LONGHORN LHD8001 User manual

MGE Entreprise
Av. Kouwait - 8050 Hammamet
Tunisie
Tel.1: 00216 72 278 663
Tel.2: 00216 22 645 120
Email: manager@mge-security.com
www.mge-security.com/
INSTALLATION
MANUAL
LHD8001
SECURITY SYSTEM

Zone number
Installation position
Type
Bypass or not
1
2
3
4
5
6
7
8
9
10
11
12
14
15
16
User
User address
Installer
Installation company
Installation date
Tel of installation company
Fax of installation company
Center stations
Address of center stations
Tel of center stations
Tel of the control panel
No.
Name
Amount
1
Control panel
1
2
Remote Controller
2
3
Wireless Passive Infrared Detector
1
4
Wireless Magnetic Switch
1
5
Power adapter
1
6
Installation manual
1
7
Telephone line
1
8
Accessories bag
1
Zone number
Installation position
Type
Bypass or not
21
22
23
24
INSTALLATION INFORMATION
Appendix 2: Zone type setting figure
Wireless zone
CONTAINER LOADING LIST
You should find the following equipment in your system. Verify
each of the components is included:
Wired zone
Note: The accessories bag includes EOL resisters(2.2k, 4pcs)
screws(4pcs) and expansion tube.
-35-

18 Auto-disarm time
20
Edetector w i r e l e s s
21 canceling
22 controller
23 canceling
29 Software version
31 All zones bypassed
32 All wireless zone
33
All re mote controllers
34 Zone type initializa-
35
Srestoring d e f a u l t
No.
Setting item
Keypad operation
Parameter / Select
Default
Table of Contents
Auto-arm
17 setting time
35 X Y #
X=1~3(NO. X auto-arm time)
Y=hour minute(4 digits)
Y=88 88 1.
2. General introduction
Specifications 1
1
setting
19 Zone definitions
nroll
36 X Y #
40 X Y #
61 X #
X=1~3(NO. X auto-disarm time)
Y=hour minute(4 digits)
X=01~16(16 Wireless zones)
X=21~24(4 Wired zones)
Type code Y=1~8
X=01~16(NO. X wireless
zone detector)
Y=88 88
Refer to 9.3
3.
4.
5.
6.
Term definition
Notice before using
Installation step
Operation
6.1 Control panel composition
2
3
3
7
7
Wireless detector
62
X
# X=01~16(NO. X wireless
zone detector ) 6.2 Power up the system
6.3 System initialize successful 8
8
Enroll remote
63
X
# X=1~5(NO.
controller)
X
remote 6.4 Alarm
6.5 Alarm type 8
9
Remote controller
64
X
# X=1~5(NO.
controller)
X
remote 7. Zone type and zone assignment
7.1 Zone type 10
10
24 Zone bypass
25 Zone reactivate
26 Voice recording
27 Record playing
28 Viewing event log
65
66
70
71
80
X
X
0
X
X
#
#
#
#
#
X=01~16(16 wireless zones)
X=21~24(4 wired zones) No bypass
X=17( panic zone) except wired
X=30(conrtol panel anti-tamper zones
zone)
Ditto
Record user address
X=1~8 play alarm type,
X=9 play user address
X=01~40, read 1~40 records
7.2 Zone assignment
7.3 Zone type displaying
8. Function key operation
8.1 Arm-away
8.2 Arm-stay
8.3 Disarm
8.4 Panic
9. System programming
9.1 Password input
10
10
10
11
11
12
13
13
13
9.2 Operation step 14
inquiring
88
X
#
X=1 inquire U1 software
version
X=2 inquire U201 software
version
X=3 inquire U402 software
version
9.3 Basic system programming
9.3.1 Communicator programming
9.3.2 User address code setting
9.3.3 User password modification
15
15
16
16
30 All zones bypassed
reactive
910
920
#
# 9.3.4 Operation password setting/canceling
9.3.5 Ringing attempts adjustment 16
17
9.3.6 Bell ON/OFF setting 17
detectors canceling
canceling
tion
ystem
930
940
950
960
#
#
#
#
9.3.7 Auto-arm/disarm option
9.3.8 Telephone line monitor
9.3.9 Protocol option
9.3.10 Relay output type setting
9.3.11 Bell/Buzzer chirp times setting
9.3.12 Exit delay time adjustment
17
18
18
18
18
19
-34-

2
setting
5
Ringing attempts
7
Auto-arm / auto-
10
Relay output type
11
time setting
12
adjustment
13
adjustment.
10minutes
100seconds
40seconds
16
setting
9.3.13 Entry delay time adjustment
9.3.14 Year setting
9.3.15 Date setting
9.3.16 Hour and minute setting
9.3.17 Auto-arm time setting
9.3.18 Auto-disarm time setting
9.3.19 Zone definitions
9.3.20 Enroll wireless detector
9.3.21 Wireless detector canceling
9.3.22 Enroll remote controller
9.3.23 Remote controller canceling
9.3.24 Zone bypass
19
20
20
20
20
21
21
22
23
23
23
23
6. Dimension: 250 150
45mm
250mm
9.3.25 Zone reactivate 24 Appendix 1: Parameter setting
9.3.26 Voice recording
9.3.27 Record playing 24
25 No. Setting item Keypad operation Parameter / Select Default
9.3.28 Viewing event log
9.3.29 Software version inquiring
9.3.30 All zones bypassed
25
26
27
1
Communicator
programming
User address code
11
20
X Y #
X #
NO.X(X=1~6) alarm
telephone number Y=1~15
digits telephone number
X is the 4 digits user address
code
Null
1234
9.3.31 All zones reactivate 27
3
User password
modification 21 X # X is the 4 digits new user
password
1234
9.3.32 All wireless zone detectors canceling
9.3.33 All remote controllers canceling
9.3.34 Zone type initialization
9.3.35 System default restoring
10 .Remote telephone operation
10.1 Telephone disarm
10.2 Telephone arm-away
27
27
27
27
28
28
28
4
Operation password
modification
adjustment
6
Bell ON/OFF setting
disarm option.
22 X Y #
23 X #
24 X #
25 X #
X=1~5 (NO. Xoperation
password) Y is the 4 digits
new operation password
X=1~9times(X=0 indicating
no telephone remote control
and no automatically
receiving the telephone)
X=1: ON, X=0: OFF
X=1: Valid,X=0: Invalid
Null
X=6
X=1
X=0
10.3 Telephone arm-stay
10.4 Telephone spot supervision 29
29
8
9
Telephone line
monitior
Protocol option
26 X #
27 X #
X=1: ON, X=0: OFF
X=0:ContactID, X=1:4+1
X=1
X=0
10.5 Hearing present alarm type.
10.6 Hang-up/stop alarm dialing 29
29
setting
28 X # X=1:Alarm output
X=2:Fire alarm output
X=3:Arm output
X=2
11. Control Panel Communication Code
12. Warranty
13. Troubleshooting
14. Technical parameter
30
31
31
32
Bell and buzzer chirp
Exit delay time
Entry delay time
29 X #
30 X #
31 X #
X=00 30 the delay time are X=10,
0~30minutes
X=00 30 the delay time are
X=10,
0~300seconds
X=00 30 the delay time are X=04,
0~300seconds
Appendix 1: Parameter setting
Appendix 2: Zone type setting figure 33
35
14
Year setting
15
Date setting
Hour and minute
32 X #
33 X #
34 X #
X=year (2 digits)
X=month date(4 digits)
X= hour minute(4 digits)
X=00
X=01 01
X=00 00
-33-

