
11
If, as a result of fitting this kit, more than one supply is taken into a unit, that unit must be marked:-
"Two, (or more if applicable), supplies are taken into this equipment.
Isolate both, (all), before undertaking any maintenance work."
RETURN AIR SENSOR 97200212 (FOR RCC 30 REMOTE CONTROLLER 97200211)
The sensor can be fitted to the return air inlet to an air conditioning unit to improve operation eg. if the wall thermostat is
placed outside the space being conditioned, or if there is considerable stratification in a room with a high ceiling, where
the wall thermostat would not measure a representative temperature.
ISOLATE THE SYSTEM ELECTRICALLY PRIOR TO INSTALLATION OF THE
SENSOR
1. Cut off the faston terminals on the cables and strip back.
2. Connect the sensor to terminals B1 and M , as shown (polarity is unimportant).
Changeover to the remote sensor is automatic on power up of the controller.
3. Tie wrap the sensor to a suitable place in the return airflow, where it will soak in a
representative temperature.
4. After installation, adjust the thermostat to confirm satisfactory operation.
5. Sensor input B1-M carries mains potential.
If the sensor cable needs to be extended, the cables used must be suitable for mains
voltage.
PROGRAMMABLE TIMER KIT 52500151
This kit can be used to give ON/OFF switching of the mains voltage control circuits of WM units where the total current
does not exceed 3 Amps.
ELECTRIC HEATER CURRENTS CANNOT BE SWITCHED DIRECTLY.
It is not required for WM L units which have built in timers.
PROGRAMMER SPECIFICATION: Selection Switch
Type: Digital electronic 230V, 50Hz "OFF",
Programme: 7 day "TMD " (TIMED)
Setting Resolution: 1 minute "CON " (CONSTANT ON)
Max. Switched Current: 3 A (fan load) "ADV " (ADVANCE)
The timer will accommodate 0.75mm2to 2.5mm2wires.
Three core cable is required between the timer and the air conditioning unit.
The timer motor must be connected to an uninterrupted supply source.
TIMER MOUNTING
1. Carefully unpack and identify the components.
2. If the unit is to be surface wired, remove the appropriate knockouts in the backplate. Screw the backplate to the wall
with No. 8 wood screws through the fixing holes.
3. If the backplate is to be fixed to a BS4662 single gang plaster depth box, use 3.5mm machine screws.
WIRING FOR ON/OFF SWITCHING
1.a) Wire timer terminal 'L' to unit terminal 2.
b) Use the terminal provided to connect terminal 4 to live (terminal L, remote controller RCC 30 [97200211]).
c) Wire timer terminal 'N' to unit terminal N
2.Discard the in-line fuse carrier.
3.Plug in the unit and secure the screws.
4.Program as described in the separate timer instructions.