Macurco RD-24 User manual

IMPORTANT: Keep these user instructions for reference.
Macurco™ RD-24
Modbus Remote Driver
Installation & Operation Manual

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 2 |P a g e
Table of Contents
1 General Safety Information........................................................................................................................................................3
1.1 List of warnings .................................................................................................................................................................3
2 Use Instructions and Limitations................................................................................................................................................3
2.1 RD-24 General Description................................................................................................................................................3
2.2 Features.............................................................................................................................................................................3
2.3 Specifications ....................................................................................................................................................................3
3 Installation Instructions .............................................................................................................................................................4
3.1 Location & Mounting.........................................................................................................................................................4
3.2 Installation.........................................................................................................................................................................5
3.2.1 General Wiring Information .....................................................................................................................................5
3.2.2 Power Connection ....................................................................................................................................................5
3.2.3 RS-485 Communication Connection.........................................................................................................................6
3.2.4 Input/Output Connections .......................................................................................................................................7
3.2.5 Expansion Board Connections ..................................................................................................................................8
4 Operations .................................................................................................................................................................................9
4.1 Power up ...........................................................................................................................................................................9
4.2 Initial Operating Mode ......................................................................................................................................................9
4.2.1 RD-24 Settings ..........................................................................................................................................................9
4.2.2 Programming Mode..................................................................................................................................................9
4.2.3 Configuration Refresh.............................................................................................................................................10
4.3 Configuration...................................................................................................................................................................10
5 Appendix A –Table of Figures..................................................................................................................................................15
6 Appendix B –Modbus Registry ................................................................................................................................................16
6.1 Read Configuration..........................................................................................................................................................17
6.2 Fail-safe ...........................................................................................................................................................................17
6.3 Configure Analog Outputs Range....................................................................................................................................17
6.4 Multipurpose command..................................................................................................................................................17
6.5 Write Output Command Expansion Boards #1, #2, #3 and #4........................................................................................18
7 Macurco Gas Detection Product limited warranty ..................................................................................................................23
Technical Support Contact Information........................................................................................................................................23
General Contact Information........................................................................................................................................................23

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 3 |P a g e
1General Safety Information
1.1 List of warnings
WARNING
Each person using this equipment must read and understand the information in this user manual
before use. Use of this equipment by untrained or unqualified persons or use that is not in accordance
with this user manual, may adversely affect product performance.
RD-24 may not function effectively below 32°F (0°C) or above 125°F (52°C). Using the equipment
outside of this temperature range may adversely affect product.
Immediately exit any environment that causes an alarm condition on the sensor.
Do not disassemble unit or attempt to repair or modify any component of this instrument. This
instrument contains no user serviceable parts, and substitution of components may adversely affect
product performance and void product warranty.
2Use Instructions and Limitations
2.1 RD-24 General Description
The RD-24 is a remote input/output device that allows flexibility for applications needing more relays, analog outputs, or analog
inputs. Using Modbus communication, you can control multiple I/O based on the application. The RD-24 requires 24VDC to
operate and can be used to engage or disengage other equipment such as: fans, louvers, horns, strobes, gas valves, etc. The
remote device can be wired in daisy-chain on the gas detector loop to save wire and allows for great flexibility for mounting
location.
2.2 Features
•Modbus addressable remote device: relays, analog output, analog input
•Compatible with the Macurco DVP-1200 control panel
•Wall mount NEMA 4X enclosure
•4 expansion slots for expansion boards: up to 8 relays, 8 analog outputs, or 16 analog inputs, or combination of the
three
•24VDC Input
•Status Indicators (LED): Power, communication, Slot 1-4
2.3 Specifications
•Size: 10.26” x 11.06” x 3.16” (26.06 x 28.09 x 8.03 cm)
•Weight: 2.8 lbs. (1.3 kg)
•Voltage/Current: Power Input: 24VDC, 2A Overcurrent Projection
•RD-24 Current Draw without expansion boards: 20mA
•Operating Temperature: 32 to 125°F (0 - 52°C)
•Ambient Humidity: 0% - 95% RH non-condensing
•Mounting: Mounting holes in each corner
•Expansion Slots: 4
•Expansion Relay Board: 2 SDPT, 250VAC, 10A Max (resistive)
•Expansion Analog Input Board: 4 Analog Inputs
•Expansion Analog Output Board: 2 Analog Outputs