Types of fault
Potential reasons
Solutions
The system has no
feedback when zone is
touched
The zone is bypassed
Cancel bypass of the zone
When disarm, zone 1,2,3 do
not alarm; arm-stay zone 2
does not alarm
Operate normally
A u t o - a r m / a u t o - d i s a r m
invalidation
Arm/disarm is not set in valid
statue
Set arm/disarm in valid
status
Arm/disarm with the same time
Reset the arm/disarm time
Can't disarm when alarm
occurs or the system is in
entry-delay status
Refer to Auto-arm/auto-
disarm
Wireless zone misinformation
Different wireless zones use
the same code learn
Cancel this wireless zone;
change the code learn
and try again
1. General introduction
This is a new kind of intelligent security product. It transmits alarm information
via telephone communication network and is remotely controlled to deal
with emergencies in time, ensuring user's personal and property safety.
This product has complete functions, flexible configuration; strong
destroy protection and convenient operations, being suitable for
residences, stores, factories, warehouses, banks, schools and hospitals,
etc.
2. Specifications
20 Fully programmable zones: 16 wireless and 4 wired
LCD displays
14. Technical parameter
14.1 General data
1. Requirement of wired zone: connect to 2.2K resistance
2. Control device:
Remote controller
Keypad
Local or remote telephone system
3. Wireless frequency: 315MHz/ 433MHz/868 MHz(optional)
Communication protocol: ADEMCO 4+1 and Contact ID
Automatically dial center stations user cell phone or fixed telephone with
voice alarm while alarm occurs
6 alarm received telephones: 1 in center stations and 5 common
telephones
7 passwords: 1User, 1Duress, 5 Operation
Wireless code learn
Suppose to 5 remote controllers utmost
Arm or disarm via remote controller, telephone or keypad
4. Received range of the detector: 90m (in open space) Alarm modes: alarm bell and voice alarm
5. Effective range of the remote controller:
6. Length of recording: 4 seconds
7. Dialing mode of alarm: DTMF
8. Relay output parameter:
Contact capacity 10VA
Contact maximal voltage 100VDC
Contact maximal current 0.5A
14.2 Other data
1. Power adapter working voltage: 100V
50m (in open space)
240V AC
Auto-arm and Auto-disarm time programable
Bypass/Reactivate stay zone type programable
Restore user password to factory default by hardware and restore the
system factory default by software
40 Events log
System supervision for AC power failure, low battery condition and
telephone line trouble
Real-time clock
Voice-recording
Programmable relay output
2. Operating voltage of the control panel: 12VDC Anti-tamper
3. Static operating current: 130mA Spot supervision
4. Bell output current: 400mA
5. Operating temperature: -10 +55
-32- -1-

Types of fault
Potential reasons
Solutions
The system does not dial
to alarm when alarm
happens
User set the incorrect telephone
number
Set correct telephone
number
User telephone is busy
during alarm
S e t m o r e t h a n t w o
telephone numbers
Telephone cannot work normally
as the system is connected
into telephone network
Few ringing attempts lead
the system to hang up the
phone automatically
Increase ringing attempts.
Refer to ringing attempts
adjustment
Remote controller can not
operate the system
Battery is drained
Replace it with a new
battery
Enroll remote controller wit hou t
programming
Enroll remote controller w it h
programming
Remote controller is too far
from the controller or blocked
by obstacles
Adjust the distance or angle
between the system and
remote controller
Wireless zones can not
monitor normally
W i r e l e s s detector n o t
enrolled
Enroll the detector again
The indicator of power on
keypad does not work
The control panel plug is not
inserted in AC socket, or it is
not connected well
Check the connection of
the plug or replace the
socket
3
.
Term definition
Detector: A facility that detects intrusion and abnormal state
automatically via some electric or physical methods
and output switch signals or wireless signals to the
system for disposal, then output alarm signals, such
as infrared detector, smoke detector, etc.
Zone: An area of the detection range of one or one group
detectors.
Bypass: Close one of the zones temporarily, so that it can not
alarm while act in the zone.
Arm-away: The armed status while going out. All the zones without
bypass are in armed status.
Arm-stay: The armed status at night. All the zones are in armed
status except active zones.
Disarm: Close the entry/exit zones, active zones, perimeter
zones. Other zones are still in arm status.
No matter armed or disarmed, it is in valid detecting
24-hour zone: status. It is usually used in fire alarm, duress alarm
and other emergent alarm which can be cancelled
only by password holder.
Center stations It is an alarm receiving station, to which the alarm
receiver: controller sends out alarm information via telephone
line when alarm occurs. The station will take
corresponding actions after receiving the alarm.
Entry delay: A period for user to enter detection area, activate the
delay zone and disarm before the system alarms.
During the period, user can activate several specified
zones (entry zone) without alarm immediately. While
exceeding the time, the system alarms if not
disarmed. Zones with entry delay are the exit/entry
zone and active zone.
Exit delay: A period for user to leave detecting area once the system
armed. Zones with exit delay will not alarm during this
period. The zones with exit delay are the exit/entry
zone and the active zone.
User address code: 4 digits code used to be distinguished by the center sta tio ns
when the control panel with network alarms.
Duress password: When user is forced to disarm the control panel by burglar,
user inputs duress password, the control panel is
disarmed but sends alarm information to the center
stations or receiver. The duress password can be used
to disarm but set parameters. The duress password is
the last digit of user password plus 1 without carry
(9+1=0). E.g. while user password is 8889, the
duress password is 8880; while user password is
9999, the duress password is 9990.
-2-
12. Warranty
Although it is an advanced and reliable security system, it does not offer
guaranteed protection against burglary, fire, or other troubles. The
limitations are as follows:
1. Intruders may get access to unprotected openings or have technical
sophistication to invalidate the system.
2. The system will disable without power.
3. Alarm warning devices such as bells may not alert people if they are
installed in an improper position. If the alarm bell is installed outside, there
are less likely to waken or alert people inside the bedrooms.
4. Telephone line used to transmit alarm signals may be out of service for
any reason, or can not perform communication normally for vicious attack.
5. Unsuitable installation position of detectors. If smoke detector is installed
in an improper position, it is not easy for smoke to enter the detecting area.
Because of doors or walls, it is hard for the detector to detector fires in other
rooms, e.g. the detector in the first floor can not sense fires in the second
floor.
6. Lack of maintenance may lead to the system disabled. Weekly testing is
necessary to ensure the system work normally.
13. Troubleshooting
-31-

