Masibus 8208 User manual

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 1 of 42
M
Mo
od
de
el
l
8
82
20
08
8
U
Us
se
er
r’
’s
s
M
Ma
an
nu
ua
al
l
8
8-
-C
Ch
ha
an
nn
ne
el
l
S
Sc
ca
an
nn
ne
er
r
Masibus Automation & Instrumentation Pvt. Ltd.
B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India
Web: www.masibus.com

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 2 of 42
Contents
(1) Introduction (03)
(2) Installation (05)
(3) Hardware Specification Detail (08)
(4) Front and Back Panel Description (11)
(5) Key Function Description (14)
(6) Menu Layout (15)
(7) Relay/OC Outputs (22)
(8) Calibration Procedure (27)
(9) Modbus Communication Detail (29)
(10) Miscellaneous (36)

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 3 of 42
1. INTRODUCTION:
Forewo rd
Thank you for pur chasing 8 208 un iver sal Scann er . This manual
desc ribes th e basic functi on s and op erati on method s of 8208. Please
read through this user‟s manual carefully before using the product.
Notic e
The cont ents of thi s manual are subj ect to ch ange wi thout noti ce as a
resul t of conti nuin g improve ments t o the ins trument‟s performance and
functi ons
Every effort has been made to ensure accuracy in the preparation of this
manual. Should any errors or omissions come to your attention, however, please
inform MASIBUS Sales office or sales representative. Under no circumstances may
the contents of this manual, in part or in whole, be transcribed or copied without our
permission.
Trademarks
Our product names or brand names mentioned in this manual are the
trademarks or registered trademarks of Masibus Automation and Instrumentation (P)
Ltd. (herein after referred to as MASIBUS).
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated. All other product names mentioned in this user's
manual are trademarks or registered trademarks of their respective companies.
Revis ion
1st Edition: July 2010.

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 4 of 42
Checki ng the Conten ts of the P ackag e
Unpack th e box and ch eck the content s befor e using th e
product . If the pr oduct i s diff erent from th at whi c h you have order ed,
if any part s or a cces sories a re mis sing, or if t he p roduct appea rs to b e
damag ed, c ontact your sal es rep resentati ve .
Product Ordering Code:
The 8208 Scanner unit has a nameplate affixed to the one side of the
enclosure. Check the model and suffix codes inscribed on the nameplate to confirm
that the product received is that which was ordered.
Model
Suffix code
Optional code
Remarks
List of Accessories
The product is provided with the following accessories according to the model
and suffix codes (see the table below). Check that none of them are missing or
damaged.
No
Item
name
Part
number
Qty
Remarks

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 5 of 42
2. INSTALLATION:
How to Install:
Mounting method: Panel mounting
To install the controller select a location where:
ono one may accidentally touch the terminals
omechanical vibrations are minimal
ocorrosive gas is minimal
otemperature can be maintained at about 25˚C to 35˚C and the
fluctuation is minimal
ono direct radiant heat is present
ono magnetic disturbances are caused
ono wind blows against the terminal board
ono water splashed
ono flammable materials are around
Turn off the power to the controller before installing it on the
panel because there is a possibility of electric shock

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 6 of 42
External Dimensions and Panel Cutout Dimensions:
Unit: mm