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 4 |P a g e
•Current: 1.2A Max (4 Analog Input Boards each with 4 sensors reading 100% of their value)
•Settings: Dip Switch –8 positions
•Status Indicators: (LED): Power, communication, Slots 1-4
•Baud Rate: 4800, 9600, 19200 (default), 98400, 57600, 115200 bps
•Enclosure: NEMA 4X
•Warranty: Two-year limited warranty
3Installation Instructions
3.1 Location & Mounting
Macurco RD-24 is shipped with mounting screws. RD-24 should be mounted with sufficient space all around for access to
conduit entry holes (not provided) top and bottom side of the unit.
Figure 3-1 –Internal view without expansion boards

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 5 |P a g e
Figure 3-2 –Internal view with expansion boards
3.2 Installation
3.2.1 General Wiring Information
All the connectors in RD-24 are spring tightening (*excluding the Analog Input board) and will accept wire from 14 to 24 AWG.
To connect the wires to terminals, press down the white button of the connector (use flat-headed screwdriver), insert bare wire
into respective wire cavity of the connector and release the white button. Ensure that the wire cannot be easily pulled from the
connector. Refer to Figure 3-2 - below for location of different connectors in RD-24.
*The Analog Input board has 4 screw-terminal connectors.
3.2.2 Power Connection
The power connections to the RD-24 should be size AWG18 (minimum) for short runs. For longer runs, follow recommended
power wire gauge guidelines. Match the polarity for power connection.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 6 |P a g e
3.2.3 RS-485 Communication Connection
For RS-485 or communication connection it is recommended to always use a twisted wire to reduce noise and allow for reliable
data communication over greater distances. For best performance use shielded 3-conductor wire with one twisted pair
providing a pair for signal (A & B), common (COM) and shield ground (SHD) connection.
NOTE: Running the RS-485 cable adjacent to or in the same conduit with high voltage wires is not recommended as there may
be interference from the high voltages.
The RD-24 provides integral termination for end of line resistors (EOL). The termination uses a 4-pin connector (labeled J8) to
select termination. Place the EOL jumper on one of the following positions:
•NU = No termination (default)
•120 = 120 Ohm
•100 = 100 Ohm
Figure 3-3 –EOL Jumper Placement

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 7 |P a g e
3.2.4 Input/Output Connections
Figure 3-4 –RD-24 Board Diagram
Macurco RD-24
Dip Switch
EOL Resistor
RS-485 COMMS
IN/OUT
POWER
IN/OUT
Expansion Board #2
SHD
COM
B
A
SHD
COM
B
A
GND
GND
24V
24V
Expansion Board #1
Expansion Board #3
Expansion Board #4

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 8 |P a g e
3.2.5 Expansion Board Connections
3.2.5.1 Expansion Relay Board
2 SDPT, 250VAC, 10A Max (resistive), Current: Single Relay activated 35mA, Both relays activated 55mA
Figure 3-5 Relay Expansion Board
3.2.5.2 Expansion Analog Output Board
Expansion Analog Input Board: 2 Analog Outputs, Both outputs at 4mA Current: 32mA, Both at 20mA
Current: 70mA
Figure 3-6 Analog Output Expansion Board
3.2.5.3 Expansion Analog Input Board
Expansion Analog Output Board: 4 Analog Inputs Current: no sensor 21mA, one sensor at 0% 48mA, one
sensor at 100% 75mA
Figure 3-7 Analog Input Expansion Board