25 telephone number from 2 to 6
11. Control Panel Communication Code
Communication between control panel and center stations have two
formats ADEMCO 4+1 and ADEMCO Contact ID.
4. Notice before using
Please set '911' as alarm phone number under the police's approval.
Read the manual carefully before using
ADEMCO 4+1 Table of event
codes NO. Identification ADEMCO Contact ID OPERATION OF
USER ARM/DISARM Number
Connect the AC power supply after other wiring is complete
Please use backup power when AC power failure
No.
1
2
3
DEFINITION
Fire alarm, including fire alarm
gas and panic zone
Plunder alarm, duress zone
Rob alarm, Entry/Exit /Active/
Perimeter/Anti-tamper zone
00
01
02
Operation of using keypad
without password, such as arm-
away disarm and arm-stay
User password to arm/disarm, by
using keypad or remote telephone
operation
Corresponding operation password
to arm/disarm by using keypad or
remote telephone operation
Do not disassemble the control panel and detector frequently
Any questions, please contact with our company
5. Installation step
5.1 Installation requirements
Work out a protection scheme based on user requirements, then decide
4
5
Disarm
Arm
11
21
15 Remote controller arm/disarm
Disarm/arm operation by using
the type and of the detector
Confirm the installation position and wiring direction according to the
specific condition. Make sure the position invisible without affecting its
Using duress code to disarm, the reliability. It is better to wire in concealed way
6
7
AC power failure
Low-battery
98 system will be disarmed and then
send duress alarm information to
the center stations, the NO. of the
duress code user is 98 which
The construction scheme and engineering drawings must be filed for
maintenance late
included in the disarm information
8 Restore default 99 Auto-arm/auto-disarm
5
.
2 Inner wiring
Open the case of the control panel
ADEMCO Contact ID TABLE OF EVENT CODES
No.
DEFINITION
100
110
121
131
132
134
137
151
301
302
401
441
455
521
570
Panic zone alarm
Fire zone alarm
Duress code, Duress zone alarm
Perimeter zone alarm
Active zone alarm
Entry/Exit zone alarm
Control panel anti-tamper alarm. Anti-tamper zone alarm
Gas zone alarm
AC power failure
Low-battery
Arm/Disarm operation
Arm-stay operation
Auto-arm/disarm failing
Bell canceling function
Zone bypass operation, zone/user is 99 represent all
zones bypassed or all zones bypass canceling
-30-
Open outlet door for inserting cables
Outlet slot
Figure 1
Press those two points and
open the back cover
Figure 2
-3-

Standby battery socket
Anti-tamper switch
Standby battery switch
Antenna Standby battery
Bell output
Wired zone Z1
Wired zone Z2
10.3 Telephone arm-stay
After picking up the telephone, press '# +4digits password(user
password, operation password) + 2 + #' to arm, For example, if user
password is 1234, press '#12342#'. When alarm occurs, user has to
disarm first and then arm the system again.
When the control panel dials to alarm, user can press 3 to disarm and
then press 2 to arm after hearing alarm voice.
Wired zone Z3
Wired zone Z4
Password
restore jumper
10.4 Telephone spot supervision
After picking up the telephone, press '# + 4digits password(user
Power input
Relay output
Grounding
Telephone
line input Telephone
line output
Keypad line slot
password, operation password) + 4 + #' to monitor on the spot. For
example, if password is 1234, press'#12344#'. When the control panel
dials to alarm, user can press 4 to monitor his/her house after hearing
Figure 3 Control panel inside
After wiring close the cover
Figure 4
5.2.1 Power connection
Power Adapter: Input 100V~240VAC 50/60Hz 0.3A, output 12VDC 1A
connect output plug with socket (Refer to the figure 3)
The control panel with 7.2V/1800mAh NH rechargeable battery as
standby battery. In working status and the battery is well charged, it can
supply the system with power more than 14 hours, low-battery, it can
supply power more than 1.5 hours
Low-battery, power indi cator f lashe s fast, when AC power is low-voltage,
power indicator flashes slow .When AC power and standby power is in
working voltage, power indicator switched on .When standby or AC power
is low- voltage buzzer chirps 1 minute
-4-
voices. The control panel will not dial any other numbers.
The spot supervision time is about 30 seconds, this status will be over
after hearing the prompt voice 'Di', and user can operate continually in
ten seconds.
10.5 Hearing present alarm type
After picking up the telephone, press '# + 4digits (user password,
operation password) + 5 + #' to hear present alarm type. For example, if
user password is 1234, press '#12345#'. The control panel will play the
alarm voices 5 times and pause 5 seconds among them. If no key is
pressed, the system will hang up automatically. If no alarm occurs, user
can hear 'Di-' twice.
Whenthe control panel dials to alarm, press 5 to hear alarm type. The
system will play the alarm voice 5 times and pause 5 seconds among
them. If no key is pressed, the system will hang up automatically.
10.6 Hang-up/stop alarm dialing
Whenthe control panel dials to alarm, user presses '0' after hearing
alarm voice, the control panel will hang up automatically and not dial any
other numbers.
Whendialing via phone, the system can use operation digit '0' to hang up
automatically.
-29-

