Loreme THL101 User manual

E 1
TEMPERATURE SWITCH WITH LOCAL DISPLAY
LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3
Phone 03.87.76.32.51 - Telefax 03.87.76.32.52
Download manual at : www.loreme.fr
CONFIGURATION HANDBOOK
THL101
REV 0.0 - 28/09/09

E 2LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: C[email protected]r - Technique@Loreme.fr
Table of contents
DEVICE PRESENTATION ........................................................................................................................................ p3
VISUALIZATION ....................................................................................................................................................... p3
CONFIGURATION .................................................................................................................................................... p4
1) Relays configuration ................................................................................................................................ p4
1.1) Threshold configuration ............................................................................................................. p4
1.2) Hysteresis configuration ............................................................................................................. p4
1.3) Threshold type configuration ..................................................................................................... p4
2) End of configuration ................................................................................................................................. p4
EMC CONSIDERATION ........................................................................................................................................... p5
1) Introduction ............................................................................................................................................... p5
2) Recommendation of use .......................................................................................................................... p5
2.1) General remarks .......................................................................................................................... p5
2.2) Power Supply ............................................................................................................................... p5
2.3) Inputs / Outputs ........................................................................................................................... p5
WIRINGS .............................................................................................................................................................. p6

TABLE OF CONTENTS
E 3
The THL101 is a outdoor field thermostat with local indicator for a PT100 2 or 3 wires input, mounted in an enclosure
resistant to harsh environments (> IP65).
It brings together on the same circuit functions of measurement, display, and alarm configuration. It consists of:
- a 3 digits green LED display,
- 2 LED for the state of the relay,
- 2 relays,
- 2 buttons for setting the alarm relay.
Technical specifications can be downloaded at: http://www.loreme.fr/fichtech/THL101_eng.pdf
USER INTERFACE
Push button functions
•/ Configuration access or <YES> or value increment button.
• <NO> or value decrement button.
Visualization
The device displays the temperature measured over a range of -99 ° C to 650 ° C.
An overflow will be indicated by the message "Hi " and an underflow will be indicated by the message "Lo ".
A sensor failure is indicated by the message "Err" and a defect in the measuring circuit is indicated by "- - -".
Device Presentation
Buttons
Terminals for
PT100
LED display
1000 points.
Terminals for
relay 1 and 2
Relay 2 state LED
(On if relay is activated)
Relay 1 state LED
(On if relay is activated)
/

TABLE OF CONTENTS
E 4LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: C[email protected]r - Technique@Loreme.fr
Configuration
The buttons are used to configure the two alarm relays. The configurable parameters are:
- The threshold,
- the hysteresis.
- The type of alarm detection, high or low.
Access to the configuration is done by pressing the button.
1) Relays configuration
When entering configuration mode, the unit displays ‘AL1’. The button provides access to configuration sections of
the relay 1. The button provide access to configuration sections of the relay 2 , The unit displays ‘AL2’, The button
provides access to configuration sections of the relay 2 and the key exits of configuration sections.
1.1) Threshold configuration
The device displays the message ‘thr’. Pressing button provides access to the threshold setting and pressing
button to switches to the next topic. The device displays the threshold value and the buttons or permits to incre-
ment or decrement the value. the display blinks during the setting. The adjusted value is automatically validated after 4
seconds if no button is pressed.
1.2) Hysteresis (dead band) configuration
The device displays the message ‘db’. Pressing button provides access to the hysteresis setting and pressing
button to switches to the next topic. The device displays the hysteresis value and the buttons or permits to incre-
ment or decrement the value. the display blinks during the setting. The adjusted value is automatically validated after 4
seconds if no button is pressed.
1.3) Type of detection
The user can, with this setting, set the direction of the threshold detection.
It works in this manner:
- High threshold detection (cooling):
.alarm is activated when temperature goes above threshold,
.alarm is removed when temperature goes below threshold minus hysteresis.
- low threshold detection (heating):
.alarm is activated when temperature goes below threshold,
.alarm is removed when temperature goes above threshold plus hysteresis.
The configuration possibilities are:
- High detection with the display ‘AHi’.
- Low detection with the display ‘ALo’.
The actual configuration is displayed on topic access.
Pressing button validates the displayed choice and ends the configuration.
Press button to display next choice.
2) End of configuration
The new parameters are saved in non volatile memory and the message ‘End’ is displayed briefly, indicating that the
parameters have been successfully saved. Then, device returns to measure mode.
Note:
If the waiting time for action on the buttons & exceeds 30 seconds then the device automatically returns to meas-
urement mode without saving the new settings.

