Maico ER shell User manual

Installation instructions for ER shell
ER EC flush-mounted exhaust air systems (according to
DIN 18017-3)
ERGH flush-moun-
ted box for EREC
systems
www.maico-ventilatoren.com

Table of contents
2
Table of contents
Preface................................................... 3
1 Scope of delivery .................................. 3
Overview of ER EC system .................. 4
2 Intended use.......................................... 5
3 Safety instructions ............................... 5
3.1 General safety instructions ........ 5
3.2 Safety instructions regarding in-
stallation, operation, cleaning
and maintenance .......................
6
4 System and product information ........ 8
4.1 Certificates of approval.............. 8
4.2 Installation conditions ................ 8
4.3 Permitted exhaust air systems .. 8
4.4 Possible combinations............... 8
4.5 Covers: Functions...................... 10
5 Technical data....................................... 10
5.1 Environmental conditions and
operating limits ..........................
10
5.2 Regulations for operation with
fireplaces ...................................
11
5.3 Technical data table .................. 11
5.4 Storage ...................................... 12
6 Mounting preparations......................... 12
6.1 Requirements in line with ap-
proval.........................................
12
6.2 Preparations for wall installation 13
6.3 Ceiling installation preparations. 14
6.4 Preparations for the electrical
connection .................................
16
6.5 Preparing the shutter ................. 16
6.6 Conversion of exhaust socket
for air outlet towards rear...........
17
6.7 Conversion of air outlet adapter
for air outlet towards rear...........
17
7 Housing installation ............................. 18
7.1 Installation of ER GH housing ... 18
7.2 Installation information............... 18
7.3 Important information about
plastering ...................................
18
7.4 ER GH wall installation, single
room ..........................................
19
7.5 ER GH ceiling installation,
single room ................................
20
7.6 ER GH wall installation, second
room ..........................................
21
7.7 ER GH ceiling installation,
second room...............................
21
8 Electrical connection ............................ 22
8.1 Electrically connecting the unit ... 23
9 Final mounting....................................... 23
9.1 Attaching fan insert..................... 24
9.2 Attaching cover ER-A, ER-AK,
ER-AH or ER-AB ........................
24
9.3 Key lock...................................... 24
10 ER-AS extraction socket for WC
odour extraction ....................................
25
11 Operating the unit.................................. 25
12 Spare parts............................................. 25
13 System and accessory components ... 26
13.1 System components................... 26
13.2 Accessory components .............. 26
14 Dismantling ............................................ 27
15 Environmentally responsible dis-
posal .......................................................
27
16 Wiring diagram ...................................... 27
Wiring diagrams ......................... 27

Preface
3
Preface
Please read these instructions carefully before in-
stalling the flush-mounted housing. Before the fi-
nal assembly (fan insert and cover), please read
the instructions for the ER covers. The informa-
tion regarding filter changes and cleaning/main-
tenance is included in these instructions. Follow
the instructions. Pass these instructions on to the
owner for safekeeping.
1 Scope of delivery
ERGH flush-mounted housing
Article no. 0084.0350
• Flush-mounted plastic housing with exhaust
socket DN 75/DN 80 (no fire protection)
• Plastic shutter
• Plaster protective cover
• Installation and operating instructions
EREC fan insert (final assembly)
Article no. 0084.0360
• 2-level fan for installing in ERGH flush-moun-
ted housing.
• Air volume of 30m³/h, 60m³/h (20 / 40 /
100m³/h also possible if combined with an in-
telligent cover).
• Start delay 60s.
• Overrun time 15min.
For system and accessory components with more
detailed information and order numbers: System
and accessory components [}26].

