
508094-03Issue 2208Page 2 of 2
General Instructions
This chassis is the self-contained cooling section of a
MagicPak All-In-One™ HWC unit. It is designed to be
assembled into an HWC cabinet, and is not intended for
any other use or application.
This chassis is a replacement chassis for HWC8* and
HWC9* series units. 13P* chassis may be used as
replacement for 12P* series units. 12P* chassis may not
be used as replacement in 13P* models.
NOTE: The tonnage of this replacement chassis must
match the tonnage of the chassis being replaced.
If any damage to the contents is found at the time of delivery,
proper notation should be made on the carrier’s freight bill.
Damage claims should be led with the carrier at once.
Claims of shortage should be led with the manufacturer
within 5 days.
Removing the Old Chassis
1. Make sure that the electrical supply is disconnected
and the gas supply is turned o.
2. Remove the lter access panel and center rear panel.
3. Disconnect the wire harness plug and remove the line
voltage wires from the contactor.
4. Disconnect the condensate drain tube from drain pan.
5. Remove the blower close-o panel and remaining
screws retaining the chassis in the cabinet.
6. Slide out the existing chassis.
7. Slide in new HWC chassis and attach chassis in
reverse order of the removal.
8. Re-Install the center rear panel on the unit, being
careful not to pinch any wiring.
9. Re-install the lter access panel on the center rear
panel.
WARNING
Consult current HWC specications to ensure wire and
breaker are sized appropriately.
10. Establish the gas and electrical supply to the unit and
check the following.
a. Set thermostat for a call for cooling.
b. The compressor, condenser fan, and blower will
start approximately 8 seconds after the thermostat
calls for cooling.
c. When the thermostat is satised in the cooling
mode, the compressor and condenser fan motor
will shut o immediately. The circulating air blower
will continue to operate for approximately 90
seconds.
d. Set the themostat to call for heat.
e. Verify the main burners are lit. The circulating air
blower will start approximately 60 seconds after
the thermostat calls for heat.
f. Allow the unit to reach steady state conditions
and verify that the unit is operating within the rise
range shown on the unit rating plate. If the unit
is not operating within the rise range, adjust the
blower speed.
g. Turn thermostat down. The circulating air blower
will continue to operate for approximately 120
seconds after the thermostat is satised.
11. Install the new wiring diagram (supplied) on the unit
over the existing wiring diagram. If wire modications
were required, mark the changes on the wiring diagram
for future reference.