Lynx LYNXR Assembly instructions

/<1;56HULHV
6HFXULW\6\VWHPV
,QVWDOODWLRQDQG6HWXS*XLGHIRU
/<1;5/<1;5DQG/<1;5(1
AWAY
OFF
STAY
AUX
®
K5963 5/01
®

–2–
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage
for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the
National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of
the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping
area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke
detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining
room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed.
Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the
door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or
humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could
prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
DINING KITCHEN
BEDROOM
BEDROOM
.
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BEDROOMBEDROOM
BEDROOM
BEDROOM
LIVING
ROOM
TV ROOM
DINING
LIVING ROOM
LIVING ROOM
BASEMENT
BEDROOMBEDROOM
BEDROOM
CLOSED
DOOR
GARAGE
KTCHN
KITCHEN
TO
BEDROOM
01000-002-V0
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would
include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to
the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the
phone lines, if connected to an alarm monitoring station).

–3–
Table of Contents
SYSTEM FEATURES....................................................................................................................... 4
MOUNTING THE CONTROL ......................................................................................................... 5
WIRING CONNECTIONS................................................................................................................ 6
AC POWER AND BACKUP BATTERY......................................................................................... 9
INSTALLING WIRELESS ZONES................................................................................................ 11
MECHANICS OF PROGRAMMING............................................................................................. 14
ZONE RESPONSE TYPE DEFINITIONS...................................................................................... 15
DATA FIELD DESCRIPTIONS ..................................................................................................... 17
*56 ENHANCED ZONE PROGRAMMING MODE ..................................................................... 24
*80 DEVICE PROGRAMMING MENU MODE ........................................................................... 29
*81 ZONE LIST MENU MODE..................................................................................................... 32
*83 ENHANCED SEQUENTIAL MODE ...................................................................................... 33
*84 ASSIGN ZONE VOICE DESCRIPTORS................................................................................ 35
*85 RECORD CUSTOM VOICE DESCRIPTORS ........................................................................ 37
REMOTE PROGRAMMING/CONTROL (DOWNLOADING).................................................... 38
SYSTEM OPERATION .................................................................................................................. 39
TESTING THE SYSTEM................................................................................................................ 44
SYSTEM COMMUNICATION ...................................................................................................... 45
TROUBLESHOOTING GUIDE...................................................................................................... 47
REGULATORY AGENCY STATEMENTS .................................................................................. 49
SPECIFICATIONS.......................................................................................................................... 50
LYNXR/LYNXR24 PROGRAMMING DEFAULT TABLES....................................................... 51
LYNXR-EN PROGRAMMING DEFAULT TABLES................................................................... 52
INDEX............................................................................................................................................. 55
LIMITATIONS OF THIS SYSTEM STATEMENT....................................................................... 57
WARRANTY................................................................................................................................... 58
SUMMARY OF CONNECTIONS DIAGRAM.............................................................................. 59

–4–
System Features
8/LYNXR and LYNXR-EN are not intended for UL985 Household Fire applications
unless a 24-hour backup battery (P/N LYNXRCHKIT-HC) is installed.
Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended
for home automation.
The LYNXR-Series controls are self-contained, rechargeable wireless control/communicators that feature easy installation
and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each zone
(LYNXR-EN if programmed). The following illustration highlights the main features of this system.
AWAY
OFF
STAY
AUX
®
ZONES and DEVICES
•1 hardwire zone
•Up to 24 wireless zones
(5800 Series Transmitters)
•Up to 16 wireless button zones
•Up to 8 Powerline Carrier Devices
•Supports wireless keypads
8 USER CODES
•Installer code
•Master code
•5 Secondary codes
•Duress code
•3 Panic functions
OTHER FEATURES
•Exit error feature (detects difference between
an actual alarm and exit alarm caused by
leaving a door open after the exit delay
expires)
•Event log stores up to 84 events
•Macro/ 1-button paging
•RF Jam Detection
• Remote phone control
ALARM OUTPUT
•Built-in sounder
•Piezo output
(30mA max.)
•Bell output
(120mA max.)
•Steady output for
burglary/panic
•Temporal pulse
output for fire alarms
•Long Range
Radio/Alarm audio
Verification
PROGRAMMING
•Options stored in EEROM
•Can be uploaded, downloaded or
controlled via IBM-compatible
computer using Compass downloader
software and specified HAYES
modem
COMMUNICATION
•Ademco Low Speed
•Sescoa/Radionics
•Ademco Express
•Ademco Contact ID
•Paging feature
SYSTEM POWER
•Primary Power: Ademco
1332/1332X10 Plug-in Transformer,
110VAC to 9VAC, 15VA output
(1332CN in Canada)
•Backup battery: Six 1.2V
rechargeable nickel-metal hydride
batteries.
FEATURES
•Real-time Clock display and Fixed-Word display
•Message Center (for user recorded messages)
•Voice announcement of system and zone status
•Voice chime
• Alarm Clock
•Reminder
•X-10 Scheduling
•Latch Key Reports
•Automatic Stay Arming
SPECIAL FEATURES
LYNXR24
•24-hour backup
LYNXR-EN
•Two-way voice
communication
•Speaker phone
operation