Overview of ER EC system
4
Overview of ER EC system

Specialist installer qualifications
5
ERGH flush-mounted housing with plastic
shutter
1 ERGH housing with housing floor seal and 3
snap-fit fasteners for fan insert. Housing for
air outlet direction upwards, right, left or at
rear
2 Exhaust socket DN75/DN80 (plastic): In-
stallation with socket above or at rear
3 Airstream-operated shutter: Figure with hous-
ing installation position “air outlet above”
4 Plaster protective cover
S Housing segment for second room connec-
tion
ER EC fan insert
5 Spiral housing
6 Air outlet adapter: Air outlet above (factory
setting)
7 Air outlet adapter: Air outlet at rear
Covers: Figure with ER-AB
ER-A, ER-AK and ER-AH not shown
8 Cover – lower part with central screw
9 G2 air filter
10 Cover – upper part
Second room connection for toilet seat air ex-
traction
11 ER-ZR second room connection set
11.1 Installation socket DN75/DN80
11.2 Adapter
11.3 Internal grille
11.4 G2 filter mat
12 Second connection suction duct for toilet
seat air extraction (DN70)
13 ER-AS extraction socket (DN70) for toilet
seat air extraction
①Rating plate
②Wiring diagram (Tick device type.)
③TÜV sticker
Specialist installer qualifications
Installation may only be carried out by trained
specialists who have the necessary knowledge
and experience in ventilation engineering. The
unit must be connected in accordance with the
national technical approval.
Only a qualified electrician is permitted to work
on the electrics. You are deemed a qualified elec-
trician if you are familiar with the relevant stand-
ards and guidelines, can competently and safely
connect units to an electrical power supply in line
with the Wiring diagram [}27] and are able to
recognise and avoid risks and dangers associ-
ated with electricity on the basis of your technical
training and experience.
2 Intended use
ER EC fans are used to extract air from interior
bathrooms and toilets rooms, storage rooms or
open plan kitchens (with outside windows), for ex-
ample in multi-storey residential buildings, retire-
ment homes or hotel complexes.
Installation in a ventilation shaft, in the wall, front
wall or a suspended ceiling is permissible.
The fans can be used as standalone units or for
toilet seat air extraction (according to
DIN18017-3).
The fans are only intended for domestic use and
similar purposes.
3 Safety instructions
3.1 General safety instructions
The unit must not be used in the following
situations under any circumstances:
DANGER Risk of combustion/fire from
flammable materials, liquids or gases in the
vicinity of the unit.
Do not place any flammable materials, liquids or
gases near the unit, which may ignite in the event
of heat or sparks and catch fire.
DANGER Explosion hazard due to gases
and dust.
Explosive gases and dust may ignite and cause
serious explosions or fire.
Never use unit in an explosive atmosphere (risk
of explosion).

3 Safety instructions
6
DANGER Explosion hazard due to explos-
ive substances in the lab extraction units.
Explosive substances in lab extraction units may
ignite and cause serious explosions or fire.
Aggressive substances may damage the unit.
Never use unit in combination with a lab extrac-
tion unit (risk of explosion).
WARNING Risk to health from chemicals
or aggressive gases/vapours.
Chemicals or aggressive gases/vapours may
harm health, especially if they are distributed
throughout the rooms by the unit.
Never use unit to distribute chemicals or aggress-
ive gases/vapours.
NOTICE Damage to unit due to steam-satur-
ated or greasy air or adhering solid particles.
Steam-saturated or greasy air or solid particles
which may adhere to the unit, can soil the unit
and reduce the efficiency.
Never use unit to convey these substances.
NOTICE Damage to unit due to grease and oil
vapours from range hoods.
Grease and oil vapours from range hoods may
contaminate the unit and air ducts and reduce ef-
ficiency.
Never use unit to convey these substances.
NOTICE Damage to the unit when continu-
ously conveying steam-saturated air.
Never use unit to convey steam-saturated air
NOTICE Damage to the unit due to imbalance
of the impeller when conveying solid
particles.
Never use unit to convey solid particles that could
adhere to the unit.
NOTICE Unit damage during the construction
phase, caused by soiling of the unit and air
ducts.
Unit operation is not permitted during the con-
struction phase.
Do not operate unit during the construction
phase.
NOTICE Damage to unit in the event of mois-
ture ingress.
IPX5 (protection against water jets).
Never use unit outdoors.
3.2 Safety instructions regarding in-
stallation, operation, cleaning and
maintenance
DANGER Risks for children and people
with reduced physical, sensory or mental cap-
abilities or a lack of knowledge.
Unit may only be installed, commissioned,
cleaned and maintained by persons who can
safely recognise and avoid the risks associated
with this work.
DANGER Danger of electric shock from
operating the unit when not fully mounted.
Electric components are a potential source of
electric shock.
If the unit is open, all off the supply circuits must
be switched off (mains fuse off), secured against
being accidentally switched back on and a visible
warning sign must be attached.
Only operate the unit when it is completely in-
stalled.

