  9. M-system R7M-DC4G-R User manual

M-system R7M-DC4G-R User manual

This manual suits for next models

1

Other M-system I/O System manuals

M-system R3Y-RS8 User manual

M-system

M-system R3Y-RS8 User manual

M-system R30NE1 User manual

M-system

M-system R30NE1 User manual

M-system R7F4HEIP-DAC16B User manual

M-system

M-system R7F4HEIP-DAC16B User manual

M-system R7ML-EA8 User manual

M-system

M-system R7ML-EA8 User manual

M-system M8BS1-16U0 User manual

M-system

M-system M8BS1-16U0 User manual

M-system R7K4DH-1-DAC32A User manual

M-system

M-system R7K4DH-1-DAC32A User manual

M-system R7 Series User manual

M-system

M-system R7 Series User manual

M-system R8-YS2 User manual

M-system

M-system R8-YS2 User manual

M-system R3-DC64A User manual

M-system

M-system R3-DC64A User manual

M-system R7D-YV2/UL User manual

M-system

M-system R7D-YV2/UL User manual

M-system R7F4DC-DA16A-J User manual

M-system

M-system R7F4DC-DA16A-J User manual

M-system R3-US4 User manual

M-system

M-system R3-US4 User manual

M-system R7 Series User manual

M-system

M-system R7 Series User manual

M-system R7F4HC-DAC32C-K User manual

M-system

M-system R7F4HC-DAC32C-K User manual

M-system R3-SV8 User manual

M-system

M-system R3-SV8 User manual

M-system R7ML-SV4 User manual

M-system

M-system R7ML-SV4 User manual

M-system R7L-TS4 User manual

M-system

M-system R7L-TS4 User manual

M-system R3-RS4 User manual

M-system

M-system R3-RS4 User manual

M-system R3-TS4 User manual

M-system

M-system R3-TS4 User manual

M-system R3-AS8 User manual

M-system

M-system R3-AS8 User manual

M-system R3-CZ4 User manual

M-system

M-system R3-CZ4 User manual

M-system R7D-SV4 User manual

M-system

M-system R7D-SV4 User manual

M-system R7L-EA8 User manual

M-system

M-system R7L-EA8 User manual

M-system R3-SV16N User manual

M-system

M-system R3-SV16N User manual

Popular I/O System manuals by other brands

SMC Networks EX600-AXA Installation & maintenance manual

SMC Networks

SMC Networks EX600-AXA Installation & maintenance manual

Siemens SIMATIC ET 200SP HA Equipment manual

Siemens

Siemens SIMATIC ET 200SP HA Equipment manual

Advantech PCM-27J3AU Startup manual

Advantech

Advantech PCM-27J3AU Startup manual

Hitachi HX-RIO3 Series user manual

Hitachi

Hitachi HX-RIO3 Series user manual

ICP DAS USA tM-AD2 quick start

ICP DAS USA

ICP DAS USA tM-AD2 quick start

IFM AL1200 operating instructions

IFM

IFM AL1200 operating instructions

Allen-Bradley D Series installation instructions

Allen-Bradley

Allen-Bradley D Series installation instructions

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley SLC 500 1746-FIO4I user manual

Allen-Bradley

Allen-Bradley SLC 500 1746-FIO4I user manual

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

System Sensor M201E installation instructions

System Sensor

System Sensor M201E installation instructions

NTP Technology Penta 721 digital I/O installation guide

NTP Technology

NTP Technology Penta 721 digital I/O installation guide

Bosch B208 user manual

Bosch

Bosch B208 user manual

Acces I/O products MPCIE-ISODIO-16 Hardware manual

Acces I/O products

Acces I/O products MPCIE-ISODIO-16 Hardware manual

ExpertDAQ EX-9017F Operation manual

ExpertDAQ

ExpertDAQ EX-9017F Operation manual

SeaLevel SeaI/O-580E user manual

SeaLevel

SeaLevel SeaI/O-580E user manual

Technosoft iPOS360x MX Technical reference

Technosoft

Technosoft iPOS360x MX Technical reference

National Instruments 776570-00 user manual

National Instruments

National Instruments 776570-00 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