–5–
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from
the front assembly board.
Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific
model being installed prior to programming the system.
DISCONNECT
THIS END ONLY!
01009-003-V0
MXXXX
K5108
REDWIRE
MARKING
16
1
LOCKING TABS
PC BOARD
PART NUMBER
LOCATION
PC BOARD
PART NUMBER
LOCATION
Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the LYNXR-Series controls to be
used on a desktop.
AWAY
OFF
STAY
AUX
01000-004-V0
WIRE ENTRY
KNOCKOUT
(1 of 3)
®
1. Separate the front assembly from the
back plate by pressing on the two
locking tabs at the top of the unit.
2. Carefully disconnect the ribbon cable
from the front assembly, leaving the
ribbon cable connected to the
terminal block PC board. The back
plate contains the terminal block for
making wiring connections.
3. Mount the back plate to a sturdy wall,
feeding the field wiring through the
appropriate openings in the back plate.
4. After wiring connections are made,
carefully reconnect the ribbon cable to
the front assembly PC board connector
(properly aligning the red wire).
5. Before closing the assembly, verify
which LYNXR model is being installed
by checking the model number printed
on the PC Boards. (Example:
SALYNXREN indicates the unit being
installed is a LYNXR-EN.)
6. Snap the front assembly to the back
plate so it is held by the locking tabs.
1. Slide the control panel onto the
mounting base locking tabs.
2. Bring all wiring through the bottom of
the mounting base, using one of the
three wire entry locations, before
making connections to the control
panel.
3. Use tie-wraps to secure the wiring to
the built-in wire loops as needed.
Use the two supplied screws to secure
the control panel to the mounting base.

–6–
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of
Connections diagram on the inside back cover when making connections.
MXXXX
K5108
01009-005-V0
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a noncorrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
EARTH GROUND
See Earth Ground paragraph.
PHONE LINES
Use either the plug-in jacks or the
screw terminals.
HARDWIRE ZONE
Supports 1 EOLR supervised zone using either closed circuit
or open circuit sensors.
SOUNDERS
The system includes a built-in sounder in the master keypad. If
desired, an external bell or piezo sounder can be connected.
Bell: Use a 6-14V bell with maximum current drain of 120mA.
Piezo: Use a 6-14V piezo sounder with maximum current drain of
30mA.
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following: 3
pulses – pause – 3 pulses – pause – 3 pulses. . .
POWERLINE CARRIER DEVICES
Supports up to 8 Powerline Carrier
Devices for turning on/off lights and
appliances. Requires the use of an
ADEMCO 1332X10 transformer.
AC TRANSFORMER
Use the supplied ADEMCO
1332X10 9VAC, 15VA
Plug-in Transformer
(1332CN in Canada).
LOCAL SOUNDER DISABLE JUMPER
Remove the shorting jumper (shunt) to disable local sounder,
leaving only the external sounder active.
UL NOTE: Do not remove the shorting jumper (the shunt) for
UL installations.
LONG RANGE RADIO
Compatible with ALARMNET 7845C and 7720
Devices. LYNXR and LYNXR24 are compatible with
the LYNXAVM.

–7–
Wiring Connections
Wiring Connections
2. Make Phone Line Connections - For local or full line
seizure proceed to the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the
8-position jack or terminals 2 (TIP) and 3 (RING).
b. Connect the handset phone lines to either the RJ11
jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series
with the incoming phone line. Plugging the Direct
Connect Cord directly into the RJ31X jack, allows the
control to seize the phone line when an alarm occurs
and normal phone line usage by the premises phones if
the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines
(typically red and green, respectively) and connect
them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown)
respectively.
c. Wire the flying leads of a Direct Connect Cord to the
control’s phone terminals as shown in the diagram
or plug into the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
RJ31X
1
2
345
6
7
8
RING
TIP
INCOMING
PHONE LINE
TO
PREMISES PHONES
TIP RING TIP RING
BROWN
GREY
RED
GREEN
INCOMING
PHONE LINE TO
PREMISES
PHONES
}
}
GREENRED
GREY BROWN
RING
TIP
DIRECT
CONNECT
CORD
OR
OR
8-POSITION
JACK
01000-008-V0
Full Line Seizure Connections
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
3. Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections
diagram.
b. Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in
series with the devices, following the
last device.
c. Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
4. Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by
removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding
will occur upon AC loss, since the external sounder does not operate when AC power is lost.
8/Do not remove shorting jumper (the shunt) for UL installations.
5. Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
a. Remove the shorting jumper (shunt) on the terminal board.
6. Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF
CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer
to the
*80 Device Programming Menu Mode
section for details on programming Powerline Carrier Devices.

–8–
Wiring Connections
INCOMING
PHONE
LINE
TO
HANDSET
PHONE
LINE
WARNING:
TO PREVENT RISK OF SHOCK
DISCONNECT TELEPHONE LINE
ATTELECOM JACK BEFORE
SERVICING THIS UNIT.
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO
DISABLE
WEEKLY TESTING IS
REQUIREDTO ENSURE
PROPER OPERATION
OFTHIS SYSTEM
ALL OUTPUT CIRCUITS ARE POWER LIMITED.
PREMISES
TELEPHONE
2k OHMS
EOLR
1234865 11
710 12 15 16
13 14
PHONE ZONE
AAV / LRR
TRIGGER
(LYNXR/LYNR24)
LRR
TRIGGER
(LYNXR-EN) SOUNDERS PLCD AC
EARTH
GROUND
EARTH
GROUND
HARD
WIRED
ZONE
INCOMING
TELEPHONE
LINE
RING
TIP
RING
TIP ( ) ( ) (+)
(+)( )
(+)
PIEZO
6-14VDC
120mA max.
(e.g.WAVE2EX)
6-14VDC
30mA max.
DATA
OUT SYNC
IN
POWERLINE
CARRIER DEVICES
RJ11
8
POS
JACK
AC
AC
SYNC
COM
DATA
9
BELL
TRIGGER
SIGNAL
(NEG)
THE LYNX SERIES CONTROLS ARE
EQUIPPED WITH AN INTEGRAL
RECHARGEABLE BATTERY PACK.
LYNXR: P/N LYNXRCHKIT-SC
LYNXR24: P/N LYNXRCHKIT-HC
LYNXR-EN: P/N LYNXRCHKIT-SC
OR
P/N LYNXRCHKIT-HC
01009-009-V0
NOTE
USE ONLY 1332/1332X10 OR 1332CN
TRANSFORMERS PROVIDED
1332/
1332X10/
1332CN
PLUG-IN
TRANSFORMER
9VAC, 15VA
1332X10
ONLY
CONNECTIONS
REPLACE EVERY FOURYEARS

