M-system DAL4 User manual

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6782 Rev.1 P. 1 / 4
INSTRUCTION MANUAL
REPEATER
(SIN-NET, M-Bus use) MODEL DAL4
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Repeater ..............................................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 11VA
24V DC rating: 24V ±10%, approx. 250mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to close the terminal cover for safety.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Specifications
Body
INSTALLATION
■DIN RAIL MOUNTING
Set the unit so that its DIN rail adaptor is at the bottom.
Hang the upper hook at the rear side of the unit on the DIN
rail and push in the lower. When removing the unit, push
down the DIN rail adaptor utilizing minus screwdriver and
pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■WALL MOUNTING unit: mm (inch)
•
M4 SCREWS
2–M5
60 (2.36)
60 (2.36)
•M5 SCREWS
2–M4
60 (2.36)
50 (1.97)

DAL4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6782 Rev.1 P. 2 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
• DAL4-1
75 (2.95)
75 (2.95)
910111213141516
12345678
3 (.12)1(.04)
112 (4.41) [3.3 (.13)]
DIN RAIL
35mm wide
8 (.31) 16–M3.5
SCREW
TERMINAL
COVER
2–5.8 (.23) dia. or
2–4.8 (.18) dia.
MTG HOLE
8 (.31) deep
•When mounting, no extra space is needed between units.
• DAL4-2
75 (2.95)
75 (2.95)
910111213141516
12345678
3 (.12)1(.04)
112 (4.41) [3.3 (.13)]
DIN RAIL
35mm wide
8 (.31) 16–M3.5
SCREW
TERMINAL
COVER
2–5.8 (.23) dia. or
2–4.8 (.18) dia.
MTG HOLE
8 (.31) deep
•When mounting, no extra space is needed between units.
• DAL4-5, 7
75 (2.95)
75 (2.95)
910111213141516
12345678
3 (.12)1(.04)
112 (4.41) [3.3 (.13)]
DIN RAIL
35mm wide
8 (.31) 16–M3.5
SCREW
TERMINAL
COVER
2–5.8 (.23) dia. or
2–4.8 (.18) dia.
MTG HOLE
8 (.31) deep
•When mounting, no extra space is needed between units.
RXD TXD

DAL4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6782 Rev.1 P. 3 / 4
■CONNECTION DIAGRAM
4
3
2
1
13
14
15
16
U(+)
V(–)
POWER
9
10
PORT-A
Shielded
Twisted-pair Cable
6
5
8
7
■DAL4-1 ■DAL4-2
LINK A
13
14
15
16
U(+)
V(–)
POWER
9
10
FIBER OPTICS
LINK B
FIBER OPTICS
*Jumper Pin
+
–
Jumper Pin*
+
–
PORT-B
Shielded
Twisted-pair Cable
*Jumper Pin
+
–
PORT-C
Shielded
Twisted-pair Cable
Jumper Pin*
+
–
PORT-C
Shielded
Twisted-pair Cable
Terminating
Resistors
Terminating
Resistor
Terminating
Resistor
■DAL4-5, 7
PORT-A TXD
PORT-A RXD
FIBER OPTICS
13
14
15
16
U(+)
V(–)
POWER
9
10
Jumper Pin*
+
–
PORT-C
Shielded
Twisted-pair Cable
Terminating
Resistor
****
**
**
**
**
**
FG***
12
FG***
12
FG***
12
When the unit is located at the end of transmission line via twisted-
pair cable (= no cross-wiring), short across these terminals.
Do not short them for the one not located at the end.
When the DAL4 is to be connected with the 22LA1 or DLA1 multi
transmission devices,do not connect the shield wire to the SG
(4, 8 or 16) but to the FG at the instrumentation panel.
Grounding the FG improves noise immunity of the power and
transmission lines, and is a recommended practice when the DAL4
is installed where a noise is present.
*
**
***
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
9 – 10 with a multimeter.
3) Twisted-pair cable: CPEV-0.9 dia. or larger. Check that
the (+) are connected to (+), (–) are connected to (–).
4) Twisted-pair cable ports: When the port is located at the
end of a transmission line, or unused, short across the
terminating resistors (2 – 3, 6 – 7 or 14 – 15).

DAL4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6782 Rev.1 P. 4 / 4
LIGHTNING SURGE PROTECTION
■MULTIPLEX TRANSMISSION
4
3
2
1
13
14
15
16
9
10
6
5
12
7
11
DAL4-1
8
A
B
C3
2
1
MDP-DM3
G
A
B
C3
2
1
G
–
+
DLA1, 22LA1
LINE
–
+
LINE
MDP-DM3
1
2
3
B
C
A
G
PANEL
+
–
+
–
+
–
*
*
*
*Terminating resistor
Notes
• Be sure to use lightning surge protectors (model: MDP-DM3) on twisted-pair cables.
• Be sure to connect the terminal No. 1 of the MDP-DM3 with SG terminal of the DAL4.
• For connecting model DLA1 or 22LA1 with the DAL4 in the same panel, install them between the MDP-DM3 and the DAL4.
Be sure to connect the terminal No. 1 of the MDP-DM3 with SG terminal of the DAL4.
• Lightning surge protectors for power supply line are recommended for complete protection.
■M-BUS
4
3
2
1
13
14
15
16
9
10
6
5
12
7
11
DAL4-1
8
A
B
C3
2
1
MDP-DM3
G
A
B
C3
2
1
G
–
+
DLA2, SMLM
LINE
–
SG SG
+
LINE
MDP-DM3
1
2
3
B
C
A
G
PANEL
+
–
+
–
+
–
*
*
*
*Terminating resistor
Shielded
Twisted-pair Cable
Shielded
Twisted-pair Cable
Shielded
Twisted-pair Cable
Notes
• Be sure to use lightning surge protectors (model: MDP-DM3) on twisted-pair cables.
• Be sure to connect the terminal No. 1 of the MDP-DM3 with SG terminal of the DAL4.
• For connecting model DLA2 or SMLM with the DAL4 in the same panel, install them between the MDP-DM3 and the
DAL4. Be sure to connect the terminal No. 1 of the MDP-DM3 with SG terminal of the DAL4.
• Lightning surge protectors for power supply line are recommended for complete protection.
Other M-system Repeater manuals
Popular Repeater manuals by other brands

turck
turck IOLR-EH30-H1151 quick start guide

Kenwood
Kenwood NEXEDGE NXR-710-E instruction manual

Kenwood
Kenwood NXR-700H Service manual

Silvercrest
Silvercrest SWV 300 C1 User manual and service information

Icom
Icom D-STAR ID-31A; D-STAR ID-31E quick guide

Silvercrest
Silvercrest SWV 1166 A1 Operation and safety notes