EM-7803-BB P. 1 / 4
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Relay contact output module..............................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 35mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and output signal for safety.
• Before you remove the terminal block or mount it, make
sure to turn off the power supply and output signal for
safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to close the terminal cover for safety.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
RELAY C CONTACT OUTPUT MODULE, 4 points
(Modbus) MODEL
R7M-DC4G
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
R7M-DC4G
EM-7803-BB P. 2 / 4
COMPONENT IDENTIFICATION
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
X10 X1
NODEADD. B.RATE
CNFG.
12345678
0123
10 11 12 13
2341
15 16 17 18
7896
14
5
ERR RD
RUN SD
PWR
4567
123
(A) (F)
(H)(G)
(B) (C) (D) (E)
■LEFT SIDE VIEW
TERM
ON OFF
(I)
(A) Status Indicator LED
(B) Station Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operation Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) Discrete Output Status Indicator LED
(G) Modbus, Power Supply Terminal
(H) Output Terminals
(I) Terminating Resistor SW
■FRONT VIEW
■STATUS INDICATOR LED
ID COLOR FUNCTION
PWR Red Turns on when the internal 5V is sup-
plied normally.
RUN Red Turns on when the data is received
normally.
ERR Red Turns on when the received data is ab-
normal. Blinks when setting is abnormal.
SD Red Turns on when the module is transmit-
ting.
RD Red Turns on when the module is receiving.
■DISCRETE OUTPUT STATUS INDICATOR LED
LED red indicators show the signal status.
ON : a contact output (NO)
OFF : b contact output (NC)
■NODE ADDRESS
Node Address is selected between 1 and 99 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■BAUD RATE
Baud Rate is selected with the rotary switch.
(Factory setting 0).
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps
5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps
■OPERATING MODE
• Output at the Loss of Communication: SW1-4
SW1-4 OUTPUT AT THE LOSS OF COMMUNICATION
OFF B contact output
(Discard the last data received normally)
ON Hold the output (*)
(maintains the last data received normally)
(*) Factory setting
Note: Be sure to set unused SW1-1 through 1-3 and 1-5
through 1-8 to OFF.
■POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT
4
DA
567
123
DG +
24V 0V
DB SLD FG
(1) DB –
(2) SLD Shield
(3) FG FG
(4) DA –
(5) DG –
(6) +24V Power input (24V DC)
(7) 0V Power input (0V)
■OUTPUT TERMINAL ASSIGNMENT
10
+24V
11
Y0
12
Y1
1
0V
2
COM0
3
COM0
13
Y2
4
COM0
14
Y3
5
COM0
15
Y4
6
COM1
16
Y5
7
COM1
17
Y6
8
COM1
9
COM1
18
Y7
NO. ID FUNCTION NO. ID FUNCTION
1 0V 0V 10 +24V 24V DC
2 COM0
Output common 0
11 Y0 Output 0 (NO)
3 COM0
Output common 0
12 Y1 Output 0 (NC)
4 COM0
Output common 1
13 Y2 Output 1 (NO)
5 COM0
Output common 1
14 Y3 Output 1 (NC)
6 COM1
Output common 2
15 Y4 Output 2 (NO)
7 COM1
Output common 2
16 Y5 Output 2 (NC)
8 COM1
Output common 3
17 Y6 Output 3 (NO)
9 COM1
Output common 3
18 Y7 Output 3 (NC)
■TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate.
(Factory setting OFF)
■EXTENSION MODULE
Combinations with all extension modules are available
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
R7M-DC4G
EM-7803-BB P. 3 / 4
PC CONFIGURATOR
The following parameter items can be set with using PC Configurator Software (model: R7CON).
Refer to the users manual for the R7CON for detailed operation of the software program.
■INTERFACE SETTING
PARAMETER SETTING RANGE DEFAULT SETTING
Communication Timeout 0.0 – 3276.7 (sec.) 3.0 (sec.)
Data Mode RTU / ASCII RTU
Parity NONE / ODD / EVEN NONE
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
4567
123
10 11 12 13
2341
15 16 17 18
789
6
14
5
30 (1.18) [5 (.20)]
3 (.12)5.5 (.22)
DIN RAIL
35mm wide
54 (2.13)
17 (.66)
50 (1.97) 18.5 (.73)
115 (4.53)
7–M3 SCREW
TERMINALS
for Modbus, POWER
18–M3 SCREW
TERMINALS
for OUTPUT
6 (.24) 6 (.24)
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
R7M-DC4G
EM-7803-BB P. 4 / 4
■CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
4
1
2
5
3
DA
DB
DG
SLD
FG
6
7
0V
24V DC
10
5
1
13
17
4
18
2
8
9
3
12
15
11
16
6
7
Y1B (NC)
COM1
COM1
Y0A (NO)
Y0B (NC)
COM0
COM0
Y1A (NO)
Y3B (NC)
COM3
COM3
0V
+24V
Y2A (NO)
Y2B (NC)
COM2
COM2
Y3A (NO)
14
COMMUNICATION CABLE CONNECTIONS
■
MASTER CONNECTION
Tx+/Rx+
Tx–/Rx–
SG
Rx+
Rx–
Host PC
DA
DB
DG
SLD
FG
Remote Unit
DA
DB
DG
SLD
FG
Remote Unit
TERMINATOR TERMINATOR
Be sure to connect the terminating resistor included in the product package to the unit at both ends of transmission line.
The terminator must be connected across DA and DB.
The Host PC can be located other than at the extreme ends of transmission line.
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.5 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)