–9–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in Canada). Refer to
the wiring table below for wire gauge and length.
Use only the provided ADEMCO
1332/1332X10 or 1332CN Transformer
Distance from Transformer
to Control Wire Gauge
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between
terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery. In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a “low battery”
message is displayed and a report is sent to the central station. In addition, the system will beep once every 45 seconds to
audibly indicate a low battery condition (press any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the 1332/1332X10 (1332CN in
Canada) AC Transformer to terminals 15 and 16
as shown in the wiring diagram.
2. Remove battery retainer.
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
6. Connect battery connector to receptacle on
terminal block PC board.
7. After all wiring connections have been made, snap
the front assembly to the back plate and plug the
transformer into a 24-hour, 110VAC unswitched
outlet.
8. Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should
clear within four hours or by entering Test Mode.
01009-007-V0
1
BATTERY
RECEPTACLE WIRING
TERMINALS
MXXXX
K5108
TAPE
RETAINER
BATTERY
PACK
16
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
Ensure the cover is snapped closed prior to applying AC power.

–10–
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR Series is equipped with an integral, replaceable, rechargeable battery pack composed of six (6) rechargeable
1.2-volt nickel-metal hydride batteries. Select the appropriate battery pack, based on the installation’s requirement, and install
the battery pack.
Model/Part Number
Battery StandbyTime
Low Battery Notification
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion
LYNXRCHKIT-HC 24-hours (minimum) At least 1-hour before battery depletion
Replacing the Rechargeable Battery
01009-006-V0
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
MXXXX
K5108
RETAINER
BATTERY
RECEPTACLE
BATTERY
CONNECTOR
BATTERY
PACK
TAPE
Ensure the control panel assembly is snapped closed prior to applying AC power.
1. When battery replacement is required, unplug
the transformer from the wall outlet, and open
the control panel cover.
2. Remove the battery retainer and disconnect the
battery pack connector from the receptacle on
the terminal block PC board.
3. Remove the battery pack from the back plate.
4. If required, replace the tape that secures the
battery pack.
5. Install a replacement battery pack (P/N
LYNXRCHKIT-SC or LYNXRCHKIT-HC) into the
back plate.
6. Install the battery retainer.
7. Connect the battery connector to the receptacle
on the terminal block PC board.
8. After the wiring connection has been made, snap
the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
10.Rechargeable batteries may take up to 48-hours
to fully charge. The “LOW BAT” message should
clear within four hours or by entering Test Mode.

–11–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the system using the
*56 or *83 interactive mode, or input to the control via the downloader. 5800 Series transmitters (except the 5800RL
and 5827, described separately) do not have DIP switches. Each transmitter's zone number is programmed into the
system in *56 mode. Some transmitters, such as the 5816 and 5817, can support more than one "zone" (referred to as
loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1, the reed contact is loop 2.
Each loop must be assigned a different zone number.
8/The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for
UL Household Burglary installations, the loop wiring may not exceed 3 feet.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP,
5819, 5819S(WHS & BRS), 5827BD, and 5850(GBD) transmitters are not intended for any UL
installations.
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to each
individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input
number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV, 5827, or 5827BD Wireless Keypad
with the system, you must program a House ID Code (01–31) in field *24 to
establish proper communication, and the keypad must be set to the same ID.
House ID 00 disables all wireless keypads. An RF House ID is not necessary
for other 5800 Series transmitters; the entry should be left at “00” (default) in
those cases. The 5827 reports low battery status as zone “00”.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises
(5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5827 and 5827BD), each
transmitter is supervised by a check-in signal that is sent to the receiver at
70–90 minute intervals. If at least one check-in is not received from each
supervised transmitter within a 12-hour period, the "missing" transmitter
number(s) and "FAULT" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises (5801,
5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type,
as described in the *56 Enhanced Zone Programming Mode section.
5800 Series transmitters have built-in tamper protection and will annunciate
as a fault condition if covers are removed.
Note: The 5804E and 5804WATCH transmitters are only supported by the
LYNXR-EN.
1
4
7
2
5
8
0
3
6
9
#
*
•
•
••
•
•••
•
•
•
••
•
•
•
•••
5806/5807/5808 5890 / 5890PI5816
5827 5827BD5804BD/5804BDV
01009-010-V0
123
456
789
0
*#
Transmitter Input Types
All of the transmitters described have one or more unique factory-assigned input (loop) ID codes. Each of the inputs
requires its own programming zone (e.g., a 5804's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate input type):
Type Description
"RF" (Supervised RF) Sends periodic check-in signals, as well as fault, restore, and low battery signals.
The transmitter must remain within the receiver's range.
"UR" (Unsupervised RF) Sends all the signals that the "RF" type does, but the control does not supervise
the check-in signals. The transmitter may therefore be carried off-premises.
"BR" (Unsupervised Button RF) These only send fault signals. They do not send low battery signals until they are
activated. The transmitter may be carried off-premises.

