4
Alfa LU-VE is a trademark registered and owned by LU-VE Group.
Alfa LU-VE reserves the right to change specifications without prior notification.
Electrically powered component.
Switch off power supply before any
maintenance or installation activity.
Risk of injuries.
Wear safety footwear.
Risk of injuries.
Wear protective gloves.
2 General
2.1 Operating principle
Alfa LU-VE finned coil air heat exchangers have been designed to achieve an optimized exchange
of thermal energy between air and another medium. The ‘heart’ of our air heat exchangers is the
finned coil, built up from a circuit of interconnected tube serpentines and fins to increase the heat
exchanging surface. Thanks to the combination of key design variables (coil materials, coil geom-
etry, casing design, fan type), air heat exchangers are very versatile products with a great variety of
applications in many industries.
Air cooled condensers are key components in air cooling systems with an evaporating refrigerant
like HFO/HFC, ammonia or CO2. In these systems air cooled condensers are used to condensate
(liquify) the hot, compressed refrigerant gas using relatively cold outside air to cool down the cond-
erser tubes.
CO2gas coolers replace traditional air-cooled condensers in refrigerating systems designed for
the use of carbon dioxide as a single refrigerant. In a gas cooler, hot compressed CO2gas flows
through the cooler tubes and is cooled down by the ambient air that is forced through the coil. The
refrigerant gas is not liquefied in the gas cooler, but later on in the expansion valve. Air cooled gas
coolers operate with considerably higher pressures than air cooled condensers.
2.2 Safety
Ensure that the following guidelines are observed:
• All work on the equipment must be carried out by trained personnel.
• The electrical supply is suitable for the equipment supplied.
• Refrigerant, temperature and pressure must agree with the data on the product label of the rel-
evant heat exchanger.
• As the heat exchanger is supplied indirectly, the producer is not acquainted with its actual appli-
cation.
• The heat exchanger should be installed in conformance with all recognized national standards of
electrical and refrigeration installation practice.
• The supplied heat exchanger is optimized for the refrigerants as stated in the data sheet or
order documents. Please contact Alfa LU-VE before using any other refrigerants. The allowed
maximum pressure (design pressure PS) is noted on the type plate. During production the heat
exchanger was subjected to a strength test exceeding the design pressure PS. However, during
normal use the design pressure PS may not be exceeded.
• Heat exchangers supplied by Alfa LU-VE are normally not equipped with a high-pressure cut
out. The installer is responsible for fitting a high-pressure cut out on the system in which the
heat exchanger is used.
• The heat exchanger shall not be blocked in. If the ambient temperature rises, the pressure could
rise and exceed the design pressure.
• It is not permitted to use the heat exchanger for any purpose other than the one it was designed
for by Alfa LU-VE.
2.3 Transport and storage
During transportation the heat exchanger must be handled with all required care. Any instruction or
warning signs attached to the heat exchanger or the packaging must be followed. Avoid shocks or
continuous vibrations during transport. These may cause damage to the product. If required, con-
sult Alfa LU-VE and disassemble during transport any parts that are likely to be set into vibration.
Air heat exchangers must be adequately fixed on the transport vehicle. If temporary storage of the
heat exchanger is required, the following points should be observed:
• Store the heat exchanger in its packing, in a dry place with sufficient protection against sun and
other environmental influences.