TABLE OF CONTENTS
E 5
1) Introduction
To meet its policy concerning EMC, based on the Community directives 2014/30/EU & 2014/35/EU, the
LOREME company takes into account the standards relative to this directives from the very start of the con-
ception of each product.
The set of tests performed on the devices, designed to work in an industrial environment, are made in accor-
dance with IEC 61000-6-4 and IEC 61000-6-2 standards in order to establish the EU declaration of confor-
mity. The devices being in certain typical configurations during the tests, it is impossible to guarantee the re-
sults in every possible configurations. To ensure optimum operation of each device, it would be judicious to
comply with several recommendations of use.
2) Recommendations of use
2.1 ) General remarks
- Comply with the recommendations of assembly indicated in the technical sheet (direction of assembly,
spacing between the devices, ...).
- Comply with the recommendations of use indicated in the technical sheet (temperature range, protection
index).
- Avoid dust and excessive humidity, corrosive gas, considerable sources of heat.
- Avoid disturbed environments and disruptive phenomena or elements.
- If possible, group together the instrumentation devices in a zone separated from the power and relay cir-
cuits.
- Avoid the direct proximity with considerable power distance switches, contactors, relays, thyristor power
groups, ...
- Do not get closer within fifty centimeters of a device with a transmitter (walkie-talkie) of a power of 5 W, be-
cause the latter can create a field with an intensity higher than 10 V/M for a distance fewer than 50 cm.
2.2 ) Power supply
- Comply with the features indicated in the technical sheet (power supply voltage, frequency, allowance of the
values, stability, variations ...).
- It is better that the power supply should come from a system with section switches equipped with fuses for
the instrumentation element and that the power supply line be the most direct possible from the section
switch.
- Avoid using this power supply for the control of relays, of contactors, of electrogates, ...
- If the switching of thyristor statical groups, of engines, of speed variator, ... causes strong interferences on
the power supply circuit, it would be necessary to put an insulation transformer especially intended for instru-
mentation linking the screen to earth.
- It is also important that the installation should have a good earth system and it is better that the voltage in
relation to the neutral should not exceed 1V, and the resistance be inferior to 6 ohms.
- If the installation is near high frequency generators or installations of arc welding, it is better to put suitable
section filters.
2.3 ) Inputs / Outputs
- In harsh conditions, it is advisable to use sheathed and twisted cables whose ground braid will be linked to
the earth at a single point.
- It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling
phenomena.
- It is also advisable to limit the lengths of data cables as much as possible.
EMC Consideration

TABLE OF CONTENTS
E 6LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: C[email protected]r - Technique@Loreme.fr
Wirings
Power supply +: terminal 1.
Power supply -: terminal 2.
Input PT100: terminals 3, 4, 5.
Relay 1: terminals 7, 6
Relay 2: terminals 8, 6
Table of contents
Other Loreme Thermostat manuals
Popular Thermostat manuals by other brands

Neomitis
Neomitis RT7 RF operating instructions

Hetta
Hetta HM01RF quick start guide

SmartWay Solutions
SmartWay Solutions Talking Thermostat VT3000 user guide

KMC Controls
KMC Controls CTE-1005 installation guide

meitav-tec
meitav-tec ETN24-SUPER-SH-F Owner's manual & technnician settings

Warmup
Warmup 3IE installation guide