10. Remote telephone operation
User can dial telephone number of the control panel perform the operations:
arm away/stay, disarm spot supervision and hearing alarm types.
Dial telephone number of the control panel for more than ringing attempts
set. The system will answer automatically and announce the user with a
voice 'Di'. Then user presses '# + 4 digits password(user password operation
password) + 1 operation digit + #', the control panel will operate
corresponding commands. 6 operation digits, 1 means arm-away, 2 means
arm-stay, 3 means disarm,4 means spot supervision, 5 means hearing
current alarm voices, 0 means hang-up / stop dialing to alarm.
For example, user password is 1234. To disarm the control panel, user can
press '# 1 2 3 4 3 #' after switching on the system. If the operations is
correct, 'Di' will be heard once. If the operations is incorrect, 'Di' will be heard
twice. If password is wrong, user can input password and operate digit again
5.2.2 Bell output terminals
The maximal drive capacity of bell terminal (+BELL -) is 400mA /12VDC
Connect the two power lines of the bell to 'BELL+' and 'BELL-' terminals
Whenthe system is powered up and initialized bell will chirp once,
indicating it works normally .Setting the bell on/off and the chirping time
can be programable with software
5.2.3 Wired zone connection
Each loop is connected to an end-of-line (EOL) resistor. For different
detectors, modes of connection are shown as followed:
Whenconnecting N.C. detector, connection mode:
without inputting '#' in advance. The control panel will hang up if password is
input incorrectly three times or user does not press any key in 30 seconds
during the operations.
Whenalarming, the control panel dial user telephone, if there is no voice
Zone
N.C. Detector
after receiving the telephone or user unwilling to wait, pressing any key (key
'5' recommended), the control panel will play voice information immediately.
Alarm information order is user address record then the alarm type voice.
The system will circulate play the alarm voice information.
Note: 1.Do not press any keys during voices 'Di' or messages can not be
received correctly. Do not press any key when the system is in voice alarm
status. 2.If user hang up the telephone without any operation the control
panel will dial user telephone repeatedly.
10.1 Telephone disarm
After picking up the telephone press '# + 4digits password(user
password, operation password) + 3 + # ' to disarm, for example, if user
password is 1234, press '#12343#'.
When the control panel dials to alarm, user can press 3 to disarm after
hearing alarm voice.
10.2 Telephone arm-away
After picking up the telephone, press '# +4digits password(user
password, operation password) + 1 + #' to arm, When alarm occurs, user
has to disarm first and then arm the system again. For example, if user
password is 1234, press '#12343#' and then press '1#' to arm after
hearing prompt voices.
When the control panel dials to alarm, user can press 3 to disarm and
then press 1 to arm after hearing alarm voice.
-28-
G
Figure 5 N.C. Detector
When connecting N.O. detector, connection mode:
Zone
N.O. Detector
G
Figure 6 N.O. Detector
5.2.4 Telephone line connection
Connect telephone line to 'LINE_IN' interface of the control panel
(Refer to the figure 3)
Connect telephone or facsimile machine to 'LINE_OUT' interface of the
controller panel, ensuring no effect on telephone(Refer to the figure 3)
Under the telephone line monitoring status, the control panel will alarm
when the telephone line trouble. 'T' flashes per second in lower right
corner of LCD, buzzer chirps for 1 minute. After disarmed buzzer off and
'T' flashes on LCD
-5-

5.2.5 Relay output
9.3.30 All zones bypassed
Enter: 910
The maximal load capacity of relay terminal ' ' Operations: (PROG user password #) 910 #
Contact capacity 10VA Functions: The system can provide a command to bypass all zones.
Contact maximal voltage 100VDC
Contact maximal current 0.5A
9.3.31All zones reactive
Enter: 920
Relay output type can be set as required including alarm output,fire alarm Operations: (PROG user password #) 920 #
output and armed output. Please refer to program the system Functions: The system reactive all bypassed zones.
5.3 Control panel Installation
9.3.32 All wireless zone detectors canceling
Enter: 930
The control panel should be mounted in a location which allows
convenient access to AC power, telephone line Operations: (PROG user password #) 930 #
Control panel aerial can not be blocked by subject Functions: After the operations, all wireless detectors are canceled.
Please use standby battery to ensure the control panel can work
normally when AC power failure 9.3.33 All remote controllers canceling Enter: 940
Fix the control panel to the wall by screws. Interval between screws in the Operations: (PROG user password #) 940 #
same row is 140mm and vertical intervals between screws in two rows are
80mm. Nail 4 screws in the wall and hang the control panel on the Functions: After the operations, all remote controllers are canceled.
screws(Refer to the figures below) 9.3.34 Zone type initialization Enter: 950
2.5
4.0mm Operations: (PROG user password #) 950 #
Functions: After the operations, all zone types restore to default setting.
9.3.35 System default restoring
Enter: 960
Operations: (PROG user password #) 960 #
Notice: while hanging the control panel:
refer to the figures (depth of screws in the wall)
Figure 7
Figure 8
-6-
Functions: After the operations, all parameters restore to default in factory
default setting. User password, operation password, user address code,
telephone number and date can not be canceled by this operation.
-27-

commands successfully, alarm time, alarm type, corresponding zone type
and zone number display on LCD. Press '6' key to turn up '9' key to turn down
for continually inquiring. Flip requirement press '#' then press '80 XX #'
until the last inquiring finished.
6. Operation
6.1 Control panel composition
For example: Viewing the No.5 event record input password 80 05 #, LCD Record monitor microphone
LCD displays alarm time alarm zone and alarm type.
Armed indicator
Year-Month-Day Hour: Minute
ZONE 17 Panic Power indicator
Alarm indicator
Key
Viewing the No.9 event record, press '#' first then input 80
09
# If the Horn
event record is null, LCD displays: Figure 9
Program Fail! 1. LCD:
Displays time and system working status
Provides function indicator lights and word descriptions for zone status
'T' will flash in the lower right corner of LCD when telephone line trouble
9.3.29 Software version inquiring
Operations: (PROG user password #) 88
#
Enter: 88 X 2. Armed indicator: indicator on (arm-away)
indicator flashes (arm-stay)
Parameters definition: X=1 inquire software version U1
X=2 inquire software version U201
X=3 inquire software version U402
Function: When power up the system, if these three software version of
CPU are not identical, LCD displays 'Version vary!' and buzzer beeps, user
can cancel the alarm by disarm command. In this condition it is better to
inform the supplier in time. This operation can inquire software versions of
the th ree CPU. For example: inquire software version U1: (PROG user
indicator off (disarmed)
3. Power indicator: indicator flashes quickly indicate low-battery; indicator
flashes slowly indicate AC power low-voltage; indica tor
on indicate standby battery and AC power are in
normal working status. While power failure, buzzer
chirps one minute.
4. Alarm indicator : indicator on when zone alarming; indicator flashes when
dialing the center stations.
password #) 88
1
# 5. Horn : Voice guide the operation.
6. Record monitor microphone: spot supervision or used for recording.
The U1 CPU
version V 1.1
Indicate present U1 software version is V1.1
-26-
7. KeyFour function keys: AWAY, STAY, DISARM, and PROG keys. The PROG
key is a compound key and its other function is for panic
Digit key, '*' key and '#' key are used in programming and relevant
operations. '*' key is used to cancel the last operation; '#' key is used
to confirm the input; '6' and '9' are used to turn pages while inquiring
events log or many zones alarm at the same time
Note: Pressing any keys, buzzer sounds 'Di' and keypad backlighting on. If
no key be pressed within 30 seconds the keypad backlighting off.
-7-

