14/20 53799173-05
ADDING REFRIGERANT
1If additional refrigerant charge is required:
After evacuating the indoor unit and interconnecting pipework, open the valves using a 4 or 5mm Allen key. The
high and low side pressures should equalise within a minute.
2Additional charge for all systems, including heat pumps, should be introduced with the system in the AIR
CONDITIONING MODE.
3Additional charge should be introduced through the Schrader valve on the indoor unit or the service port on the
suction service valve on the outdoor unit (see charging section overleaf to calculate the weight).
4 DCUE, DHPUE and MHPUE are supplied with link JP6 fitted on the outdoor unit pcba; this allows additional
charging and overrides alarms during the charging process. With both units powered, the DCUE, DHPUE or
MHPUE fans will run at high speed and IMPACT E indoor fans will run at maximum speed. When JP6 is linked, the
infrared handset is inoperative.
NOTE: MCU+ units are fitted with head pressure control; before charging, isolate the unit and transfer the blue
5Ensure that the refrigerant being added is the same refrigerant that the system was originally charged with.
6If a manual HP cutout is fitted, ensure that the reset button is depressed.
7On DCUE, DHPUE and MHPUE models a random start delay of up to 1 minute occurs when mains is first applied.
A 3 minute delay occurs between successive compressor operations on all systems incorporating DCUE, DHPUE
and MHPUE units, or MCU(+) units fitted with a 3 minute timer kit.
8Run the system for a few minutes to allow it to stabilize. Where possible, charge to a sweat line on the evaporator.
Typical suction pressures on short lines at UK conditions, with high speed evaporator fan, low speed condenser
fan (commissioning speed for DCUE, DHPUE and MHPUE), should be; Electromechanical Comfort Systems
approx. 4.4 bar (65 psig); Electronic Comfort Systems approx. 3.8 bar (55 psig); Heat Pump Systems approx. 4.0
bar (58 psig).
Care should be taken when the compressor is first started in the field to ensure that the system is not overcharged,
in which case liquid return to the compressor could result.
9On DCUE, DHPUE and MHPUE units, once refrigerant has been added, REMOVE link JP6, identified by a white
label (otherwise the unit will always run at full speed).
10. On MCU+ units,return the blue wire from 1 to 4.
WHEN INSTALLATION HAS BEEN COMPLETED - CHECK :-
1. All pipe work and joints for leakage.
2. All pipe work and fittings for insulation.
3. All bolts are secure and that the fan rotates freely.
CHARGING
IMPACT WALL MOUNTED SYSTEMS - pipe runs below 7.5m.
Each outdoor unit is charged with R22 or R407C as shown on page 18.
Where additional refrigerant is needed this is shown on P18. Additional oil is not required.
IMPACT WALL MOUNTED SYSTEMS - pipe runs over 7.5m.
For pipe runs over 7.5m, extra refrigerant and oil must be added to the system by the installation engineer as
shown on page 18 PLUS additional refrigerant and oil for each metre over 7.5m, based on the following:
Expansion line size. 3/8 1/2 5/8
Additional refrigerant (g/m) 16 30 48
Additional oil 25g per 350g of additional refrigerant to a
maximum of 300g