3 Safety instructions
7
DANGER Danger if the relevant regula-
tions for electrical installations are not ob-
served.
Before removing the housing cover or removing
the fan insert and before installing the electrics,
switch off all supply circuits, switch of mains fuse
and secure it against being accidentally switched
back on again. Attach a warning sign in a clearly
visible place.
Be sure to observe the relevant regulations for
electrical installation; e.g. DIN EN 50110-1. In
Germany, particularly observe VDE 0100, with
the corresponding sections.
A mains isolation device with contact openings of
at least 3mm at each pole is mandatory.
Only connect unit to permanently wired electrical
installation and with NYM-O or NYM-J cables,
depending on the unit variant, 3 x 1.5mm² or 5 x
1.5mm².
Units may only be operated using the voltage and
frequency shown on the rating plate.
Unit may be energized even when at a standstill
and may switch on automatically due to sensors
(time delay, humidity etc.). Maintenance and fault
finding only permissible when carried out by qual-
ified electricians.
The degree of protection stated on the rating
plate is only guaranteed if installation is under-
taken correctly and if the connecting cable is cor-
rectly guided through the stepped grommet (The
grommet must completely enclose the cable
sheathing). The fan insert must also be engaged
and the housing cover installed.
DANGER Danger due to fire transmission
if an incorrect connection duct is connected to the
housing. Always use the correct cable material
for the respective housing. Requirements in line
with approval [}12].
if an incorrect ceiling compound is used for ex-
haust air systems with an intermediate ceiling
(ceiling barrier system). Ensure that the gap re-
maining between the main duct and wall or ceil-
ing is fully sealed with non-flammable materials
resistant to deformation, such as concrete, ce-
ment mortar or plaster.
WARNING Risk to health if filters are not
replaced or if there are no air filters.
Heavily soiled or moist air filters can accumulate
harmful substances (mould, germs, etc.). This
may also happen if the unit is shut down for an
extended period. If the air filter is missing, the
unit and air ducts become soiled.
Never operate the unit without air filters.
Only use original filters.
Regularly change air filter when a filter change is
indicated (LED or TimeStrip).
If the unit has not been used for a long time, al-
ways replace the air filters.
WARNING Risk of injury when working at
heights.
Use appropriate climbing aids (ladders).
Stability should be ensured, if necessary have
the ladders steadied by a 2nd person.
Ensure that you are standing securely and can-
not lose your balance and that there is no one
under the unit.
WARNING Risk of injury and risk to
health from parts which may affect the ventil-
ation system which are added or modified at a
later date.
Parts (range hood, air-ventilated fireplace etc.)
which are added or modified at a later date may
result in health risks and operation which is not
permitted. Parts may only be added or modified
at a later date if system compatibility is estab-
lished/ensured by a planning office. If using an
exhaust air range hood or air-ventilated fireplace,
this must be accepted by a regional master chim-
ney sweep.
WARNING Risk of injury and health risk
in the event of changes or modifications or if
components which are not permitted are
used.
The unit may only be operated with original com-
ponents. Changes and modifications to the units
are not permitted and release the manufacturer
from any guarantee obligations and liability, e. g.
if the housing is drilled at a point which is not
permitted.
CAUTION Exercise caution when hand-
ling packaging materials.
Observe applicable safety and accident preven-
tion requirements.
Store packaging material out of the reach of chil-
dren (risk of suffocation).

