
5
IOM - 7602-444 Communicating Service Tool
Option Selection Menu
Unit Conguration Menu
OPTION SELECTION
MOTORIZED VALVE OFF
COMPRESSOR ASCD 0
SELECT OPTION
PREVIOUS SELECT
NOTE: “Motorized Valve” used here refers to a two-position
motorized water valve, not to be confused with the modulating
motorized water valve found in the LOOP CONFIG.
3.2 OPTION SELECTION
This option allows the conguration of heat pump options to
be modied.
Adjust the Option settings using the up/down arrow buttons.
Press the center button to select each item.
• Motorized Valve (defaults stored in control) – valid
range: O, On “On” delays compressor start until
the valve is fully open.
• Compressor ASCD (Anti-Short Cycle Delay (default
stored in control) – valid range: 5 to 8 (in 1 minute
increments)
NOTE 1: The Compressor Anti-Short Cycle Delay setting
provides equipment protection by forcing the compressor to
wait a few minutes before restarting.
NOTE 2: If multiple units are connected to one thermostat,
refer to section 3.6 for unit selection.
3.3 UNIT CONFIGURATION
Adjust the Unit Conguration settings including Heat
Pump Family, Heat Pump Size, Blower Type, and Loop
Conguration using the up/down arrow buttons. Press the
center button to select each item.
• Heat Pump Family (default stored in control) –
valid range: TE, TY, TES, TEP, TRT, TSM, TSL
• Heat Pump Size (default stored in control) – valid
range: depends on Heat Pump Family setting
• Blower Type (default stored in control) – valid
range: NO BLOWER, 2-SPD PSC, COM ECM-V,
1-SPD PSC, 2-SPD CTM, PWM ECM, VFD
• Loop Cong (default stored in control) – valid
range: Other, VS PUMP, MOD VALVE
Airow, pump and valves can be congured from ‘System
Conguration’ screen.
Select ‘VS PUMP PARALLEL’ when applying an internal
variable speed ow controller with other ow controllers on a
single loop in parallel.
NOTE: Refer to section 3.6.3 for multi-unit conguration
instructions.
UNIT CONFIGURATION
CURRENT CONFIG TE026
HEAT PUMP FAMILY TE
HEAT PUMP SIZE 026
BLOWER TYPE ECM
LOOP CONFIG VS PUMP
SELECT OPTION
PREVIOUS SAVE
Equivalent Model Numbers
Heat Controller Climate Master
HE-Series TZ
HZ-Series TE
HZS-Series TES
HB-Series 0.5-5T TC
HB-Series 7-25T TL
HKV-Series TL
HRC-Series TRC