Loreme THL36 User manual

E 1
TEMPERATURE PROTECTION RELAY
TEMPERATURE REGULATOR
LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3
Phone 03.87.76.32.51 - Telefax 03.87.76.32.52
Download manual at : www.loreme.fr
CONFIGURATION HANDBOOK
THL36
REV 0.2 - 19/02/16

E 2LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Comm[email protected] - Tech[email protected]r
Table of contents
DEVICE PRESENTATION ........................................................................................................................................ p3
RELAY THRESHOLD SETTING .............................................................................................................................. p4
CONFIGURATION .................................................................................................................................................... p4
1) Input configuration ................................................................................................................................... p4
2) Relay configuration ................................................................................................................................... p4
2.1) Threshold configuration ............................................................................................................. p4
2.2) Hysteresis configuration ............................................................................................................. p4
2.3) Threshold type configuration ..................................................................................................... p4
3) End of configuration ................................................................................................................................. p5
EMC CONSIDERATION ........................................................................................................................................... p6
1) Introduction ............................................................................................................................................... p6
2) Recommendation of use .......................................................................................................................... p6
2.1) General remarks .......................................................................................................................... p6
2.2) Power Supply ............................................................................................................................... p6
2.3) Inputs / Outputs ........................................................................................................................... p6
WIRING / OUTLINE DIMENSIONS .......................................................................................................................... p7

TABLE OF CONTENTS
E 3
THL36 is a digital thermostat usable for simple temperature regulation (heating or cooling). It is fully programmable from
the front side. The device can be used with 2 or 3 wires PT100 sensors or with J, K, T thermocouple, temperature com-
pensated. It has a 3 digit display for temperature reading, 2 keys for setting the alarm threshold and configuration, and a
output relay inverter with 10 A breaking capacity for regulation.
Technical specifications can be downloaded at: http://www.loreme.fr/fichtech/THL36_eng.pdf
USER INTERFACE
Threshold setting access or “Yes” button or value increment.
Threshold setting access or “No” button or value decrement.
+Configuration access.
Visualization
The device can display the measured temperature over a range of -99 °C to +999 °C with 1 digit after the decimal
point. Besides measured temperature, different messages can be displayed:
- "Hi " for a measure overflow.
- "Lo " for a measure underflow.
- "Err" for a sensor breaking.
- "- - -" for a measuring circuit default.
- "Ert" for a default of the integrated temperature sensor (thermocouple cold junction compensation).
The relay activation is indicated by the top right point of the display. In case of breaking or default, the relay is deacti-
vated.
Device Presentation
lift the cover here
PT100 or Tc sensor
input connector
Output relay connector
Power connector
7 segments 3 digits (1000 pts)
display.
threshold adjustment and
configuration buttons.
Relay state indicator:
On : relay is activated.
Off : relay is deactivated.

TABLE OF CONTENTS
E 4LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Comm[email protected] - Tech[email protected]r
Threshold setting
Press or button to access the setting mode. The device displays the threshold value and the buttons or
permits to increment or decrement the value. the display blinks during the setting. The adjusted value is automatically
validated after 4 seconds if no button is pressed. The threshold value is then stored in internal non volatile memory and
the message ‘End’ appears briefly indicating success of memorizing.
Configuration
Press +buttons for more than five seconds to access configuration mode.
1) Input configuration
The device displays the current input type. Pressing button validates the choice and move to the relay configuration.
Press button to display the next input type.
The displayed input type choices are:
- ‘rtd’ for a platinum PT100 sensor.
- ‘tcJ’ for à J thermocouple sensor.
- ‘tcH’ for à Kthermocouple sensor.
- ‘tct’ for à Tthermocouple sensor.
2) Relay configuration
The device displays ‘rEL’. Pressing button provides access to the relay configuration. Pressing button leaves
the configuration mode and returns to measure mode.
The relay parameters are:
- Threshold,
- Hysteresis,
- The type of detection, high or low.
2.1) Threshold configuration
The device displays the message ‘thr’. Pressing button provides access to the threshold setting and pressing but-
ton to switches to the next topic. The device displays the threshold value and the buttons or permits to increment
or decrement the value. the display blinks during the setting. The adjusted value is automatically validated after 4 sec-
onds if no button is pressed.
2.2) Hysteresis (dead band) configuration
The device displays the message ‘db’. Pressing button provides access to the hysteresis setting and pressing
button to switches to the next topic. The device displays the hysteresis value and the buttons or permits to incre-
ment or decrement the value. the display blinks during the setting. The adjusted value is automatically validated after 4
seconds if no button is pressed.
2.3) Type of detection
The user can, with this setting, set the direction of the threshold detection.
It works in this manner:
- High threshold detection (cooling):
.alarm is activated when temperature goes above threshold,
.alarm is removed when temperature goes below threshold minus hysteresis.
- low threshold detection (heating):
.alarm is activated when temperature goes below threshold,
.alarm is removed when temperature goes above threshold plus hysteresis.