4 System and product information
8
NOTICE Non-intended operation/impermiss-
ible operation due to incorrectly mounted
unit.
Only install unit in accordance with the planning
documents.
In particular, note the information on ventilation
channels and sound deadening.
Observe planning instructions regarding unit pos-
ition and distance to other façade components.
If necessary, use isolating elements.
4 System and product informa-
tion
4.1 Certificates of approval
Certificates of approval on request.
4.2 Installation conditions
If installed in accordance with DIN 18017-3,
use is only permitted:
• in single air extraction systems with a common
main duct;
• with an air supply via shaft or duct;
• with permitted connection ducts;
• with the ER EC housing suited to the system;
• if correctly installed as per the instructions in
this manual and national technical approval;
• with sufficient space from the wall or ceiling;
• if unit is completely installed;
• with the correct air filters;
• with the outside air openings stated in the plan-
ning documents.
• with flush-mounted installation in the wall or
ceiling.
If the installation deviates from DIN 18017-3:
• ER EC fans can also be used as standalone
units.
• Installation in the wall or ceiling is permitted.
• The extraction of an additional room (open plan
kitchen etc.) or a toilet seat air extraction is per-
mitted.
4.3 Permitted exhaust air systems
The ER EC single air extraction system can be
used in combination with a ceiling barrier sys-
tem inside and outside the shaft.
A fan connection duct, made of flexible aluminium
duct, is also prescribed for a second connection.
Use in an air extraction system is permissible
without protection requirements.
4.4 Possible combinations
ER-A
ER-AK
ER-AH
ER-AB
ER EC ER GH
In the shell construction phase the ERGH
flush-mounted housings are installed, electrically
wired and provided with a plaster protective
cover.
In combination with the second room connection
set (ER ZR) and the ER-AS extraction socket, the
EREC can also be used for toilet seat air extrac-
tion (extraction via flushing pipe).
Final mounting is undertaken once the plaster-
ing and paint work is complete: Place the fan in-
sert into the housing and attach the cover with air
filter. For covers ER-AK, ER-AH and ER-AB, ad-
just the setting values as necessary.
ER GH flush-mounted housing
• DN 75 or DN 80 connection diameter.
• Plastic housing without fire protection equip-
ment. Can be combined with ceiling barrier sys-
tem.
• Sealed housing with water jet protection for
areas 1 (IP X5).
• For the wall or ceiling installation, inside or out-
side the exhaust air shaft.
• Permissible air outlet direction with wall installa-
tion upwards, to the right, to the left or to the
rear.
• Turn air outlet to the right or left by turning the
housing by 90°.
• Plastic exhaust socket with airstream-operated
plastic shutter, maintenance-free.
• Fix exhaust socket in housing, can be conver-
ted for air outlet at rear without tools.
• Easy-to-install snap-fit fasteners for fastening
the fan insert.
• For the connection sockets of a toilet seat air
extraction or a second room connection, knock-
out point at bottom.

4 System and product information
9
• Electrical connection at side or rear. Cable
feedthrough with stepped grommet.
• Can be mounted simply in the shaft with mount-
ing support or the mounting grooves. Accessor-
ies for UPM 60/100 mounting support or ER-MS
mounting grooves (installation kit: 4 hammer
head screws, 4 nuts and 90° brackets).
• Can be screwed directly into the front wall or
ceiling (4 slots in the external frame).
• Mains cable type NYM-O or NYM-J, 3 x 1.5 or 5
x 1.5mm², depending on the cover variant.
ER EC fan insert
• Fan insert for installation in housing.
• Electrical plug connection for quick installation
in the housing.
• Energy-saving EC motor.
• Motor not speed controllable.
• Air outlet adapter (scope of delivery) for conver-
sion of air outlet towards the rear.
Covers
• Cover with exhaust air filter. Trouble-free filter
change without tools.
• ER-AH and ER-AB: Barrier-free products,
switch on and off automatically.
• ER EC fans with water jet protection for areas 1
(DIN VDE 0100-701).
• It is possible to rotate the cover by ±5° to com-
pensate for housings which have been fitted at
an angle.

5 Technical data
10
4.5 Covers: Functions
ER-A ER-AK ER-AH ER-AB
Filter change indicator
(6 months) with TimeStrip
●
Filter change indicator
(6 months) with LED
● ● ●
Control with time module ● ● ●
Control with fully automatic humidity control: Extraction
takes place automatically if the specified switch-on hu-
midity is exceeded.
●
Control with motion detector. Full load level after motion
is detected (range motion sensor is 5m)
●
Barrier-free product, as it switches itself on and off auto-
matically
● ●
Not speed controllable ● ● ● ●
Electrical plug connection for quick connection of the ER
EC with ER GH housing and ER-AK, ER-AH or ER-AB
with the ER EC fan insert.
● ● ●
Air volume – base load 30m³/h for continuous operation ● ● ● ●
Air volume of the base load and full load levels can be set ● ● ●
Additional air volumes that can be set
in base load: 20m³/h, 40m³/h, 60m³/h or 100m³/h and
in full load: 20m³/h, 30m³/h, 40m³/h or 100m³/h
● ●*** ●
Full load level on/off via light switch or separate switch.
During manual operation (e.g. using light switch), the
start delay and overrun time apply.
● ● ● ●
Full load operation (60m³/h) with start delay of 60
seconds and overrun time of 15 minutes, non-adjustable
●
Full load operation (60m³/h), start delay can be set with
0, 30, 60*, 90 or 120 seconds
● ● ●**
Overrun time of the full load level can be set for 0, 3, 6,
15*, 24 or 30 minutes
● ● ●
Adjustable interval control for ventilating rooms that are
not regularly used. Time interval can be set for 0*, 1, 2, 4,
6 or 12 hours, 10 min. operating time per interval
● ● ●
Interval control can be switched off. ● ● ●
Switching option: The base load can be switched on or
off by an additional switch (Wiring diagram [}27]).
● ● ● ●
* Factory setting: Tolerance of time details max. ±
5 %
** For the ER-B, the start delay only affects the
light switch operation.
*** For ER…H humidity control in full load, 60m³/
h and 100m³/h can be set.
5 Technical data
5.1 Environmental conditions and op-
erating limits
• Permissible maximum temperature of air me-
dium + 40 °C.