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 9 |P a g e
4Operations
4.1 Power up
Power LED will light up green to indicate the unit is operational. TX LED will flash blue to indicate the unit is communicating.
Slot 1, Slot 2, Slot 3 and Slot 4 will light up green when corresponding relay is activated/populated. Refer to Figure 3-3 above for
location of Slot 1-4.
4.2 Initial Operating Mode
4.2.1 RD-24 Settings
The DIP switches are used to set the Modbus address and are also used to change the communication settings. Valid Modbus
addresses for RD-24 are from 193 to 200 where switch 1 is the least significant bit (LSB) and switch 8 is the most significant bit
(MSB). Address 254 is used to place the RD-24 in programming mode. Address 255 is used to refresh the configuration of the
RD-24.
4.2.2 Programming Mode
When the RD-24 is powered with address set to 254, it enters programming mode. The STATUS LED will be flashing RED and
GREEN alternatively every 200 milliseconds to indicate that RD-24 is ready and waiting for the user to enter new communication
settings using 8 dip switches. Using the 8 dip switches, the user can change the communication settings like baud rate and
parity.
When looking at the switches with “Address” marking on top, the switches are defined from left to right.
•Switch 8, switch 7 and switch 6 are used to modify baud rate
•Switch 5 and switch 4 are used to modify parity
•Switch 1 is used to request to save the new settings
•Switches 3 and 2 are unused and should be left in the ON position.
Switch 8
Switch 7
Switch 6
Description
OFF
OFF
OFF
Default Value (19200 Bd)
OFF
OFF
ON
4800 Bd
OFF
ON
OFF
9600Bd
OFF
ON
ON
19200 Bd (Default value)
ON
OFF
OFF
38400 Bd
ON
OFF
ON
57600 Bd
ON
ON
OFF
115200 Bd
ON
ON
ON
Do not change
Table 4-1 –Baud Rate Configuration