6.2 Power up the system
9.3.27 Record playing
Enter: 71 X
Check all wiring are correct Operation: (PROG X #)
71
x
#
Switch on AC power or turn on the standby battery, buzzer will beep twice;
keypad backlighting and power indicator will be on. Keypad begins to
initialize and then buzzer beeps continuously, LCD displays:
Initialize...
LCD circularly displays the status information, buzzer beeps twice per
minute. Buzzer steady beeps to indicate the initialize successful, LCD
displays the status information. The system begins working .If the system
works normally, it will take two seconds for initialization. If this process
takes more than eight seconds, LCD displays 'Communication Error!' and
buzzer chirps per second. The failure cause is bad wiring between the
control panel and keypad.
Parameters setting: X=1~8 specified alarm voice, X=9 user address record
playing
X=1: enter/exit alarm
X=2: active alarm
X=3: perimeter alarm
X=4: panic alarm
X=5: fire alarm
X=6: gas alarm
X=7: anti-tamper alarm
X=8: duress alarm
X=9: (voice recorded by user.)
Function: User can check voice effect.
6.3 System initialize successful
Initialize successful, LCD will display:
Arm-away
Year-Month-Day Hour: Minute
Indicating the system is in arm-away status, the present time is 'Year-
Month-Date Hour: Minute' or the system is in arm-stay or disarm status.
The corresponding display is the status when the system is closed last
time.
Version vary!
Year-Month-Day Hour: Minute
If LCD displays 'Version vary!' and buzzer beeps, that indicate user can
For example: (PROG user password #) 719
While playing, LCD displays:
Playing...
04 sec
After playing, LCD displays:
Input Command
9.3.28 Viewing event log
#
Enter: 80 XX
clean CPU (U1 U201 U402) with different software version. Cleaning Operations: (PROG user password #) 80 XX #
the alarm voice and the display by disarm command. In this status please
contact with the manufacture or the supplier. Refer to the appendix 1 for
inquiring software version.
6.4 Alarm
The alarm can be classified as two types: zone alarm and system trouble.
-8-
Parameters definition: XX=01~40 event logs.
Functions: The system stores 40 event logs, which can be viewed by user
at any time. The system logs alarm in zones, but system trouble for AC
power failure, low battery, telephone line trouble, etc.
Note: XX=01~40 is event number in time order. The latest event number is
01, the rest are numbered in this way. When the fortieth even is logged, the
latest event log replace the oldest event log. After inputting
-25-

Alarm
type
Center
stations
Phone
Alarm
Alarm
indicator
Keypad
buzzer
Bell
Fire zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Gas zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Panic zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Perimeter
zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Active zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Entry/Exit
zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Duress
zone
Yes
Yes
/
Mute
Mute
Anti-tamper
zone
Yes
Yes
On
Chirp (time adjustable)
Chirp (time adjustable)
Telephone
line trouble
No
No
/
Chirp for 1 minute
Mute
AC power
failure
Yes
No
Flash
Chirp for 1 minute
Mute
Low-battery
Yes
No
Flash
Chirp for 1 minute
Mute
XX=21~24 (4 wired zones)
XX=30(control panel with anti-tamper function)
Bypass for all wired zones in factory default setting. Wireless zones are still
valid.
Functions: Close some zone temporarily, then the zone can be activated
freely without alarm.
1) Zone alarm
The zone will alarm if the 24- hour zone be triggered otherwise buzzer will
chirp to indicate user must disarm the system within enrty-delay. If the
zone with entry-delay be triggered, buzzer chirps, LCD displays:
Please disarm!
9.3.25 Zone reactivate
Enter: 66 XX If disarm within the end of entry-delay time, there will be no zone alarm. If
the system is in zone alarm status and the zone be triggered again, the
Operations: (PROG user password #)
66
XX # system will prompt zone alarm only but entry-delay.
Parameters definition: XX means reactive bypassed zone.
XX=01~16 (16 wireless zones) Zone number
Real time
ZONE 17 Panic
Year-Month-Day Hour: Minute T
Zone type
Alarm for telephone
line trouble
XX=17('Panic' key on the keypad and remote
controller)
XX=21~24 (4wired zones)
XX=30(control panel with anti-tamper function)
Functions: User can reactive bypassed zone.
Whenalarming LCD displays relevant alarm information, alarm indicator
on, buzzer chirps. If zones alarm at the same time, LCD circularly displays
the ala rm info rmati on per 2 seconds or press '6' key or '9' key to flip the alarm
zone information.
2) System trouble
The system trouble including low-battery, AC power failure and telephone
9.3.26 Voice recording Enter: 700 line trouble. Under these conditions, buzzer chirps 1 minutes, the indicator
and LCD displays relevant alarm information. The power indicator shows
Operation: (PROG user password # )
700
# low-battery and AC power failure. The letter 'T' flashes on the lower right
While recording LCD displays: corner of the LCD per second to indicate the telephone line trouble.
6.5 Alarm type
Recording...
04 sec
After recording LCD displays:
Input Command
User can check voice effect of recording by inputting command.
Function: The control panel can record voice for 4 seconds. User can
record family address and other alarm voice. When alarming, the system
sends voice alarm information via telephone network.
-24-
-9-

