
USING YOUR ELECTRONIC CONTROL
Control Function Guide
First Use
Initial startup requires no adjustments. When plugged in, the unit will
during installation, simply press and the unit will immediately switch on.
ogressing towards
the selected temperature. Time to reach set point varies based upon ambient
temperature, temperature of product loaded, door openings, etc. Marvel recommends
allowing the unit to reach set points before loading.
Function Command Notes
ON/OFF Press and release. Unit will immediately turn ON or OFF.
Adjust Temperatures
Toggle Between oF / oC Hold and for 5 seconds. The display will change units.
Leave Interior Light On Press and release to leave interior light on for
12 hours; press again to deactivate.
After 12 hours, factory default is restored; light will turn on when
door is open.
Hide Display Hold and press . operate. Repeat command to turn on display.
Adjust Light Color While holding , press and release to scroll
through lighting options.
Option Open Door Closed Door
White White
Blue Blue
White Blue
Light will be set at full intensity when door is open, and 50%
intensity when door is closed.
Enable Sabbath Mode Press and hold for 5 seconds and release.
Disable Sabbath Mode Display and interior light return to normal operation.
Showroom Mode Hold and for 5 seconds.
The oF / o
will function. Unit will not cool. Repeat command to return to
normal operation.
When the door is left open for more than 30 minutes:
• A tone will sound for several seconds every minute
• will appear in display
• Close door to silence alert and reset
High/Low Temp. Notications
Interior lights indicates zone temperature being set;
Blue = Upper (33o - 45o)
White = Lower (38o- 65o)
Note: The set temperature of the lower zone can't be
colder than the set temperature of the upper zone.
Adjusting the set temperature of the upper zone may
cause the lower zone to automatically adjust. The lower
zone cannot be more than 20oabove the set temperature
of the upper zone.
See table on next page.
Press or and release to adjust the upper
zone. Press to change to lower zone.
Press or and release to adjust.
light and display will go dark and remain so until user
resets mode - unit continues to operate.
Press and hold for 5 seconds and release.
High/Low Temp Notifications
When the compartment temperature exceeds the control
setting for an extended amount of time:
•“HH” will appear in display (High
Temp)
•“LL” will appear in display (Low Temp)
Contact service dept. for further instructions.
19