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 10 |P a g e
Switch 5
Switch 4
Description
OFF
OFF
Default Parity EVEN (Default Value)
OFF
ON
Parity is ODD
ON
OFF
Parity is NONE
ON
ON
Do not change
Table 4-2 –Parity Configuration
Set the switches to the desired value and then set switch 1 to ON and then OFF, and the new settings will be saved
in EEPROM.
The result of saving operation is displayed on STATUS LED. Alternating GREEN/OFF every 200 milliseconds indicates
saving new settings passed and alternating RED/OFF every 200 milliseconds indicates that saving new settings failed.
Once the new settings have passed, disconnect power from the unit, set the address for the device using the
address switches and apply power back to unit.
4.2.3 Configuration Refresh
Upon initial installation, or when the user would like to change the RD-24 configuration (move, swap, or change
expansion board type or locations), the following process must be followed. Before making any changes, power off
the RD-24. Next, make the preferred changes to the RD-24 configuration. After, set the dip switch address to 255 and
power on the RD-24 for at least 3 seconds. The LED below the dip switch should blink green rapidly. After at least 3
seconds, power off the RD-24. Using the dip switch, change the address back to its original setting, or a number
between 193 and 200. Power on the RD-24. Last, navigate in the DVP-1200 menu CONFIGURE SYSTEM →MANUAL
CONFIGURE →CONFIG. RLYS,SIGNALS,SENSORS,REM. DEV. →REMOTE DEVICES. Select the Remote Device and delete
it from the DVP-1200. If the RD-24 is still powered on, the DVP-1200 will automatically find it back and update the
configuration. If the DVP-1200 does not find the device after 60 seconds, power cycle the panel and check again.
4.3 Configuration
4.3.1.1 Configure RELAY(S)
Menu path: Main Menu-->CONFIGURE SYSTEM -->MANUAL CONFIGURE -->CONFIGURE ZONES -->ADD/EDIT ZONES--
>RELAY(S): -->
NOTE: Programming Configure Relays - The panel has 8 onboard relays so remote relays start at 9. Reference the
Remote Device: I/O Chart at the end of this manual.
To add relays to a zone or delete relays assigned from a zone, select “RELAY(S):” from the zone configuration menu
and press ENTER. Then, select ADD RELAY or DELETE RELAY as shown below. The bottom box of the display will show
any relays assigned to the zone and will get updated as you make changes.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 11 |P a g e
Figure 4-1 –Zone Relay Menu
To assign a relay to the zone, select ADD RELAY and press ENTER. Input the relay number and press ENTER. The relay
will be added to the zone and the display will return to the RELAYS menu with the bottom box of the display
updated to reflect the changes made.
To delete a relay, select DELETE RELAY from the RELAYS menu and press ENTER. Input the relay number to delete
and press ENTER (to delete all relays assigned to the zone, input “0” and press ENTER). The relay(s) will be deleted
from the zone and the display will return to the RELAY menu with the bottom box of the display updated to reflect
the change made.
Figure 4-2 –Zone Delete Relay Menu
Relay assigned as Alarm Relay cannot be added to a zone. If an attempt to add an alarm relay to a zone is made,
then it will display an error message “CANNOT ADD RELAY. DEDICATED FOR ALARM” as shown in Figure 4-21.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 12 |P a g e
Figure 4-3 Zone Add Relay Error
Figure 4-21 –Zone Add Relay Error
4.3.1.2 Configure 4-20mA OUTPUT or Analog Output
Menu path: Main Menu-->CONFIGURE SYSTEM -->MANUAL CONFIGURE -->CONFIGURE ZONES -->ADD/EDIT ZONES--
>4-20MA OUTPUT: -->
NOTE: Assigning Analog Output - The panel has 3 onboard analog outputs so remote analog inputs start at 4.
Reference the Remote Device: I/O Chart at the end of this manual.
To assign 4-20mA output to a zone, select “4-20MA OUTPUT:” from the zone configuration menu and press ENTER.
Then select “OUTPUT NUMBER:” and press ENTER.
Figure 4-4 –Zone 4-20mA Output Menu
Input the 4-20mA output number to assign it to the zone. The display will return to the 4-20 O/P menu screen and
show the currently assigned 4-20 mA output in the OUTPUT NUMBER field.
NOTE: A zone can be assigned only one 4-20mA output, and a 4-20mA output can only be assigned to one zone. 4-
20mA output once assigned to a zone can be re-assigned to a different zone or can be deleted from the zone.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 13 |P a g e
Figure 4-5 –Zone 4-20mA Output Number Menu
NOTE: Oxygen sensor readings are excluded for 4-20mA output i.e., oxygen sensor readings are not considered while
computing output value for 4-20mA output.
Next, the output mode can be set to PEAK or SCALE.
PEAK –In this mode, the gas reading active in the zone (except for oxygen) corresponding to highest mA output is
used to control the analog output assigned to the specific zone. In this case, any active gas reading, that is part of
the zone will be taken into consideration, and the sensor reading corresponding to highest mA output will be used
to control the analog output. E.g. If a CO and NO2 sensor is assigned to a zone and CO Sensor reading is 50ppm
(which corresponds to 8mA) and NO2 sensor reading is 10.0ppm (which corresponds to 12mA) then the 4-20mA or
“Analog”output assigned to the zone will output 12mA.
SCALE –In this mode, the 4-20mA value for all detectors added to a zone are computed (for all sensor types except
oxygen), and the output is the average of the 4-20mA value for all detectors assigned to the zone. E.g. If a CO and
NO2 sensor is assigned to a zone and CO Sensor reading is 50ppm (which corresponds to 8mA) and NO2 sensor
reading is 10.0ppm (which corresponds to 12mA) then the 4-20mA or “Analog”output assigned to the zone will
output 10mA.
To select the output mode for 4-20mA output, select OUTPUT MODE from the 4-20 O/P menu and press ENTER.
Then, select PEAK or SCALE from the 4-20 O/P MODE menu and press ENTER. The display will return to the 4-20 O/P
menu and the output mode selection will be updated as shown in Figure 4-29.
When the status of the zone is TROUBLE then 4-20mA output assigned to corresponding zone will switch the output
to 20mA.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 14 |P a g e
Figure 4-6 –Zone 4-20mA Output Mode Menu
4.3.1.3 Configure 4-20mA Input or Analog Input
Analog Inputs read gas sensors connected to RD-24 and will work the same as digital sensors readings, which
are the sensors with MRS-485 connected to DVP-1200 through the RS-485 network using the Modbus
protocol.
Sensors connected to RD-24 should be displayed to the user as “RD-24 #address.#analog_input”.
#analog_input has a range from 1 to 16, as each RD-24 can have up to 4 expansion boards connected, and
each analog input expansion board has 4 analog inputs.
DVP-1200 has the capability to connect to up to 192 sensors. By default, DVP-1200 is configured to connect
to 192 digital sensors.
Each RD-24 that is discovered by DVP-1200 and has analog inputs will cause the controller to internally map
the RD-24 analog inputs to one of the 192 sensors and automatically adjust the limit of digital sensors that
can be connected to the controller.
The sensor mapping will be done from top to bottom. It grows from sensor #192 all the way to 128.
By default, DVP-1200 allocates space to connect to 192 digital sensors. If an RD-24 with analog inputs is
connected to the controller, DVP-1200 will automatically allocate sensor addresses from the list of 192 in the
following order:
-The first RD-24 connected to DVP-1200 will occupy sensor addresses 177 thru 192 in order and as needed.
For example: Slot 1, input 1 will occupy address 177 and Slot 4, input 4 will occupy address 192.
-The second RD-24 connected to DVP-1200 will occupy sensor addresses 161 thru 176 in order and as
needed.
-The third RD-24 connected to DVP-1200 will occupy sensor addresses 145 thru 160 in order and as needed
-The fourth RD-24 connected to DVP-1200 will occupy sensor addresses 129 thru 144 in order and as needed
NOTE: The addresses have been allocated to the exact locations as described –they do not change based on the
number of analog input expansion boards installed into any number of RD-24 units. For a full list of
addresses and slot designations, see “Remote Device I/O Chart” below.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 15 |P a g e
5Appendix A –Table of Figures
Figure 3-1 –Internal view without expansion boards......................................................................................................4
Figure 3-2 –Internal view with expansion boards ...........................................................................................................5
Figure 3-3 –EOL Jumper Placement.................................................................................................................................6
Figure 3-4 –RD-24 Board Diagram................................................................................................................................... 7
Figure 3-5 Relay Expansion Board ....................................................................................................................................8
Figure 3-6 Analog Output Expansion Board .....................................................................................................................8
Figure 3-7 Analog Input Expansion Board ........................................................................................................................8
Table 4-1 –Baud Rate Configuration................................................................................................................................9
Table 4-2 –Parity Configuration.....................................................................................................................................10
Figure 4-1 –Zone Relay Menu........................................................................................................................................11
Figure 4-2 –Zone Delete Relay Menu ............................................................................................................................11
Figure 4-4 –Zone 4-20mA Output Menu .......................................................................................................................12
Figure 4-5 –Zone 4-20mA Output Number Menu.........................................................................................................13
Figure 4-6 –Zone 4-20mA Output Mode Menu.............................................................................................................14