Zone
type
Valid or
not when
disarm
Valid or
not when
away
Valid or
not when
stay
Exit
delay
Entry
delay
Sound and
flash
Mounted
position or
detector
Type
number
Entry/Exit
zone
Invalid
Valid
Valid
Yes
Yes
Yes
Gate
01
Active
zone
Invalid
Valid
Invalid
Yes
Yes
Yes
Indoor
02
Perimeter
zone
Invalid
Valid
Valid
No
No
Yes
Veranda
Window
03
Panic
zone
Valid
Valid
Valid
No
No
Yes
Panic
Button
04
Fire
zone
Valid
Valid
Valid
No
No
Yes
Fire
Detector
05
Gas
zone
Valid
Valid
Valid
No
No
Yes
Gas
Detector
06
Anti-tampe
r zone
Valid
Valid
Valid
No
No
Yes
Anti-tamper
Device
07
Duress
zone
Valid
Valid
Valid
No
No
No
Emergency
Button
08
Zone type
LCD display
Type number
Entry/Exit zone
Entry Exit
01
Active zone
Active
02
Perimeter zone
Perimeter
03
Panic zone
Panic
04
Fire zone
Fire
05
Gas zone
Gas
06
Anti-tamper zone
Tamper
07
Duress zone
Duress
08
7. Zone type and zone assignment
7.1 Zone type
other remote controller. Changing the code learn to solve the above problem.
If the problem is the above reasons, checking the detector and make sure its
carrier frequency is different from the control panel.
Note: After inputting command, user has to trigger a wireless detector within
1 minute, otherwise the system can't enroll the wireless detector. Moreover,
user had better trigger a wireless detector as soon as possible to avoid
influence from wireless clutter wave. During the code learn operation, only
the '*' key is valid, press this key to exit the code learn operation status.
9.3.21 Wireless zone detector canceling
Enter: 62 XX
Operations: (PROG
user password
#) 62
XX
#
Parameters definition: XX=01~16, indicating zone number of wireless
detector.
Functions: Cancel wireless detectors as required.
For example: Cancel NO.03 detector in wireless zones
7.2 Zone assignment press: (PROG user password #) 62 03 #
Wireless zone: 01~16
Wired zone: 21~24 9.3.22 Enroll remote controller Enter: 63 X
Panic zone: 17
Duress zone: 18 Operations: (PROG user password #) 63 X #
Anti-tamper: 30
7.3 Zone type displaying
Parameters definition: X=1~5, number of remote controller.
Functions: The system can enroll 5 remote controllers at most. After
inputting command, press any key of remote controller towards the control
panel until buzzer chirps once. It indicate the system enroll the remote
controller successful. Refer to 9.3.20.
9.3.23 Remote controller canceling
Enter: 64 X
Operations: (PROG user password #) 64 X #
Parameters definition: X=1~5, number of wireless remote controller.
Functions: After canceling some remote controller it have no effect on the
system.
9.3.24 Zone bypass
Enter: 65 XX
8 Function key operation
Operations: (PROG user password #) 65 XX
Parameters definition: XX means zone bypass number.
#
There are 4 function keys on the control panel and remote controller.
(arm-away, arm-stay, disarm and panic)
-10-
XX=01~16 (16 wireless zones)
XX=17 (Panic key on remote controller and
keypad.)
-23-

The factory default setting is all wireless zones are type 4(panic zone).
Wired zone 21 is type 1(entry/exit zone), Wired zone 22 is type 2(active zone),
Wired zone 23 is type 3(perimeter zone) Wired zone 24 is type 4(panic zone)
Functions: Set different zone types .It can not modify the zone types of the
zone 17(panic zone), the zone 18 (duress password zone) and the zone
type of the No.30 (control panel anti-tamper zone)
For example: Set wired zone 21 as gas zone, wireless zone 3 as fire alarm zone,
Arm-away
Arm-stay
Disarm
Panic
press (PROG user password #) 40 21
6
# 40 03 5 #
Note: When the system is in arm- away status, all zones are valid; when the
system is in arm- stay status, active zone is bypassed but other zones are
still valid ; when the system is in disarm status, fire alarm zone, gas zone,
panic zone, anti-tamper zone and duress zone are still valid.
8.1 Arm-away
Figure 10
9.3.20 Enroll wireless zone detector Enter: 61 XX 1. When the system is in disarm/arm-stay status, press 'AWAY' key on the
control panel or 'Arm-away' key on the remote controller, armed
Operations: (PROG user password #) 61 XX # indicator on, buzzer beeps 'Di-Di', the system is in exit-de lay and LCD
Parameters setting: XX=01~16, indicating zone number of wireless detector .
Functions: Enroll wireless detectors as required.
For example: Enroll NO.03 wireless zone detector
displays:
Arming...
press: (PROG user password #) 61 03 # The keypad buzzer will stop after exit-delay expired, LCD displays:
Learning code...
60 sec
The code learn operation time is about 60 seconds .During this period,
trigger the zone detector with code learn, buzzer chirps once to indicate
code lean successful, LCD displays:
Input Command
If the system hasn't received the wireless signal at the end of operation time,
it indicate the code learn failure, buzzer chirps 5 times, LCD displays:
Program Fail!
If code learn fail after trying and trigger the detector many times, there will
be two reasons: First, the enrolling code learn has been used by other
detector in the system; Second, the enrolling code learn has been used by
-22-
Arm-away
Year-Month-Day Hour: Minute
2. When the system is in zone alarm status, press 'AWAY' key on the
control panel or 'Arm-away' key on the remote controller, LCD displays:
Can't arm
Please disarm
3. In Arm-away status, the 'AWAY' key on the control panel is invalid.
8.2 Arm-stay
The arming mode can be applied when user is at home. All zones are in
armed status except 'Active Zone'.
1) If the control panel is in disarmed status, press the 'STAY' key on the
control panel or 'Arm-stay' key on the remote controller, armed
indicator flashes, buzzer chirps once and LCD displays:
Arm-stay
Year-Month-Day Hour: Minute
-11-

