M-system 20VS5-201 User manual

20VS5-201
P. 1 / 4EM-4422 Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
ISOLATION AMPLIFIER
(high-accuracy, input isolation) MODEL
20VS5-201
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Amplifier ....................................................................... (1)
■MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■POWER INPUT RATING & OPERATIONAL RANGE
•PowerSupply
Operational voltage range: 15V DC ±10%
Powerconsumption:Approx.15mADC(noload)
Install the filter for the power supply as indicated below.
■ENVIRONMENT
•Indooruse
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ven-
tilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotsubjecttheunittophysicalimpact.
•Environmentaltemperaturemustbewithin-10to+70°C
(14to158°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
■WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■INSTALLING THE MODULE
Whenitisinstalledontheprintedwiringboard,landdiam-
eterø1.5andthrough-holeø0.9arerecommended.
■AND ....
•Theunitisdesignedtofunctionassoonaspowerissup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to en-
dure it without breakdown, however, it may shorten ap-
propriate life duration.
CHECKING
1) Terminal wiring: Check that wiring is correctly connect-
ed according to the connection diagram.
2) Powerinputvoltage:Checkvoltageacrossthepins.
3) Input:Checkthattheinputsignaliswithin0–100%of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
10µF
+
–
COM
POWER
560µH
14
15
+15V
10µF
+
–

20VS5-201
P. 2 / 4EM-4422 Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
TERMINAL CONNECTIONS
■EXTERNAL DIMENSIONS mm (inch)
■TERMINAL ASSIGNMENTS
+
–
+
–
OUTPUT
2
1
6
14
15
5
3
4
17
16
+
–
POWER
Note. The reference voltage source is common to the COM (–), terminal 4.
*To be used in the printing wiring board on which the unit is mounted.
REFERENCE VOLTAGE SOURCE*
COM (–)
INPUT NON-INVERTING INPUT
INVERTING INPUT
FEEDBACK
PIN ASSIGNMENT
6
5
4
3
2
1
REFERENCE VOLTAGE SOURCE (–)
REFERENCE VOLTAGE SOURCE (+)
COM (–)
NON-INVERTING INPUT
17
16
15
14
OUTPUT (+)
OUTPUT (–)
POWER SUPPLY (–)
POWER SUPPLY (+)
INVERTING INPUT
FEEDBACK
161417
12.7 (.5) 20.32 (.8) 7.62
(.3)
0.5 (.02)
2.54 (.1) 0.25
(.01)
20.32 (.8)
MAX. 47.5 (1.87) 10.7 (.42)
MAX. 16 (0.63)7.75
(.31)
2.55 (.1)

20VS5-201
P. 3 / 4EM-4422 Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
APPLICATION EXAMPLES
The primary amplifier in this unit is high accurate. Installing external resistors to the inverting input (pin 2) and the feed-
back (pin 1), this unit can be used as a non-inverting or inverting amplifier.
Theseriesresistanceoftheamplier,R2+R2must be less than 200kΩ.
The output is proportional to the input.
Thegainis0.98.
E.g.±9.8VDCfor±10VDCinput.
The output is inverted to the input. The
gain is -1.
E.g.+10VDCfor-10VDCinputand-10V
DCfor+10VDCinput.
+
–
+
R2R1
–
+
–
Non-inverting amplifier circuit G = 1 + R1/ R2
OUTPUT VO
■Non-inverting amplifier circuit: Example of G = 1 + R1/ R2
INPUT VIN
+
–
–
+
REFERENCE
VOLTAGE SOURCE
1
2
4
3
5
6
+
–
POWER 15V DC
17
16
14
15
Foranon-invertingamplicationtheout-
put is following.
VO=(1+R2/R2) × VIN
WhenR2=10kΩ,R2= 10kΩ, then the out-
put is following. The gain is 2.
VO= 2 ×VIN
+
–
+
R2R1
–
+
–
Inverting amplifier circuit G = -R1/ R2
OUTPUT VO
■Inverting amplifier circuit: Example of G = -R1/ R2(output inverted to the input)
INPUT VIN +
–
–
+
REFERENCE
VOLTAGE SOURCE
1
2
4
3
5
6
+
–
POWER 15V DC
17
16
14
15
Foraninvertingamplicationtheoutput
is following.
VO =-(R2/R2) × VIN
WhenR2=20kΩ,R2= 10kΩ, then the out-
put is following. The gain is -2.
VO= -(20kΩ / 10kΩ) × VIN = -2 × VIN
+
–
+
–
+
–
1
2
Non-inverting circuit G = 0.98
OUTPUT ±9.8V DC
–
+
REFERENCE
VOLTAGE SOURCE
nNon-inverting amplifier circuit: Basic example of G = 0.98
INPUT ±10V DC
+
–
4
3
5
6
17
16
+
–
POWER 15V DC
14
15
+
‒
+
R2R1
‒
+
‒
Inverting circuit G = -1
OUTPUT ±10V DC
■Inverting amplifier circuit: Basic example of G = -1 (output inverted to the input) (R1≈R2)
INPUT ±10V DC +
‒
‒
+
REFERENCE
VOLTAGE SOURCE
1
2
4
3
5
6
17
16
+
‒
POWER 15V DC
14
15

20VS5-201
P. 4 / 4EM-4422 Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
For a non-inverting amplica-
tion with external adjustments,
when the combined resistance of
the span adjustment and 9kΩ is
10kΩ,thegainis(1+10kΩ/R2)
× VIN.Withthespanadjustment
(2kΩ), the output is configurable.
Thezeroisadjustablewitharef-
erence voltage source of ±15V DC
and the attenuation of 200Ω and
30kΩ.
For an inverting amplication
withexternaladjustments,when
the combined resistance of the
span adjustment and 9kΩ is
10kΩ, the gain is -(10kΩ / R2) ×
VIN. With the span adjustment
(2kΩ), the output is configurable.
Thezeroisadjustablewitharef-
erence voltage source of ±15V DC
and the attenuation of 200Ω and
30kΩ.
MAINTENANCE
Regularcalibrationprocedureisexplainedbelow:
■CALIBRATION
Warmuptheunitforatleast10minutes.Apply0%,25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.
+
–
+
–
Non-inverting amplifier circuit zero/span adjustments (input ±5V, output ±10V)
OUTPUT ±10V DC
■
Non-inverting amplifier's circuit with external adjustments: Example of G = 2
+
–
–
+REFERENCE
VOLTAGE
SOURCE
9kΩ
10kΩ
50kΩ
(ZERO)
2kΩ
(SPAN)
INPUT ±5V DC
10kΩ
30kΩ
200Ω
+
–
1
2
4
3
5
6
+
–
POWER 15V DC
17
16
14
15
+
–
Inverting amplifier circuit zero/span adjustments (input ±10V, output ±10V)
■ Inverting amplifier's circuit with external adjustments: Example of G = -1 (output inverted to the input)
+
–
–
+REFERENCE
VOLTAGE
SOURCE
9kΩ
10kΩ
100kΩ
(ZERO)
2kΩ
(SPAN)
INPUT ±10V DC
10kΩ
30kΩ
200Ω
+
–
+
–
OUTPUT ±10V DC
1
2
4
3
5
6
+
–
POWER 15V DC
17
16
14
15
Table of contents