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 16 |P a g e
6Appendix B –Modbus Registry
Function
Code
Register
Address
Register
Parameter
Description / Comments
Command/Response
(HEX)
0x03
1
1
Map version
Returns map version in
C: 01 03 00 00 00 01 84
ASCII
0A
“1”
R: 01 03 02 00 31 79 90
0x03
2
4
Vendor name
Returns vendor name in
C: 01 03 00 01 00 04 15
ASCII
C9
“MACURCO”
R: 01 03 08 4D 41 43 55
52 43 4F 00 D6 D9
0x03
6
8
Product code
Returns product code in
C: 01 03 00 05 00 08 54
ASCII
0D
“70X---"
R: 01 03 10 37 30 58 2D
2D 2D 00 00 00 00 00 00
00 00 00 00 4B DE
0x03
1
4
8
Revision
Returns revision number
C: 01 03 00 0D 00 08 D5
number
in ASCII
CF
“V1.00”
R: 01 03 10 56 31 2E 30
30 00 00 00 00 00 00 00
00 00 00 00 85 4D
0x03
2
2
8
Vendor url
Returns vendor url in
C: 01 03 00 15 00 08 55
ASCII
C8
“www.macurco.com”
R: 01 03 10 77 77 77 2E
6D 61 63 75 72 63 6F 2E
63 6F 6D 00 A2 D6
0x03
3
0
4
Product name
Returns product name
C: 01 03 00 1D 00 04 D4
in ASCII “RD-24”
0F
R: 01 03 08 52 52 2D 32
34 00 00 00 53 7E
0x06
3
4
1
Fail safe
Writes failsafe
configuration
Payload: (high byte first)
bit11-bit0 (timeout value)
bit12 = 1 state ON, state
OFF
bit13 = 1 failsafe active, 0
failsafe inactive
C: 01 06 00 21 3A AF 8B1C
R: 01 06 00 21 3A AF 8B 1C
timeout = 0xAAF = 2735 state =
ON failsafe=active
0x06
3
5
1
Command
Command control relays
C: 01 06 00 22 00 00 29
Relays
Payload: (high byte first)
C0
00 = turn off relays
R: 01 06 00 22 00 00 29
K1/K2
C0
01 = turn on relay K1,
turn off relay K2
C:01 06 00 22 00 01 E8
02 = turn off relay K1,
00
turn on relay K2
R:01 06 00 22 00 01 E8
11 = turn on relay K1/K2
00