TABLE OF CONTENTS
E 5
The configuration possibilities are:
- High detection with the display ‘AHi’.
- Low detection with the display ‘ALo’.
The actual configuration is displayed on topic access.
Pressing button validates the displayed choice and ends the configuration. Press button to display next choice.
3) End of configuration
The new parameters are saved in non volatile memory and the message ‘End’ is displayed briefly, indicating that the
parameters have been successfully saved. Then, device returns to measure mode.

TABLE OF CONTENTS
E 6LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Comm[email protected] - Tech[email protected]r
1) Introduction
To meet its policy concerning EMC, based on the Community directives 2014/30/EU & 2014/35/EU, the
LOREME company takes into account the standards relative to this directives from the very start of the con-
ception of each product.
The set of tests performed on the devices, designed to work in an industrial environment, are made in accor-
dance with IEC 61000-6-4 and IEC 61000-6-2 standards in order to establish the EU declaration of confor-
mity. The devices being in certain typical configurations during the tests, it is impossible to guarantee the re-
sults in every possible configurations. To ensure optimum operation of each device, it would be judicious to
comply with several recommendations of use.
2) Recommendations of use
2.1 ) General remarks
- Comply with the recommendations of assembly indicated in the technical sheet (direction of assembly,
spacing between the devices, ...).
- Comply with the recommendations of use indicated in the technical sheet (temperature range, protection
index).
- Avoid dust and excessive humidity, corrosive gas, considerable sources of heat.
- Avoid disturbed environments and disruptive phenomena or elements.
- If possible, group together the instrumentation devices in a zone separated from the power and relay cir-
cuits.
- Avoid the direct proximity with considerable power distance switches, contactors, relays, thyristor power
groups, ...
- Do not get closer within fifty centimeters of a device with a transmitter (walkie-talkie) of a power of 5 W, be-
cause the latter can create a field with an intensity higher than 10 V/M for a distance fewer than 50 cm.
2.2 ) Power supply
- Comply with the features indicated in the technical sheet (power supply voltage, frequency, allowance of the
values, stability, variations ...).
- It is better that the power supply should come from a system with section switches equipped with fuses for
the instrumentation element and that the power supply line be the most direct possible from the section
switch.
- Avoid using this power supply for the control of relays, of contactors, of electrogates, ...
- If the switching of thyristor statical groups, of engines, of speed variator, ... causes strong interferences on
the power supply circuit, it would be necessary to put an insulation transformer especially intended for instru-
mentation linking the screen to earth.
- It is also important that the installation should have a good earth system and it is better that the voltage in
relation to the neutral should not exceed 1V, and the resistance be inferior to 6 ohms.
- If the installation is near high frequency generators or installations of arc welding, it is better to put suitable
section filters.
2.3 ) Inputs / Outputs
- In harsh conditions, it is advisable to use sheathed and twisted cables whose ground braid will be linked to
the earth at a single point.
- It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling
phenomena.
- It is also advisable to limit the lengths of data cables as much as possible.
EMC Consideration

TABLE OF CONTENTS
E 7
Power supply terminals 7 & 8.
Relay terminals Work (10), Rest (11), Common (12).
PT100 input terminals 4(+), 5(-), 6(line).
Thermocouple input terminals 4(+), 5(-).
Wirings / Outline dimensions
Table of contents
Other Loreme Relay manuals
Popular Relay manuals by other brands

Siemens
Siemens SIRIUS 8WD44 Original operating instructions

BECKWITH ELECTRIC
BECKWITH ELECTRIC M-0236B Instruction book

Rockwell Automation
Rockwell Automation Allen-Bradley Guardmaster Minotaur MSR117T installation instructions

Berker
Berker 75341101 Operation instructions

Pickering
Pickering PXI 40-780A user manual

Zamel
Zamel exta PBM-07 Manual instruction