5 Technical data
11
• The air supply to the home must be set up so
that virtually no air can flow into the living areas
from the kitchen, bathroom or WC.
• A room from which the air is to be extracted
must be fitted with a non-closable, free supply
air cross section of at least 150cm², e.g. with
Maico MLK door ventilation grille.
• ER EC units have resistance to interference in
line with EN 55014-2 (depending on pulse type
and an energy factor of 1000 to 4000V). These
values can be exceeded when operating with
fluorescent tubes. In this case, additional inter-
ference suppression measures (L, C or RC
modules, protection diodes, varistors) are re-
quired.
5.2 Regulations for operation with
fireplaces
Sufficient supply air intake must be ensured
during operation with air-ventilated fireplaces.
The maximum permitted pressure difference per
residential unit is 4 Pa.
The unit may only be installed in residential units
with air-ventilated fireplaces under the following
conditions:
• the evaluation criteria drawn up by the respons-
ible, regional master chimney sweep are met;
• Parallel operation of air-ventilated fireplaces for
liquid or gaseous fuels and air-extracting equip-
ment can be prevented using safety devices or
• the extraction of exhaust gas from the air-ventil-
ated fireplaces is monitored by special safety
devices. The ventilation system or the fire-
places must be switched off if the equipment is
triggered.
5.3 Technical data table
Rated voltage 230 V
Power frequency 50 Hz
Power consumption
ER EC and ER-A 3/5 W*
ER-AK, ER-AH and ER-
AB
2/2.5/3/5/17W*
Degree of protection IP X5
Sound pressure level
LWA7
19 to 52 dB(A)
Mains cable to ER EC,
depending on switching
variant for ER-A, ER-
AK, ER-AH, ER-AB
3 x 1.5 mm²
or
5 x 1.5 mm²
Weight
ER GH housing 0.6 kg
ER EC fan insert 0.72 kg
ER-A.. cover 0.6 kg
* Specification according to DIN 18017-3 with an
equivalent absorption area of AL = 10 m²
For more technical data → rating plate.
For characteristic curves→ www.maico-ventil-
atoren.com

6 Mounting preparations
12
5.4 Storage
Only store unit horizontally in a suitable, dry
room. Ambient temperature – 10 °C to + 60 °C.
Maico accepts no liability for corrosion damage
caused by improper storage, e.g. storage in a
damp environment.
6 Mounting preparations
Suitable mounting material is to be
provided by the customer.
6.1 Requirements in line with ap-
proval
Approval provisions
Approval provision ER GH
Number of units per
floor, residential unit or
fire zone
Max. 3 fans or 3 con-
nections
Connection diameter DN 75 or DN 80
Shaft wall Any board material
Connection ducts inside
the shaft
E.g. AFR80 flexible
aluminium duct
between main duct in
shaft and ER unit, max.
2m long (→ approval).
Connection ducts out-
side the shaft
E.g. AFR80 flexible
aluminium duct
between main duct in
shaft and ER unit, max.
6m long (→ approval).
Duct elbows in the unit
connection duct
max. 90° bend, ascend-
ing
Number of duct elbows
permitted for wall in-
stallation
Max. 2 x 90°
Number of duct elbows
permitted for ceiling in-
stallation
Max. 2 x 90°
Regulating equipment
in the exhaust air duct
Not permitted
Wall/ceiling opening for
DN 80 unit connection
duct
Brickwork or concrete:
130mm