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 17 |P a g e
6.1 Read Configuration
Device configuration is indicated by 2 bytes.
bit
15
bit
14
bit
13
bit
12
bit
11
bit
10
bit9
bit8
bit
7
bit6
bit5
bit4
bit
3
bit2
bit1
bit0
Module # 4
Module #3
Module #2
Module #1
0000 = relays
0000 = relays
0000 = relays
0000 = relays
0001 = analog outputs
0001 = analog outputs
0001 = analog outputs
0001 = analog outputs
0010 = analog inputs
0010 = analog inputs
0010 = analog inputs
0010 = analog inputs
0011 to 1110 - future
0011 to 1110 - future
0011 to 1110 - future
0011 to 1110 - future
1111 = No exp. board
1111 = No exp. board
1111 = No exp. board
1111 = No exp. board
6.2 Fail-safe
Device fail safe configuration uses 4 bytes.
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Fail safe timer value 30 to 3600 (seconds)
state
0=OFF
1=ON
Active
0=NO
1=YES
x
x
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Analog Output value when in fail safe condition: (mA x 100)
0 = 0mA
2000 = 20.00mA
x
x
x
x
6.3 Configure Analog Outputs Range
Expansion Board #4
Expansion Board #3
Expansion Board #2
Expansion Board #1
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
DAC2
DAC1
DAC2
DAC1
DAC2
DAC1
DAC2
DAC1
x
rng
x
rng
x
rng
x
rng
x
rng
x
rng
x
rng
x
rng
rng: ‘0’ – 4 to 20 mA (2 to 10V), ‘1’ 0 to 20mA (0 to 10V)
6.4 Multipurpose command
Multipurpose command uses 2 bytes, and can be used on the following situations:
•Control all relays of a remote driver (RD-24) device.
•Control all analog outputs of remote drivers with same value.
•Control remote drivers with analog outputs and relays with same output values for relays and same output
values for analog outputs.
•Command to prevent a failsafe timeout when there is no change in the state of the outputs.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 18 |P a g e
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
module#
device#
relay
Analog value (mA x 100)
or
x
x
x
rly8
rly7
rly6
rly5
rly4
rly3
rly2
rly1
bit15
bit14
bit13
Description
0
0
0
Module #1
0
0
1
Module #2
0
1
0
Module #3
0
1
1
Module #4
1
0
0
Reserved –future use
1
0
1
Reserved –future use
1
1
0
Do not apply command. Dummy message
1
1
1
Apply to all 4 modules in the remote device, bit11 sets the state of the relays and
bits10-0 analog value to be used by DACs (Analog Outputs)
bit12
Each remote driver can have up to 4 modules connected. Each module has two relays
or two Analog outputs. Bit12 defines which output to be controlled 0 –output1, 1-
output 2
bit11
Defines the state of relays, 0 –OFF, and 1 - ON
bit10
Value to be written to the analog output (DAC). 0 –2000. 0 = 0mA, 2000 = 20mA
Value to be written to relays. bits7-0.
NOTE: Only “dummy message” command has been implemented on this command.
6.5 Write Output Command Expansion Boards #1, #2, #3 and #4
Command to write to expansion board # has 4 bytes.
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
x
x
x
x
rly#1
Analog value#1 (0 –2000)
bit15
bit14
bit13
bit12
bit11
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
x
x
x
x
rly#2
Analog value#2 (0 –2000)
Note: If failsafe is active, then the remote relay must receive a message in a period equal to or less than the failsafe
timeout, otherwise relays will be placed in the failsafe position.

