R7D-RS4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7802-C Rev.5 P. 2 / 10
COMPONENT IDENTIFICATION
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
MS X10 X1
NODE ADD. B.RATE
CNFG.
12345678
10 11 12 13
2341
15 16 17 18
7896
14
5
NS
23415
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) DeviceNet, Power Supply Terminals
(G) Input Terminals
(A)
(F) (G)
(B) (C) (D) (E)
■STATUS INDICATOR LED
ID S TAT E TO INDICATE
MS Green Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red Critical failure
Blinking Red Minor failure
OFF No power supplied
NS Green Link on-line and connections in the
established state
Blinking Green Link on-line but no connections in
the established state
Red Critical link failure
Blinking Red Minor link failure
OFF No power supplied
■NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking
The R7D communicates in the baud rate setting detected at
the startup with the switch set to the positions 0 (125 kbps),
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network
to determine the baud rate on the network.
■OPERATING MODE
(*) Factory setting
• Extension: SW1-1, 1-2
SW1-1 SW1-2 EXTENSION
OFF OFF No extension (*)
ON OFF Discrete input, 8 or 16 points
OFF ON Discrete output, 8 or 16 points
• Conversion Rate: SW1-3 • Burnout: SW1-4
SW1-3
CONVERSION RATE
SW1-4 BURNOUT
OFF 250 msec. (*) OFF Upscale (*)
ON 500 msec. ON Downscale
• RTD Type: SW1-5, 1-6, 1-7, 1-8
SW1-5 SW1-6 SW1-7 SW1-8 RTD TYPE
OFF OFF OFF OFF Pt 100 (JIS ’97, IEC) (*)
ON OFF OFF OFF Pt 100 (JIS ’89)
OFF ON OFF OFF JPt 100 (JIS ’89)
ON ON OFF OFF Pt 50Ω (JIS ’81)
OFF OFF ON OFF Ni 100
ON OFF ON OFF Cu 10 @ 25°C
OFF OFF OFF ON Cu 50
ON ON ON ON PC Configurator setting
■DeviceNet TERMINAL ASSIGNMENT
23415
NO. ID FUNCTION, NOTES
1 V+ Network power supply +
2 CAN_H Network data High
3 Drain Shield
4 CAN_L Network data Low
5 V– Network power supply –
■INPUT TERMINAL ASSIGNMENT
10
INA0
11
INb0
12
INA1
1
NC
2
INB0
3
NC
13
INb1
4
INB1
14
NC
5
NC
15
INA2
6
NC
16
INb2
7
INB2
17
INA3
8
NC
9
INB3
18
INb3
NO.
ID FUNCTION
NO.
ID FUNCTION
1 NC No connection 10 INA0 RTD 0-A
2 INB0 RTD 0-B 11 INb0 RTD 0-b
3 NC No connection 12 INA1 RTD 1-A
4 INB1 RTD 1-B 13 INb1 RTD 1-b
5 NC No connection 14 NC No connection
6 NC No connection 15 INA2 RTD 2-A
7 INB2 RTD 2-B 16 INb2 RTD 2-b
8 NC No connection 17 INA3 RTD 3-A
9 INB3 RTD 3-B 18 INb3 RTD 3-b
■EXTENSION MODULE
Combinations with all extension modules are selectable.