2. If the system is in 'Arm-away' status and no zone alarms, press the
'STAY' key on control panel, input password to enter arm-stay status or
press the 'Arm-stay' key on remote controller to enter the arm-stay
X minute (24 hours), default is 8888.
Functions: The system can set 3 groups arm time. If user wants to cancel
some set arm time, set YYYY as 8888.
status directly ,buzzer chirps once ,armed indicator flashes.
3. When the system in zone alarm status, press the 'STAY' key on the
control panel or 'Arm-stay' key on the remote controller, LCD displays:
For example: Set 08:00 and 22:00 as arm time.
press: (PROG user password #) 35 1
#
0800
#
35
2
2200
Can't arm
Please disarm
Note: Before performing the functions above, please set 'Auto-arm/auto-
disarm selection' first. Refer to 9.3.7
4. When the system is in arm- stay status, buzzer chirps once. 9.3.18 Auto-disarm time setting Enter: 36 X YYYY
8.3 Disarm
1. Disarm without reserving the alarm status information press: the 'DISARM'
key on the control panel, LCD displays:
Input Password
Operations: (PROG user password #) 36 X YYYY #
Parameters definition: X means 1~3 groups disarming time. YYYY means
X hour X minute (24 hours), default is 8888.
Functions: The system can set 3 groups disarm time. If user wants to
cancel some set disarming time, set YYYY as 8888.
For example: Set 08:00 and 22:00 as disarm time,
press: (PROG user password #) 36 1 0800 # 36
2
2200
Program: press user password or operation password '0' '#' . Armed #
indicator off, buzzer chirps once, the system is disarmed, LCD displays:
Disarmed
Note: Before performing the functions above, please set 'Auto-arm/auto-
disarm selection' first, refer to 9.3.7. Auto-arm/disarm time must be different
because they can't be operated at the same time.
Year-Month-Day Hour: Minute 9.3.19 Zone definitions Enter: 40 XX Y
2. Disarm with reserving alarm status information: press the function key
'DISARM' on the control panel, LCD displays:
Input Password
If there is no alarm, input user password or operation password then
press '#' confirm. Armed indicator off, buzzer chirps once, the system is
disarmed, LCD displays:
Disarmed
Year-Month-Day Hour: Minute
If the system is in zone alarm status, after disarmed the system, armed
indicator off, buzzer chirps once, LCD displays zone alarm information
but the system is still in disarm status. User can disarm again to clean the
alarm information.
-12-
Operations: (PROG user password #) 40 XX Y #
Parameters definition: XX means wired/wireless zone number.
XX=01~16 (16 wireless zones);
XX=21~24 (4 wired zones);
Y=1, entry/exit zone;
Y=2, active zone;
Y=3, perimeter zone;
Y=4, panic zone;
Y=5, fire zone;
Y=6, gas zone;
Y=7, anti-tamper zone;
Y=8, duress zone;
-21-

XX=10 (100 seconds)
3. Disarm with remote controller, the armed indicator off when disarmed,
buzzer chirps once to indicate disarm the system, LCD displays:
XX=20 (200 seconds) Disarmed
XX=30 (300 seconds)
The factory default setting is XX=04 (40 seconds)
Function: The system entry-delay time adjustment.
Year-Month-Day Hour: Minute
If the system is in alarm status, press the 'Disarm' key, the armed
indicator off, buzzer chirps once, LCD displays the alarm information.
9.3.14 Year setting Enter 32 XX Please disarm again.(Refer to 8.3)
Note: 1. If the system is not connected with the center stations, the alarm
Operations: (PROG user password #) 32 XX #
Parameters definition: XX=00~99, indicating year, default is XX=00.
Functions: Set year in real-time clock, default value is 2000 and the last two
digits is set by user from 2000 to 2099.
For example: Set year 2010.
indicator off after disarmed; 2. After disarm the system, alarm indicator
flashes several times then be off.
8.4 Panic
Press the 'PROG' key on the control panel or the 'Panic' key on the
remote controller for 2 seconds, the control panel will alarm for panic,
press (PROG user password #) 32 10 # alarm indicator on ,buzzer chirps continually ,LCD displays:
9.3.15 Date setting
Enter: 33 XXXX
ZONE 17 Panic
Year-Month-Day Hour: Minute
Operations: (PROG user password #) 33 XXXX #
Parameters definition: XXXX is for date setting, XXXX means X month X
day, default is XXXX=0101 that is 1st Jan.
Functions: Set date in real-time clock.
For example: Set 12th May.
9. System programming
9.1 Password input
1. User needs to input password while disarming, RROG, flipping arm-
press (PROG user password #) 33 0512 # away and arm-stay status. Operations: press DISARM/PROG /STAY+
user password (or operation password) + # before confirming the
9.3.16 Hour and minute setting Enter: 34 XXXX password, LCD displays:
Operations : (PROG
user password
#)
34
XXXX
#
Input Password
Parameters definition: XXXX is for clock setting, XXXX means X hour X
minute (24 hours), default is 0000.
Functions: Set clock in real-time clock.
For example: Set 16:39.
*****
2. After confirmation, if the password is right, LCD displays
corresponding information or buzzer chirps 5 times, LCD displays:
press (PROG user password
#)
34 1639 #
Password Error
9.3.17 Auto-arm time setting Enter: 35 X YYYY
Operations: (PROG user password #) 35 X YYYY #
3. If input wrong password for 5 times continuously, the keyboard will be
Parameters definition: X means 1~3 groups arm time. YYYY means X hour
-20-
locked, LCD displays:
-13-

The keyboard
XX= 02 (2 minutes)
has been locked! XX =10 (10 minutes)
Note: The keypad will be locked with fail operation. The system unlock
automatically under the following status: 1. Restarting the system; 2. XX =20 (20 minutes)
Waiting half an hour.
XX =30 (30 minutes)
9.2 Operation step
Make sure the system in disarmed status otherwise LCD displays: The factory default setting is XX= 10 (10 minutes)
Function: Buzzer and bell chirp times adjustment.
Can't program
Please disarm!
9.3.12 Exit delay time adjustment
Enter: 30XX
Operations: (PROG user password
#)
30
XX #
User disarms first then input: PROG +user password (not the operation
password) + #, the control panel enter programming status, LCD displays:
Input Command
Parameters definition: XX=00~30, indicating time, unit is 10 seconds,
delay time is among 0~300 seconds.
XX=00 (no delay)
XX=01 (10 seconds)
XX=02 (20 seconds)
Following the cursor, input the commands. If the input digits are
incorrectly, press '*' key to delete them then press '#' key to confirm. If the XX=10 (100 seconds)
input command is correct, the control panel chirps twice, LCD displays:
XX=20 ( 200 seconds)
Input Command
XX=30 (300 seconds)
Input the command to set the program, if the command is incorrect,
control panel will chirp five times, LCD displays: The factory setting is XX=10 (100 seconds)
Function: The system exit delay time adjustment.
Command Error!
9.3.13 Entry delay time adjustment
Enter: 31 XX
Then input commands without password. If the command is correct, the
control panel chirps five times, LCD displays:
Program Fail!
That indicates the program is correct but the control panel can not carry
out the command, user should input it again.
-14-
Operations: (PROG user password #) 31 XX #
Parameters setting: XX=00~30, unit is 10 seconds, delay time is among
0~300 seconds.
XX=00 (no delay)
XX=01 (10 seconds)
XX=02 (20 seconds)
-19-