–12–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years,
depending on the environment, usage, and the specific wireless device
being used. Factors such as humidity, high or low temperatures, as
well as large swings in temperature may all reduce the actual battery
life in a given installation. The wireless system can identify a true low
battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point
within the system.
• Button-type transmitters should be periodically tested for battery life.
The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E,
and 5804WATCH button transmitters have replaceable batteries.
Note: The 5804E and 5804WATCH transmitters are only supported by the
LYNXR-EN.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all
transmitters have been properly programmed.
1. Enter Installer code (4112) + [#] + 3.
ON OFF
5802MN
5804 /5804E
5801
01009-011-V0
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer
mode. If so, wait a few minutes and try again.
2. The keypad will display all zone numbers of wireless units programmed into the system. Fault each transmitter in
turn, causing each one to send a signal. As the system receives a signal from each of the transmitters, the zone
number of that transmitter will disappear from the display. The transmitters may be checked upon installation, or
in an installed system.
3. When all transmitters have been checked, exit the Sniffer mode by keying Installer Code (4112) + OFF.
Notes:
• Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer mode to return to
normal operation.
• All BR-type units must physically be activated to clear the display, since they do not automatically send check-in
signals.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter
are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
• Any transmitter that is not “entered” will not turn off its zone number.
Go/No Go Test Mode
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to
reorient or relocate transmitters if necessary, before mounting the transmitters permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This will enable
you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the
system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire to be run to
sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not conduct this
test with your hand wrapped around the transmitter, as this will cause inaccurate results
Note: On button type transmitters whose buttons have been set to Arm AWAY, Arm STAY, or Disarm, pressing a
button will take the system out of the Go/No Go Test mode and cause that action.
a. The keypad will beep three times to indicate signal reception and display the appropriate zone number.
b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in
either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then permanently mount
each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.

–13–
Installing Wireless Zones
5800 Series Transmitter Loop Numbers(Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.
LOOP 1
5806/5807/5808/5808LST
ENROLL AS
"RF"
5804WATCH
LOOP 1
5809
ENROLL AS
"RF"
5818
ENROLL AS
"RF"
LOOP 1
5849
ENROLL AS
"RF"
LOOP 1
(SOUND)
5802 MN2
ENROLL AS
"UR" OR "RF"
LOOP
1
5850 (GBD)
ENROLL AS
"RF"
(Green)
(Red)
(Yellow)
LOOP 1
5814
ENROLL AS
"RF"
01009-012-V0
5827BD
PROGRAM
HOUSE ID
1
4
7
2
5
8
0
3
6
9
#
*
LOOP 1
(MOTION)
5890/5890PI
ENROLL AS
"RF"
LOOP
1
5802 MN
ENROLL AS
"UR" OR "RF"
5804BD/5804BDV
ENROLL AS
"BR"
PROGRAM HOUSE ID
LOOP 4
YOU MUST
ENROLL
THIS BUTTON
LOOP 3
LOOP 1
LOOP 2
•
•
••
•
•••
•
•
•
••
•
•
•
•••
5804/5804E
ENROLL AS "BR"
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
OFF
LOOP 3
ON
5816TEMP
ENROLL AS
"RF"
LOOP 1
(TEMP
SENSOR)
5817
ENROLL AS
"RF"
LOOP 2
(AUX.
CENTER)
LOOP 1
(PRIMARY)
LOOP 3
(AUX.
RIGHT)
5816
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
LOOP 2
(REED)
5816MN
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
ALTERNATE
POSITION
FOR LOOP 2
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5819S (WHS & BRS)
ENROLL AS
"RF"
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 2
(REED)
5819
ENROLL AS
"RF"
LOOP 2
(REED)
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5827
PROGRAM
HOUSE ID
123
456
789
0
*#
5800RL
SET
HOUSE ID
5801
ENROLL AS
"UR" OR "RF"
LOOP 3
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 3
1:15:00
1:13: 16
Notes: (1) You must enroll loop 4 on the 5801, 5804, 5804BD, 5804BDV, 5804E and 5804WATCH transmitters, regardless of whether or not the
loop is used.
(2) The 5804E and 5804WATCH transmitters are only supported by the LYNXR-EN.
8/The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS &
BRS), 5827BD, and 5850(GBD) wireless transmitters are not intended for any UL installations.
Setting DIP Switches on the 5800RL and 5827 Transmitter(s)
Set the 5800RL and 5827 Transmitters to the programmed House ID, using its DIP switches. (OFF position is indicated by ---)
Notes: (1) The 5827 transmitter can not be used in conjunction with the *58 RF Jam Detection feature.
(2) The 5800RL cannot be used in conjunction with the Auto Arm (scheduled arming) feature.
01000-014-V1
234561
SW-6 SETS
MODE
2-6 SETS HOUSE ID
SW-1 ACTIVATES
MODE SETTING SWITCH DOWN
FOR "OFF"
SHOWN SET FOR HOUSE ID# 12
SWITCH UP FOR "ON"
5800RL DIP SWITCH TABLE
DIP SWITCH POSITIONS DIP SWITCH POSITIONSHouse
ID 2 3 4 5 6 House
ID 2 3 4 5 6
0 --- --- --- --- --- 16 ON --- --- --- ---
1 --- --- --- --- ON 17 ON --- --- --- ON
2 --- --- --- ON --- 18 ON --- --- ON ---
3 --- --- --- ON ON 19 ON --- --- ON ON
4 --- --- ON --- --- 20 ON --- ON --- ---
5 --- --- ON --- ON 21 ON --- ON --- ON
6 --- --- ON ON --- 22 ON --- ON ON ---
7 --- --- ON ON ON 23 ON --- ON ON ON
8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- ON ---
11 --- ON --- ON ON 27 ON ON --- ON ON
12 --- ON ON --- --- 28 ON ON ON --- ---
13 --- ON ON --- ON 29 ON ON ON --- ON
14 --- ON ON ON --- 30 ON ON ON ON ---
15 --- ON ON ON ON 31 ON ON ON ON ON
Setting 5800RL DIP Switches
1
2
3
4 5
HOUSE ID
SWITCH UP FOR "ON"
SWITCH DOWN FOR "OFF"
SHOWN SET FOR HOUSE ID# 30
01000-013-VO
5827 WIRELESS KEYPAD DIP SWITCH TABLE
DIP SWITCH POSITIONS DIP SWITCH POSITIONSHouse 1 2 3 4 5 House 1 2 3 4 5
1 --- --- --- --- ON 17 ON --- --- --- ON
2 --- --- --- ON --- 18 ON --- --- ON ---
3 --- --- --- ON ON 19 ON --- --- ON ON
4 --- --- ON --- --- 20 ON --- ON --- ---
5 --- --- ON --- ON 21 ON --- ON --- ON
6 --- --- ON ON --- 22 ON --- ON ON ---
7 --- --- ON ON ON 23 ON --- ON ON ON
8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- ON ---
11 --- ON --- ON ON 27 ON ON --- ON ON
12 --- ON ON --- --- 28 ON ON ON --- ---
13 --- ON ON --- ON 29 ON ON ON --- ON
14 --- ON ON ON --- 30 ON ON ON ON ---
15 --- ON ON ON ON 31 ON ON ON ON ON
16 ON --- --- --- ---
Setting 5827 DIP Switches