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 7 of 42
How to connect wires:
Before carrying out wiring, turn off the power to the
controller and check that the cables to be connected are not alive with
a tester or the like because there is a possibility of electric shock.
NOTE:
oAll wiring must confirm to appropriate standards of good practice and
local codes and regulations. Wiring must be suitable for Voltage,
Current and temperature rating of the system.
oProvide power from a single-phase instrument power supply. If there
is a lot of noise in the power line, insert an insulating transformer into
the primary side of the line and use a line filter on the secondary side.
Do not place the primary and secondary power cables close to each
other.
oFor thermocouple input, use shielded compensating lead wires for
wiring. For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance between
the three wires. Do not connect Terminal NO –13,
16,19,22,37,40,43,46 when thermocouple or linear input is selected.
oUse repeater after each set of 32 instruments connected in RS-485
Communication.
oUnused terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
CAUTION:
High voltage transients may occur when switching inductive loads such
as some contactors or solenoid valves. Through the internal contacts,
these transients may introduce disturbances which could affect the
performance of the instrument.
For this type of load it is highly recommended that a “sunbber” is
connected across the normally open contact of the relay switching
though load. The sunbber recommended consists of a series connected
resistor/capacitor (typically 15nF/100 Ohms). A sunbber will also
prolong the life of the relay contacts. A sunbber should also be
connected across the output of a tric output to prevent false triggering
under line transient conditions

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 8 of 42
3. Hardware Specification Detail:
Input type: Universal input type
Thermocouple, RTD, Millivolt, Voltage, Current INPUT types are software selectable.
Applicable Standards: DIN (ITS-90) for Thermocouple and RTD
Type
Rang e
Accur acy
Resol ution
E
-200 t o 1000 C
+0.1% of instrument range
+ 1 digit for temperature
equal to or higher than 0º C
+ 0.25% of instrument
range + 1 digit for
temperature
below 0º C
+0.25% of instrument range
+ 1 digit(B,R,S TYPE TC)
0.1C
(1C B,R,S
TYPE TC)
J
-200 t o 1200 C
K
-200 t o 1370 C
T
-200 t o 400C
B
450 t o 1800C
R
0 to 17 50C
S
0 to 17 50C
N
-200 to 1300° C
RTD
-199.9 to
850.0 C
+ 0 .1% of instrum ent
rang e + 1 digi t
0 t o 75mV
-1999 to 9999
+ 0.1% o f rang e + 1
digi t
1 C ount
0 t o 100mv
0.4 to 2V
0 t o 2V
0-20 mA*
4-20 mA*
0 t o 5V
1 t o 5V
0 t o 10V
-10 to
20mV
*For DC current input, 100 Ohms (0.1%, 25 ppm) shunt resistor must be connected
externally. For DC current and Voltage input, Scaling is possible and decimal point is
selectable.
Sampling Period: 100mSec for TC and Linear Input, 200mSec for RTD Input.
Resolution: 17-bit
Burnout detection: Functions for TC, RTD, linear input signal. (It detects whether
sensor is connected or not) ALL Relay output can be selected for Burnout Condition.
i.e. Open sensor Up scale or Down Scale
Measurement current (RTD): 1milli Ampere

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 9 of 42
Input Impedance: >1 Mohm for thermocouple/ mV/RTD/Volts inputs & 100
ohms for mAmp input.
Noise Rejection Ratio:
NMRR (Normal mode rejection ratio) > 40 dB (50/60 Hz) or more
CMRR (Common mode rejection ratio) > 120 dB (50/60 Hz) or more
Allowable wiring resistance for RTD: Maximum 15 ohms/wire (Conductor
resistance between three wires should be equal).
Retransmission Output:
Number of outputs: 1
Process Value, Set point, or Control output can be selected as a Retransmission
output.
Output signal: 0-20 mA, 4-20 mA, 0-5 V, 1-5 V or 0-10 V DC.
Voltage or current output can be selected through software and internal jumper
settings.
Load resistance: 500 ohms Max. Or less for current output. 3k or higher for voltage
output
Output accuracy: ±0.25% of Range
Relay Contact Outputs:
Number of outputs: 4
Output signal: Three terminals (NC, NO, and C)
Relay Contact rating: 250 V AC or 30 V DC, 2A (resistive load)
Operating/release time: <10 ms
Digital Contact Outputs:
Number of outputs: 8
Output Type: Open Collector
Output Contact rating: 24 V DC, 50mA (with inbuilt current limit protection)
Communication:
Communication Type: Half duplex/Asynchronous (RS-485)
Communication Protocol: MODBUS RTU
Baud rate, Parity and Stop bit are selectable form the key board.
All parameters are Configurable through MODBUS.
Connectable number of unit: 32
Communication error Detection: CRC Check
Display Specifications:
PV display: 4-digits, 7-segment, Red LEDs, character height of 0.56‟‟
Channel No. Display: 2-digits, 7-segment, Green LEDs, character height of 0.56‟
Relay Group Display: 1-digits, 7-segment, Red LEDs, character height of 0.56‟
Statu s indi cating l amps: 16-Red LEDs for Alarms status, 4-Red LEDs for Relay
status, 1-Red LED Manual mode status, 1-Red LED Fault status, 2-Green LEDS for
Communication.
Power Supply Specifications:
Power supply: Rated AC voltage of 85 to 260V AC at 50/60 Hz ( Rated Dc voltage
100 to 300VDC) / Rated voltage of 18 to 36V DC (Optional),