9.3.8 Telephone line monitor
Enter : 26X
Note: If user want to exit program status press '*' to delete digits .When
Operations: (PROG
user password
#)
26
X
# all digits are deleted, press '*' key to exit. This operation can be realized
by pressing '#' key or one function keys .In the programming status, if
Operations definition: X=1 (ON)
X=0 (OFF)
The factory default setting is X=1 (ON)
Functions: When the control panel is not connected with telephone, use this
command to forbid checking the connection of telephone line. Avoid system
trouble voice when user turns on the control panel every time.
without pressing any key for 1 minute, the system will exit present status
and return to display clock and arm/disarm status.
9.3 Basic system programming
To program the system, press PROG user password '#', then enter the
programming status. In this status, setting the system with the command
code without password. LCD displays corresponding status or digits.
9.3.9 Protocol option Enter: 27X
Operations: (PROG
user password #) 27
X # 9.3.1 Communicator programming Enter: 11 XY...Y
Parameters definition: X=1 (4+1 Protocol) (1) Set alarm phone number
X= 0 (Contact ID Protocol) Operations: (PROG user password #) 11 X Y...Y #
The factory default setting is X= 0 and supports
Contact ID Protocol.
Functions: The control panel supports 4+1 and Contact ID communication
Protocol.
Parameters setting: X=1~6, indicates 1~6 groups telephone, 1 is alarm
number of the center stations, 2~6 are personal telephone numbers. Y...Y:
indicates telephone number, telephone number is null in factory default
setting.
Functions: The system can be set 6 groups of alarm telephone number. NO.
9.3.10 Relay output type setting Enter: 28 X 1 is for the center stations. If alarm happens the system will call center
stations and sent out alarm information using ADEMCO protocol to the
center stations. If there is no center stations service, the system begins to
Operations: (PROG user password #) 28 X # dial number from NO.2 according to the alarm information set. If user does
Parameters setting: X=1: alarm output
X=2: fire alarm output(the factory default setting)
not deal with alarm information, the system will continually dial the telephone
number for 30 times. (Refer to remote telephone operation)
For example: if user wants to set NO.2&3, operation as followed: PROG
X=3: arm output User password # 11 2 telephone number # 11 3 telephone
Functions: Relay output is N.O. If alarm output is set, the relay will close number #
when alarm. If fire alarm output is set, the relay will close only fire zone
alarm. If arm output is set, the relay will close when the system in armed
status.
Note: When duress alarm occurs, the system dial the NO.5 and NO.6
telephone of center stations. Recommended: the fifth and the sixth group of
telephone numbers should not be set as personal mobile phone number.
(2) Alarm telephone number cancelling
9.3.11 Bell/Buzzer chirp times setting Enter:29 XX Operations: (PROG User password #) 11 X #
Operations: (PROG user password #) 29 XX #
Parameters definition: XX=00~30, unit is 1 minute. delay time is among 0~
30 minutes
XX=00 (0 minute no alert)
XX= 01 (1 minute)
-18-
Parameters definition: X=1~6, indicates 1~6 groups telephone. 1 for the
center stations, 2~6 for personal telephone numbers.
Function: Cancel telephone number. (Including telephone number of the
center stations)
-15-

9.3.2 User address code setting
Enter:20 XXXX
(2)Operation password canceling
Operations: (PROG user password #) 20 XXXX # Operations: (PROG user password #) 22 X #
Parameter definition: XXXX = 4 digits user address code. The factory default
setting is 1234.
Functions: After setting user address code, when alarm occurs, the center
Parameter definitions: X=1~5(NO.X operation password)
Functions: Password canceling.
stations will determine which control panel is calling. Do not set same user
address code in one center stations. 9.3.5 Ringing attempts adjustment Enter:23X
Operations: (PROG user password #) 23 X #
9.3.3 User password modification Enter:21 XXXX Parameters setting: X means ringing attempts. X=1- 9 times (X=0
Operations: (PROG user password #) 21 XXXX # indicating no telephone remote control and no automatically receiving the
telephone) X = 6 is the factory default setting.
Parameters definition: XXXX is 4 digits new user password. The factory
default setting is 1234. User password must be different from the operation
password otherwise LCD displays 'Please select other Password!' and
buzzer chirps five times to indicate the failed operation .User can clean
operation password first then set user password to avoid the above
limitations.
Functions: Modify user password which ensure the absolute authority to the
system operation. User must hold password to operate the system. After
Functions: When user in other place dials phone connected to the control
panel, the system will receive the telephone automatically. User can input
password to arm or disarm.
Note: If telephone and the control panel use the same telephone line, set
ringing attempts as many as possible to avoid clashing. After setting ringing
attempts, the system begins to accept user remote operation.
setting password, user should ensure its safety and reliability.
Restore password in factory default setting: Hardware restores factory 9.3.6 Bell ON/OFF setting Enter: 24 X
default setting. There is a jumper 'CB400' (Refer to figure 3) in control panel Operations: (PROG user password #) 24 X #
.Normally the jumper is in 'USE' mode, if user forgets password, he/she
should turn off system power, turn jumper to 'DEFAULT' mode, then restart
the system to restore user password in factory default setting. After the
system is initialized successfully, user should turn jumper to 'USE' mode, or
the system will restore password in factory default setting when initialized
next time.
Parameters definition: X=1 (ON)
X=0 (OFF)
The factory default setting is X=1 (ON).
Functions: User can choose bell alarm or not. Setting the bell, it will be on
when the system alarms; otherwise only buzzer and horn alarm.
9.3.4 Operation password setting/canceling Enter:22 X YYYY
(1) Operation password setting 9.3.7 Auto-arm/disarm option Enter: 25 X
Operations: (PROG user password #) 22 X YYYY # Operations: (PROG user password #) 25 X #
Parameter definitions: X=1~5 (NO.X new operation password) YYYY is 4
digits new operation password which is null in factory default setting. The
new operation password must be different from the user password and
duress password otherwise LCD displays 'Please select other Password!'
buzzer chirps five times to indicate the failed operation.
Functions: User can modify five operation passwords which used to
arm/disarm the system or make the control panel flip arm-away and arm-stay
status but program the system.
-16-
Parameters definition: X=1: valid (arm/disarm allowed).
X=0: invalid (arm/disarm not allowed)
T h e f a c t o r y d ef au lt s e t t i n g i s X = 0 ( a r m / d i s a r m
no t allowed)
Functions: The system can be set auto-arm or auto-disarm in certain
moment as required. After setting these function, auto-arm/ auto-disarm time
can be set. Refer to 9.3.17 and 9.3.18 for detail information.
-17-
Table of contents
Other LONGHORN Control Panel manuals
Popular Control Panel manuals by other brands

Siemens
Siemens MJ-XL Installation and operation manual

Biamp
Biamp TEC-X 1000 Installation & operation guide

Teknim
Teknim TFP-121 Series Installation & operating manual

Smarteh
Smarteh LONGO LPC-2 user manual

Bosch
Bosch Rexroth IndraControl VAM 11.1 Project planning manual

Ecler essentials
Ecler essentials eMCONTROL1 user manual