–14–
Mechanics of Programming
General Programming Information
Programming options are stored in nonremovable, electrically erasable, nonvolatile EEROM memory. You can program the
system at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the
Control and then program the unit as desired. There are two programming modes:
•Data field programming (used for setting various system options)
•Interactive menu mode programming (used for programming zone information, programming Powerline Carrier Devices,
and for entering transmitter serial numbers)
You can also program this system remotely, using an IBM Personal Computer, a modem, and Compass Downloader for
Windows. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the
feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the volume, press
FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the default value (mid
level).
!Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model being
installed prior to the system programming.
Entering Program Mode - Use one of the following methods:
a) Press both the [✳] and [#] keys at the same time, within 50 seconds after power is applied to the Control or from exiting
Programming mode, OR
b) After power-up, enter the Installer Code (4 1 1 2) + 8 0 0. (This method disabled if exit Program mode using *98.)
Note: If a different Installer Code is subsequently programmed, use it instead of 4112 to enter the Programming mode.
Once you have entered the Program mode, data field *20 will be displayed (this is the first data field in the system) and both
keypad LEDs will flash.
Programming a Data Field
1. Press [*] + Field No. (for example, *21), then make the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then automatically display
the next data field in sequence. To go to a different field, press [*] plus the desired field number.
3. If the number of digits that you need to enter in a data field is less than the maximum number of digits available (eg.
phone number field), enter the desired data, then press [*]to program the next data field.
4. If you enter a nonexistent field, the keypad will display “EE”. Simply re-enter [*] plus a valid field number.
To view a data field without making changes, press [#] + Field No. Data will be displayed for that field.
To delete an entry in a field, press [*] + Field No. + [*].(Applies only to fields *40–*44, *88 and *94).
Interactive Mode Programming (*56, *80, *81, *83, *84, *85)
Press [*] + interactive mode No. (for example, *56). The keypad will display the first of a series of prompts.
A detailed procedure (with displays of prompts) is provided in later sections of this manual.
Interactive Mode Used to Program
*56 Enhanced Zone Programming Mode Zone characteristics, report codes, and serial numbers
*80 Device Programming Menu Mode Powerline Carrier Devices
*81 Zone List Menu Mode Zone Lists for powerline carrier activation
*83 Enhanced Sequential Mode 5800 Series transmitter serial numbers
*84 Assign Zone Voice Descriptors Voice descriptors for each zone
*85 Record Custom Voice Descriptors Up to 5 custom voice descriptors for zones
Loading Factory Defaults
To load the factory defaults, enter the Programming mode, press *97, then press number 1, 2, 3, or 4 to select from default
tables 1-4 at the back of this manual, or press “0” if you are not selecting a default table.
!If loading a default table, any data that has already been programmed into the system will be changed according to
the default table selected!
*96 resets all the subscriber account numbers and CSID in preparation for an initial download.
Exiting Program Mode
*99 allows re-entry into the Program mode using Installer Code + 8 0 0.
*98 inhibits re-entry into the Programming mode using the Installer Code.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset delay, press [#] + [0].