6 Mounting preparations
13
6.2 Preparations for wall installation
12 Suction duct for second room connection on
ER GH: AFR75/AFR80 flexible aluminium
duct
14 Main duct: Steel folded spiral-seams duct
15 Connection duct on ERGH: AFR75/AFR80
flexible aluminium duct permitted inside the
shaft
16 Power cable
Installation information
• Observe approval: Certificates of approval [}8]
and Requirements in line with approval [}12].
• Always use correct duct material for the hous-
ing.
• For fire protection systems, the gap remaining
between the connection duct and brickwork/wall
boards/wall/ceiling must be fully sealed with
non-flammable materials that are resistant to
deformation (e.g. concrete, cement mortar, fire
protection filler).
NOTICE Damage to unit, malfunctioning in the
event of corrosion damage from mortar.
Wrap ventilation ducts, connected to the unit,
with a suitable adhesive tape to protect against
corrosion inside the brickwork, e.g. using cold-
shrink tape.
Preparing the shaft
1. Produce opening in shaft or alternatively pro-
duce a wall facing. Ensure a suitable, flat sur-
face for the housing so that the fan insert can
be safely inserted in the housing later on.
2. For a second room connection, produce an
opening in the wall or shaft for the suction
duct. Note permissible housing installation po-
sitions.
3. Correctly attach main duct inside the shaft.
4. For fire protection systems, use ceiling com-
pound. To do this, encase the ceiling and pour
in the material from above.
5. Connect connection duct, suitable for the
housing, to the main duct and seal for ventila-
tion.
6. Cut connection duct to length, note a max-
imum duct length of 6m.
Cut connection duct to a length which al-
lows it to be fitted on the exhaust socket
and also sealed for ventilation at the unit
end.
7. Lay suction duct and seal gap remaining cor-
rectly as described in previous mounting in-
structions.

6 Mounting preparations
14
8. Lay power cable in shaft and allow to protrude
by around 30cm above the shaft opening. 9. Lay power cable: Electrically connecting the
unit [}23].
6.3 Ceiling installation preparations
12 Suction duct for second room connection on
ER GH: AFR75/AFR80 flexible aluminium
duct
14 Main duct: Steel folded spiral-seams duct
15 Connection duct on ERGH: AFR75/AFR80
flexible aluminium duct
16 Power cable
Be sure to note the approval and installa-
tion information: Preparations for wall installa-
tion [}13].
Preparing the shaft and suspended ceiling
1. Make an opening in the suspended ceiling.
2. Make an opening in the shaft for DN 75 or DN
80 connection duct.
3. For a second room connection, produce the
opening in the wall or shaft for the suction
duct. Observe installation positions for the
second room connection.

6 Mounting preparations
15
14 Main duct (steel folded spiral-seams
duct)
15 ERGH connection duct: Flexible alu-
minium duct
17 Floor ceiling
18 Steel threaded rod / stair bolt
19 Duct fastener
20 Duct clamp / clamping band
22 Ceiling compound
23 Shaft wall
24 Wall/board seal
25 Suspended ceiling
26 Steel screws or steel blind rivets (3 of
each)
27 Dowel
27.1 Plastic dowel or anchor bolt
27.2 Metal expansion dowel
28 Retaining bolt with nut
29 Retaining bolt
30 Steel clamping band
Be sure to note the approval and installa-
tion information: Preparations for wall installa-
tion [}13].
Duct attachment with duct clamp, alternatively
duct attachment with clamping band
Ensure a spacing of max. 1.5m between the
duct attachments.
1. Correctly attach main duct inside the shaft.
2. For fire protection systems, use ceiling com-
pound. To do this, encase the ceiling and pour
in the material from above.
3. Fit duct attachments to the ceiling. Only use
permitted mounting material.

