initialization”→““#”→ “Initialize All” → “#”.
2. It will display on LCD “Init. All?”, press “#” to confirm, or “*” to exit.
Load Defaults
Loading the system’s default program enables you to restore the factory-set programming defaults, which
keeps the control panel ID and will not delete the set phone numbers or wireless devices.
To load defaults:
1. From the main menu, select “Programming”→ “#”→ “Initialization”→ “#”→ “Load Defaults” →“#”.
2. It will display on LCD “Load Defaults?”, press “#” to confirm, or “*” to exit.
-44-

PGM Trigger
Activated by……
Disactivated……
Zone 16 Alarm
See above
See above
Zone 17 Alarm
See above
See above
Zone 18 Alarm
See above
See above
Zone 19 Alarm
See above
See above
Zone 21 Alarm
See above
See above
Zone 22 Alarm
See above
See above
Zone 30 Alarm
See above
See above
Press 1 & 2
Press 1 & 2
Cut off after PGM period
10s for Line Trb
Telephone line supervision trouble
Cut-off after 10s
Arm away
Instant Activate
Any arm status change
Arm Stay
Instant Activate
Any arm status change
Disarm
Instant Activate
Any arm status change
Siren follow
Siren follower
Siren follower
Entry/Exit
Activate
Until disarm or after PGM cut-off
Active
See above
See above
Perimeter
See above
See above
Panic
See above
See above
Fire
See above
See above
Gas
See above
See above
Tamper
See above
See above
Duress
See above
See above
Alarm type
Send to CMS
Dial phone
Send SMS
LED
Siren
Fire zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Gas zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Panic zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Perimeter zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Active zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Entry/Exit zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Duress zone
Yes
Yes
Yes
Not ring
Tamper zone
Yes
Yes
Yes
ON
Ring(cut-off adjustable)
Line loss
No
No
Yes
Not ring
AC loss
Yes
No
Yes
Not ring
Low battery
Yes
No
Yes
Not ring
WL. loss
Yes
No
Yes
Not ring
Low battery for
WL.
Yes
No
Yes
Not ring
5.3 Alar m Type and Way
There are two alarm type: instant alarm and delay alarm.
Trigger 24-hour zones, instant alarm will occur.
24-hour zones include: fire zone, gas zone, panic zone, duress zone, and tamper zone.
Note : For 24-hour zone, whether it is armed or disarmed, once triggered, it will alarm immediately.
Alarm delay occurs with voice indication as “Alarm, please disarm!” when the entry delay zone is
triggered. Before the music ends, please disarm, and the alarm message will not be sent to CMS center.
Or if you disarm after the music, the message will be sent. Entry delay happens for entry/exit zone and
active zone only.
1. For entry/exit zone, only during arm away and arm stay will the zone be triggered with
alarm delay.
Note 2. For active zone, only during arm away will the zone be triggered with alarm delay.
3. When alarm already happens in the zone, and with this zone triggered again, the panel
will alarm immediately with no indication of entry delay.
Different alarm type and zone type determines different alarm way:
With all conditions satisfied, PGM will output. The PGM under “ Go 10s when line loss, arm away, arm
stay, disarm or siren follow” is not determined by “PGM cut-off” time, while PGM under other situations
will switch to disactivated after PGM cut-off. The PGM cut-off can be set by programming.
To set PGM cut-off:
1. From the main menu, select “Programming”→ “#” → “System Option”→ “#” → “PGM”→ “PGM Cut-off” → “#”.
2. Press “#” to edit with icon indication.
3. Enter a PGM cut-off time(0-300s, 000 means continuous activation)
4. Press “#” to exit when the desired setting is displayed.
Zone Trouble Indication
This option enables you to select whether zone trouble will be indicated in the system trouble list. If this
function is turned off, it will not display.
To set zone trouble indication:
1. From the main menu, select “ Programming”→ “ #” → “ System Option”→ “ #” → “ Zone Trb. Ind.” → “ #” .
2. Press the navigation key to select “ON” or “OFF” and confirm with “#”.
3. Press “*” to exit.
-43-
-16-
Other manuals for LHD8003
1
Table of contents
Other LONGHORN Control Panel manuals
Popular Control Panel manuals by other brands

Siemens
Siemens MJ-XL Installation and operation manual

Biamp
Biamp TEC-X 1000 Installation & operation guide

Teknim
Teknim TFP-121 Series Installation & operating manual

Smarteh
Smarteh LONGO LPC-2 user manual

Bosch
Bosch Rexroth IndraControl VAM 11.1 Project planning manual

Ecler essentials
Ecler essentials eMCONTROL1 user manual