–15–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system responds to
faults in that zone. Zone types are defined below.
Type 00
Zone Not Used Zone type 00 is used to program a zone that is not used.
Type 02
Entry/Exit Burglary #2
01000-017-V0
Zone type 02 is usually assigned to sensors or contacts on which secondary entry and exit
doors that might be further from the keypad (typically used for a garage, loading dock, or
basement door).
Zone Characteristics:
• Entry delay #2 is programmable from 0-99 seconds (field *36).
• Exit delay is independently programmable from 0-99 seconds (field *34).
• Secondary entry delay, if armed in the AWAY or STAY mode.
• No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay begins regardless of the arming mode selected.
01000-018-V0
Type 03
Perimeter Burglary Zone type 03 is usually assigned to all sensors or contacts on exterior doors and windows.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
mode.
Type 04
Interior, Follower
5890 / 5890PI
01000-019-V1
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or
hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach the
keypad. It provides an instant alarm if the entry/exit zone is not violated first, and
protects an area in the event an intruder has hidden on the premises before the system is
armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
• Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or
interior-with-delay (type 10) zone is faulted first.
• Instant alarm in all other situations.
• Active when armed in AWAY or AWAY NO DELAY mode.
Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Type 05
Trouble by Day/
Alarm by Night
Zone type 05 is usually assigned to a zone, that contains foil-protected doors or windows
or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on
a sensor or contact in an area where immediate notification of an entry is desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
(night) mode.
• Provides a latched trouble sounding from the keypad and, if desired, a central station report
during the disarmed state (day).
Type 06
24-hour
Silent Alarm
Zone type 06 is usually assigned to a zone containing an Emergency button
(silent emergency).
Zone Characteristics:
• Sends a report to the central station but provides no keypad display or sounding.
Type 01
Entry/Exit Burglary #1
01000-017-V0
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit doors.
Zone Characteristics:
• Entry delay #1 is programmable from 0-99 seconds (field *35).
• Exit delay is independently programmable from 0-99 seconds (field *34).
• Exit and entry delays when armed in AWAY or STAY mode.
• No entry delay when armed in INSTANT or MAXIMUM mode.
• Exit delay regardless of the arming mode selected.

–16–
Zone Response Type Definitions
Type 07
24-hour
Audible Alarm
Zone type 07 is usually assigned to a zone containing an Emergency
button (audible emergency).
Zone Characteristics:
• Sends a report to the central station, and provides alarm sounds externally and
at the keypad.
Type 08
24-hour
Auxiliary Alarm
Zone type 08 is usually assigned to a zone containing a button for use in
personal emergencies or to a zone containing monitoring devices (i.e.:
water or temperature sensors, etc.).
Zone Characteristics:
• Sends a report to the central station and provides an alarm sound at the keypad.
(No bell output is provided and there is no keypad timeout.)
5806/5807/5808
01000-020-V0
Type 09
Supervised
Fire
Zone type 09 can be assigned to any wireless zone used as a
fire zone. This zone type is always active and cannot be
bypassed.
Zone Characteristics:
• Bell output will pulse when this zone type is alarmed.
Type 10
Interior w/Delay Zone type 10 is bypassed when the panel is armed in the STAY or STAY
NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programmed entry time) when armed in the AWAY
mode.
• Entry delay begins whenever sensors in this zone are violated, regardless of
whether an entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Type 20
Arm–Stay Zone type 20 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or
disarming.
Type 21
Arm–Away Zone type 21 is a special-purpose zone type used with 5800 Series
wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or
disarming.
Type 22
Disarm Zone type 22 is a special-purpose zone type used with 5800 series
wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Type 23
No Alarm Response Zone type 23 can be used on a zone when a Powerline Carrier Device
(e.g., X-10) action is desired, but with no accompanying alarm (e.g., front
door light).
Type 24
Silent Burglary Zone type 24 is usually assigned sensors or contacts on exterior doors and
windows where bells and/or sirens are NOT desired.
Zone Characteristics:
• Instant alarm, with NO audible indication when is armed in the AWAY, STAY,
STAY NO DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note: Keypad beeps if the zone is faulted when system is disarmed and Chime mode is
on.

–17–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the
data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entry of a number other than the one specified will give unpredictable results.
*20 Installer Code
Enter 4 digits, 0-9
The Installer Code is used to enter the 4-digit Master Security Code. See
"Master Code" in the System Operation section for procedure.
*21 Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
If enabled, security code is not required to arm the system. The user
simply presses and holds down the AWAY or STAY key to arm.
*22 Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
This option allows the choice of either always backlighting the keypad or
turning the backlighting off after 10 seconds of keypad inactivity.
*23 Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted) zones
All zones bypassed by this function will be displayed after the bypass is
initiated.
Note: UL installations: must be 0 (no forced bypass)
*24 RF House ID Code
00 = disable all wireless keypad usage
01-31 = House ID
The House ID identifies receivers and wireless keypads.
If a 5827/5827BD Wireless Keypad or 5804BD/5804BDV Transmitter is
to be used, a House ID Code MUST be entered, and the keypad should be
set to the same ID.
*25 Powerline Carrier Device (X-10) House ID
0 = A 4 = E 8 = I # + 12 = M
1 = B 5 = F 9 = J # + 13 = N
2 = C 6 = G # + 10 = K # + 14 = O
3 = D 7 = H # + 11 = L # + 15 = P
Powerline Carrier Devices require a House ID. This field identifies this
House ID to the Control. The Powerline Carrier Devices are
programmed in field * 80.
*26 Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
This option allows the installer to define the specific zones intended to
chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see *81 Zone List Menu Mode).
*27 Real Time Clock Display
0 = do not display the time
1 = display the time
Refer to the User’s Manual for setting the clock time and date.
*29 Daylight Savings Time Start/End Month
0, 0 = no daylight saving time used
1-12 = start month and end month
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
*30 Daylight Savings Time Start/End Week
0 = disable 4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend 6 = next to last
3 = third weekend 7 = 3rd from last
Enter the appropriate start and end weekend of the month.
*31 Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for a
given zone
LYNXR/LYNXR24 - Applies to Long Range Radio Output if “0” is
selected in field *91
LYNXR-EN - Applies to Long Range Radio Output if a Long
Range Radio is connected to the Trigger Single (Neg.) terminal
#8.
UL installations: must be 0 (no limit)
This field applies only to burglary zones (zone response types 1-5, 10),
and affects long range radio reporting but does not affect central station
reporting.
Note: This field applies only to the bell and does not affect keypad
sounds.
*32 Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
field *33
1 = no fire sounder timeout; continue sounding until
manually turned off
This Control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
*33 Alarm Bell Timeout
0 = No timeout 2 = 8 min 4 = 16 min
1 = 4 min 3 = 12 min
This field determines whether the external sounder will shut off after time
allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
*34 Exit Delay
00-99 = exit delay time in seconds The system will wait the time entered before sounding an alarm if the exit
door is left open after the system has been armed.
UL installations: must be set for a maximum of 60 seconds