MacurcoTM Macurco RD-24 Manual
REV –1.0.0 [34-8708-4770-1] 19 |P a g e
Appendix C –Setup Record
Record network parameters and keep them in a safe place to assist with installation and future troubleshooting will
be simplified.
Date of Install: ____________________________ Serial Number: _______________________________
Location of Install: _________________________ Installed by: _________________________________
Remote Device: I/O Chart
Relay connection
Connected device
Zone Configured
Delay
Runtime
Relay 9
Relay 10
Relay 11
Relay 12
Relay 13
Relay 14
Relay 15
Relay 16
Relay 17
Relay 18
Relay 19
Relay 20
Relay 21
Relay 22
Relay 23
Relay 24
Relay 25
Relay 26
Relay 27
Relay 28
Relay 29
Relay 30
Relay 31
Relay 32
Relay 33
Relay 34
Relay 35
Relay 36

MacurcoTM Macurco RD-24 Manual
REV –2.0.0 [34-8708-4770-9] 20 |P a g e
Relay 37
Relay 38
Relay 39
Relay 40
4-20mA output 4
4-20mA output 5
4-20mA output 6
4-20mA output 7
4-20mA output 8
4-20mA output 9
4-20mA output 10
4-20mA output 11
4-20mA output 12
4-20mA output 13
4-20mA output 14
4-20mA output 15
4-20mA output 16
4-20mA output 17
4-20mA output 18
4-20mA output 19
4-20mA output 20
4-20mA output 21
4-20mA output 22
4-20mA output 23
4-20mA output 24
4-20mA output 25
4-20mA output 26
4-20mA output 27
4-20mA output 28
4-20mA output 29
4-20mA output 30
4-20mA output 31
4-20mA output 32
4-20mA output 33
4-20mA output 34
4-20mA output 35
Remote Device
Sensor Type
Sensor Location
Modbus Address
Table of contents
Popular DC Drive manuals by other brands

American Control Electronics
American Control Electronics PAT440-10 quick start guide

Granite Devices
Granite Devices EHTHERFOX quick start guide

SOMFY
SOMFY S&SO-RS100 io instructions

Becker
Becker enocean P5-16 Assembly and operating instructions

Superior Electric
Superior Electric SLO-SYN SS2000MD4-M installation instructions

Festo
Festo CMMT-ST-C8-1C-...-S0 Series operating instructions