6 Mounting preparations
16
DANGER Risk of incorrect installation if
non-permitted mounting material is used.
Only secure connection duct to ceiling with per-
mitted mounting material (duct clamp or clamping
band).
4. Connect permitted connection duct to main
duct and seal for ventilation, for example with
cold-shrink tape.
5. Apply wall/board compound. Seal gap
between brickwork and folded spiral-seams
duct. The gap remaining must be fully sealed
with non-flammable materials that are resist-
ant to deformation. For example, use concrete
or cement mortar or for wall boards, use fire
protection filler.
6. Fit suspended ceiling. Use ER GH housings to
ensure a suitable, flat surface so that the fan
insert can be safely inserted in the housing
later on.
7. Lay power cable: Electrically connecting the
unit [}23].
6.4 Preparations for the electrical
connection
• Always note the relevant specifications for elec-
trical installations and when fitting equipment. In
Germany, observe DIN VDE 0100 and the cor-
responding parts in particular.
• Observe ambient conditions (Environmental
conditions and operating limits [}10]) and
technical data (Technical data [}10]).
• Observe permitted duct cross-section of max.
1.5mm².
1. Lay power cable to the installation location.
2. Continue with the safety test of the release
device: Preparing the shutter [}16].
6.5 Preparing the shutter
NOTICE Odours may escape from the ventila-
tion channel.
If the installation position is wrong, the plastic
shutter will not close leak-tight.
Insert shutter at the top/to the right/to the left/to
rear in the exhaust socket of the housing to fit the
installation position. Ensure that the shutter
closes entirely leak-tight.
Before fitting housing, it is essential that
the position of the shutter is checked and its
function ensured.
For wall installation with air outlet direction
(exhaust socket) to the left or right, install the
shutter rotated by 90°, see following figures.
Prepare plastic shutter: Air outlet to top, left
or right
Wall installation
1. Upwards air outlet direction: Do not carry
out any modifications (factory setting).
2. Air outlet direction to the left or right: Pull
the shutter out of the exhaust socket, depend-
ing on the installation position, rotate and rein-
sert it. Make sure that the shutter is pushed up
to stop in the exhaust socket.
As a rule, use the standard installation position
with upwards air outlet direction for ceiling in-
stallation (factory setting).

6 Mounting preparations
17
6.6 Conversion of exhaust socket for
air outlet towards rear
3 Shutter
Z Positions
X 4 locking bolts
W 4 bayonet hooks
Y 4 slots
Before the conversion, pull the shutter out
of the exhaust socket.
1. Fig. at top: At the 4 positions, loosen (pull off)
the 4 locking bolts (push buttons) on the ex-
haust socket.
2. Push the 4 bayonet hooks in the exhaust
socket at the side into the 4 slots to the right
and remove the exhaust socket.
3. Fig. at bottom: Rotate the exhaust socket so
that it is pointing to the rear.
4. Place the exhaust socket onto the housing
and push with the 4 bayonet hooks (at rear) to
the right into the slots right up to stop.
5. Push the 4 push buttons into the housing
holes on the upper side of the housing at posi-
tions [Y]. These must audibly engage.
NOTICE If the air exhaust socket is installed
incorrectly, the function of the unit is im-
paired.
Ensure that all locking bolts and push buttons are
engaged and that the socket is flush with the
housing.
6. Check for correct installation of the exhaust
socket.
7. Insert the shutter into the exhaust socket as
described in the Left air outlet direction in-
stallation position: Preparing the shutter [}16].
6.7 Conversion of air outlet adapter
for air outlet towards rear
5 Spiral housing
6 Air outlet adapter: Air outlet above (factory
setting)
7 Air outlet adapter: Air outlet at rear
For air outlet direction to the rear, replace
the air outlet adapter with the curved air out-
let adapter.
Replacement
1. Loosen the 2 locking tabs of the exhaust
socket and carefully pull it out of the spiral
housing rearwards.

7 Housing installation
18
2. Push the exhaust socket into the slot on the
spiral housing until it audibly engages with the
two locking tabs.
3. Check and secure correct connections.
7 Housing installation
7.1 Installation of ER GH housing
The following are not permitted:
• Use of an ER EC fan in the bathroom or toilet
room if other rooms in the apartment are to be
vented with the same unit at the same time.
7.2 Installation information
(also Requirements in line with approval [}12])
ERGH housing without fire protection device.
Installation is permissible in the following posi-
tions:
•Wall installation With air outlet direction (ex-
haust socket) upwards, to the right, to the left or
to the rear. Installation with UPM 60/100 mount-
ing support or directly with the wall with ER-MS
installation kit (hammer head screws and brack-
ets) in the side mounting grooves.
•Ceiling installation and suspended ceiling:
Installation with UPM 60/100 mounting support
or directly with the ceiling with ER-MS installa-
tion kit (hammer head screws and brackets) in
the side mounting grooves.
•Ceiling installation and non-suspended ceil-
ing: Mounting directly on the ceiling.
Suitable mounting material is to be provided by
the customer.
The plastic shutter should be prepared ac-
cording to these instructions so that it closes
fully sealed in the installation position.
The housing must be inserted without any dis-
tortion. Failure to do so will mean that the fan in-
sert cannot engage correctly in the housing and
the degree of protection stated on the rating plate
is no longer ensured.
Break open the housing segment [S] below to use
the ER-ZR second room connection set or the
ER-AS extraction socket.
A toilet seat air extraction unit is connected to the
housing using the ER-AS extraction socket
(DN75/80).
Use ER-MO expanded rubber for acoustic insula-
tion of thin ceilings capable of resonance (System
and accessory components [}26]).
7.3 Important information about
plastering
• Max. compensable plaster overshoot 7mm.
• Installation at a depth of 50 to 100mm can be
compensated for with the two-part wall frame
ER-MR.
• The gap remaining between the housing and
shaft must be fully sealed with non-flammable
materials that are resistant to deformation so
that incorrect air is not drawn in.
Recommendation: Keep these installation and
operating instructions until final installation in the
housing.