–18–
Data Field Descriptions
*35 Entry Delay 01
00-99 = entry delay time in seconds. The system will wait the time entered before sounding alarm upon entering
if system is not disarmed. UL installations: must be set for a maximum of 45
seconds
*36 Entry Delay 02
00-99 = entry delay time in seconds. The system will wait the time entered before sounding alarm upon entering.
UL installations: must be set for a maximum of 45 seconds
*37 Audible Exit Warning/Quick Exit
Exit Warning Quick Exit
0 = no exit warning sound 0 = no quick exit
1 = provide exit warning sound
when armed AWAY 1 = allow quick
exit
Exit Warning: Sound consists of slow continuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of exit delay.
Quick Exit: If enabled, user can restart the exit delay time after arming in
STAY mode by entering the user code and pressing the STAY key, or by
pressing the STAY key if Quick Arm is enabled. This avoids having the
user disarm then re-arm the system after allowing someone to enter or exit
*38 Confirmation of Arming Ding
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or
RF keypad only
Confirmation of arming is provided by a 1/2 second external sounder “ding”
that sounds when closing report is sent, or at the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs immediately after
the system receives the RF transmission.
*39 Power Up In Previous State
0 = always power up in a disarmed state
1 = assume the system status prior to power-down
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted, and any bypassed zones will be unbypassed.
Note: If the previous state was armed AWAY or STAY, the system will not
respond to sensor changes for 1 minute, which allows time for sensors such
as PIRs to stabilize. UL installations: must be 1 (power up in previous state)
DIALER PROGRAMMING (*40–*50)
Fields *40, *41, *42: Enter up to the number of digits shown. Do not fill unused spaces. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13 for
a pause (2 seconds)
*40 PABX Access Code
Enter up to 6 digits if PABX is needed to access an
outside line.
If fewer than 6 digits need to be entered, exit by pressing [*]. To clear
entries from field, press *40*.
*41 Primary Phone No.
Enter up to 20 digits.
If fewer than 20 digits entered, exit by pressing [*]. To clear entries from
field, press *41*.
Note: Backup reporting (8 attempts are made to the secondary phone number if
no kissoff is received after 8 attempts to the primary number) is automatic
only if there is a secondary phone number (field *42).
*42 Secondary Phone No.
Enter up to 24 digits.
If fewer than 24 digits entered, exit by pressing [*]. To clear entries from
field, press *42*. See backup reporting note for field *41. If using the
paging feature, enter the pager phone number here.
Fields *43 and *44:
Enter [*]as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000–0999. Exit field by pressing [*] if only 3 digits are used. To clear entries from field, press *43* or *44*.
See blank Programming Form for examples of account number entries. If using the paging feature, do not enter a leading 0 in the
subscriber account number, and do not use digits A-F anywhere in the number. Some paging systems provide voice mail capability, which
is activated by a leading 0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; or # +15=F.
*43 Primary Subs Account No.
Enter four digits .
Enter the primary subscriber account number.
To clear entries from field, press *43*.
*44 Secondary Subs Account No.
Enter four digits.
Enter the secondary subscriber account number.
To clear entries from field, press *44*.
*47 Phone System Select
Note: For LYNXR/LYNXR24 only options 0, 1, 2, and
3 are applicable. For LYNXR-EN all options
apply.
Central Dialing Mode
Station Pulse Tone Pulse Tone
No
WATS 0 = No
Speaker
Phone
1 = No
Speaker
Phone
4 = With
Speaker
Phone
5 = With
Speaker
Phone
WATS 2 = No
Speaker
Phone
3 = No
Speaker
Phone
6 = With
Speaker
Phone
7 = With
Speaker
Phone
This option is used to enter the correct type of phone dialing (pulse or tone),
and to select the correct WATS line option for the Central Station. For
LYNXR-EN only this option is used to activate the speaker phone option.
Note: If using pulse dialing, you must enter the numbers slowly in order to
allow the pulse dialer time to operate.

–19–
Data Field Descriptions
*48 Report Format for Primary/Secondary
Primary Secondary
See choices below See choices below
0 = 3+1; 4+1 ADEMCO Low Speed Standard
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMCO Low Speed Standard
3 = 4+2 Radionics Standard
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID Reporting
8 = 3+1; 4+1 ADEMCO Low Speed Expanded
9 = 3+1; 4+1 Radionics Expanded
Enter * as the 4th digit of *43 through *44, if 3+1 dialer reporting is to be
used. (For an explanation of these formats, see the System Communication
section of this manual.)
Notes: (1) The maximum number of alarm and alarm restore reports during
one armed period is determined by field *92.
(2) Option 7 (ADEMCO Contact ID Reporting) must be selected for
AVM.
*49 Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary
fails, then all
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All reports All
To Primary To Paging Number
6 = All reports except Open/Close Alarms, Open/Close ‡,
Troubles
7 = All reports Alarms, Troubles
8 = All reports Alarms, Open/Close ‡,
Troubles
9 = All reports except Open/Close Open/Close ‡
‡Will report Users 0, 5-8, and, if using wireless button-type
devices, will report the zone number of the arm or disarm
button 26-33. All other zones and users are not reported.
Use options 0 - 5 when reporting to telephone receivers.
Use options 6 - 9 when reporting to a pager is desired.
Pager Report Format
Options 6-9 send reports to the primary phone number and send reports to a
pager, which has its phone number entered as the secondary phone number
in field *42.
The pager report is a 7-digit code, with optional 16-digit prefix, in the
following format:
AAAAAAAAAAAAAAAA-EEE–00NN where:
AAA = Optional 16 digits for PIN number, etc. See field *88 for full
description of these characters.
EEE = 3-digit Event Code as follows:
911 = Alarm (NN = zone number)
101 = Open, system disarmed (NN = user no.)
102 = Close, system armed (NN = user no.)
811 = Trouble (NN = zone no.)
00 = Always displayed before 2-digit user/zone no.
NN = 2-digit user number or zone number, depending on the type of
event (EEE) that occurred. NN=00 indicates AC loss, system low
battery, or low battery in 5827/5827BD.
*50 15-Second Dialer Delay (Burglary)
0 = no dialer delay
1 = provide 15-second delay of burg. alarm report
If enabled, provides communication delay to the central station and allows
the subscriber time to avoid a false alarm transmission. Delay does not
apply to zone type 6, 7, 8, and 24 alarms, which are always sent as soon as
they occur. UL installations: must be 0 (no delay)
*51 Periodic Test Report
0 = no test report 2 = weekly
1 = once every 24 hrs 3 = once every 30 days
Test report code entered in field *64 is sent.
*52 First test Report Offset
0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
This is the time to first report from programming or downloading.
*53 Sescoa/Radionics Select
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats.
*58 RFJam Detection
0 = no jam detection
1 = RF jam detection with event logging, but no
central station report
2 = RF jam detection with event logging and with
central station report (if trouble/restore report is
enabled in fields *60, *71)
For Event Logging, Option 2 must be selected.
If the control detects an RF jam condition, a “FAULT” message appears for
zone 90. The Contact ID code for RF Jam is 344.
Note: This feature cannot be used in conjunction with the 5827 wireless keypad.

–20–
Data Field Descriptions
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (* 59 –* 76, &* 89)
Program Report Codes using the interactive *56 Enhanced Zone Programming Mode, or codes can be entered in data fields *59-*76, *89.
The following is a set of guidelines when programming report codes. The actual report code digits that you enter depend upon the
particular installation, and should be in agreement with you and the central station office receiving the signals.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A (reports a “0” on some
receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the first box will disable a report.
Entering "0" in the second box results in automatic advance to the next field.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above. Entering "0" in
the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone
until you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again. This is an
"enabling" code only and is not the actual code sent to the central station office. Entries in the second boxes will be ignored. For system
status (non-alarm) codes, enter a “1” in the first box for all the system conditions you want to send to the central station. A "0" in the first
box disables the report.
SYSTEM STATUS REPORT CODES (*59–*68)
*59 Exit Error Report Code
See notes above
If the system is armed and an entry/exit or interior zone is still open
after the exit delay time has expired, an alarm will sound at the
keypad and external sounder. If the system is disarmed before the
end of the entry delay that immediately follows, the alarm sounding
will stop and no message will be sent to the central station. The
keypad will display “CA (CANCELED ALARM).”
If the system is not disarmed before the end of the entry delay
mentioned above, and an entry/exit or interior zone is still open, an
“exit alarm” message will be sent to the central station if an Exit
Error report code is selected in this field. The keypad will display
“EA (EXIT ALARM),” and the alarm sounding will continue until
the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay,
and an “Exit Alarm” message will be sent to the central station.
If Contact ID format has been programmed, the message will contain
the zone number and error code 374 (Trouble–Exit Error). If 4+2
format is used, the digit entered in this field will be sent followed by
the second digit of the programmed alarm code for that zone. If 3+1
or 4+1 format is used, only the digit entered in this field will be sent.
This message will go to the primary phone no. Under any of these
conditions, no restore message will be sent.
If “0” is entered in this field, no special message will be sent, only
the regular alarm and alarm restore code for the zone.
*60 Trouble Report Code (See notes above) This will be sent if a zone goes into trouble.
*61 Bypass Report Code (See notes above) This will be sent when a zone is manually bypassed.
*62 AC Loss Report Code (See notes above) Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no AC restore report.
*63 Low Battery Report Code (See notes above) This will be sent when a low battery condition exists in the system’s
standby battery.
*64 Test Report Code (See notes above) This is sent periodically to test that the communicator and phone
lines are operational (frequency of report is selected in field *51).
*65 Open Report Code (See notes above) This is sent upon disarming of the system. 2nd digit = user number, if
expanded or 4+2 reporting is selected.
*66 Arm AWAY/STAY Report Code (See notes
above) This option allows for independent programming of AWAY and
STAY reports. 2nd digit of report is user number if expanded or 4+2
reporting is selected.
NOTE: OPEN reports are not sent if the associated closing report is
not enabled.
*67 RF transmitter Low Batt. Report Code (See
notes above)
This is sent in the event that a wireless transmitter low battery
condition exists.
*68 Cancel Report Code (See notes above) This is sent upon disarming of the system after an alarm condition
was reported.
This manual suits for next models
2
Table of contents
Other Lynx Security System manuals
Popular Security System manuals by other brands

X10
X10 DC8700 user guide

SJE Rhombus
SJE Rhombus TANK ALERT SOLAR installation instructions

Danguard
Danguard HS-200 user manual

Panasonic
Panasonic KX-HNS101 installation guide

Digital Monitoring Products
Digital Monitoring Products XR40 Security Command Executive Series user guide

DSC
DSC New Classic PC585 instruction manual