7 Housing installation
19
7.4 ER GH wall installation, single room
2 Exhaust socket with plastic shutter
4 Plaster protective cover
14 Main duct, steel folded spiral-seams duct
15 Connection duct, AFR80 DN75/80 flexible
aluminium duct
16 Power cable
31 Mounting support UPM 60/100 or ER-UPM (2
items)
32 Stepped grommet
33 ER-MO expanded rubber
1. Remove the plaster protective cover from the
housing.
NOTICE The unit will be damaged and func-
tion impaired if the fixing screws used are in-
correctly / too long.
Fixing screws may not penetrate into the hous-
ing.
Use screws provided (mounting support
UPM60/100).
2. Cut the mounting support to the required
length, bend it into shape and fix it to the
housing with the supplied fixing screws.
3. Mark fixing holes for mounting support on rear
shaft wall, produce holes and insert dowels.
Suitable mounting material is to be provided
by the customer.
DANGER Danger of short-circuits and
damage to the unit.
If the stepped grommet is not installed correctly,
water may penetrate the housing. The degree of
protection can no longer be guaranteed.
Drive through stepped grommet so that it can
seal the cable sheathing all the way round (circu-
lar, not a slot).
4. Insert power cable from rear of housing
through stepped grommet into housing.
5. Insert the housing with the mounting support
into the shaft and fix it to the rear wall of the
shaft.
DANGER Fire may spread if connection
duct is incorrectly installed.
Only use permitted duct material (Requirements
in line with approval [}12]).
Correctly attach connection duct to exhaust
socket.
6. Connect connection duct to exhaust socket
sealed for ventilation, e.g. with cold-shrink
tape.

7 Housing installation
20
7. Provide unit with electrical connection: Elec-
trically connecting the unit [}23].
8. Insert the plaster protective cover in the hous-
ing.
9. Plaster in housing flush with front edge, note
tile thickness if necessary: Important informa-
tion about plastering [}18].
7.5 ER GH ceiling installation, single
room
1. Remove the plaster protective cover from the
housing.
NOTICE The unit will be damaged and func-
tion impaired if the fixing screws used are in-
correctly / too long.
Fixing screws may not penetrate into the hous-
ing.
Use screws provided (mounting support
UPM60/100).
2. For suspended ceilings, cut mounting support
to the required length, bend it into shape and
fix it to the housing (ER GH wall installation,
single room [}19]).
3. Mark fixing holes for mounting support/hous-
ing on ceiling, produce holes and insert dow-
els. Suitable mounting material is to be
provided by the customer.
DANGER Danger of short-circuits and
damage to the unit.
If the stepped grommet is not installed correctly,
water may penetrate the housing. The degree of
protection can no longer be guaranteed.
Drive through stepped grommet so that it can
seal the cable sheathing all the way round (circu-
lar, not a slot).
4. Insert power cable from rear of housing
through stepped grommet into housing.
5. Move housing into desired position and secure
to ceiling with/without mounting support.
DANGER Fire may spread if connection
duct is incorrectly installed.
Only use permitted duct material (Requirements
in line with approval [}12]).
Correctly attach connection duct to exhaust
socket.
6. Connect connection duct to exhaust socket
sealed for ventilation, e.g. with cold-shrink
tape.
7. Provide unit with electrical connection: Elec-
trically connecting the unit [}23].
8. Insert the plaster protective cover in the hous-
ing.
9. Plaster in housing flush with front edge.
Table of contents
Other Maico Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Fueltec
Fueltec BIO-VAC 270 product manual

Wallenstein
Wallenstein QC605 Operator's manual

Fröling
Fröling T4e operating instructions

Wieland
Wieland SNA 4043K operating instructions

Martin
Martin PIT VIPER installation instructions

PCB Piezotronics
PCB Piezotronics IMI SENSORS 638A06 Installation and operating manual