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 10 of 42
Power consumption: Max. 15 VA
Data backup: Non-volatile memory (can be written up to 100000 times)
Withstanding Voltage:
Between primary terminals* and secondary terminals** at
least 1500VAC for 1 minute
Between secondary terminals at least 600V AC for 1 minute
Insulation resistance: 20Mohms or more at 500V DC
*Prima ry termi nals i ndicat e powe r termin als and r elay out put t ermi nals
** Secon dary te rminal s indi cate anal og I/O si gnals, vol tage pul se
output , Conta ct input t erminal s , Rem ote input , RS 485 .
Signal Isolations Specifications:
PV input terminals(8 Channel input): Isolated from other input/output terminals.
Retransmission output terminals (voltage/current): Not isolated from current or
voltage outputs Isolated from other input/output terminals and internal circuit.
Relay contact control output terminals: Isolated between contact output terminals
and from other Input/output terminals and internal circuit.
Digital contact control output terminals: Isolated from other Input/output terminals
and internal circuit.
RS-485 Communication terminals: Isolated from other input/output terminals and
internal circuit
Power terminals: Isolated from other input/output terminals and internal circuit.
Construction, Installation, and Wiring:
Construction: Only the front panel is dust-proof
Material: ABS resin and Polycarbonate
Case color: Black
Weight: About 0.5 kg or less
Dimensions: 96 (W) x 96 (H) x 110 (depth from panel face) mm.
Installation: Panel-mounting type. With
Panel cutout dimensions: 92.5 + 0.8(W) x 92.5 + 0.8(H) mm
Environmental Conditions:
TEMPCO: FOR PV (Main input) less than 100ppm. FOR Retransmission less than
150ppm.
Humidity: 30% to 95% RH (Non-Condensing)
Instrument Warm-up Time: 30 minutes after power on
Ambient temperature: 0 to 55°C

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 11 of 42
4. Front and Back Panel Description:
FRONT PANEL
Name of Part
Function
Process Value
Display(DATA window)
Displays Process Value.
Display Parameter Name When You Set Parameter.
Displays Error Message When An Error Occurs.
Channel No. Display
(CHANNEL)
Displays Channel Number in run mode. Also it will display
relay number (01 –04) in set mode
Group No. Display
(GROUP)
Displays Group Number for Relay Mapping.
Relay Indicator LED
(RL1, RL2, RL3, & RL4)
When Respective Relay LED Lits (In Red).
Alarm1(AL1) Indicator
LEDs for Channel-1 to 8
When Alarm1 Occurs, Respective Alarm LED for
Channel-1 to 8 will Lit (In Red).
Alarm1(AL2) Indicator
LEDs for Channel-1 to 8
When Alarm2 Occurs, Respective Alarm LED for
Channel-1 to 8 will Lit (In Red).
Auto/Manual Indicator
LED (MAN)
If LED is on, it indicates Manual mode and if LED is off
Auto Mode.
Communication Indicator
LED(T1,R1 & T2,R2)
When Communication on, two LEDs blink.

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 12 of 42
BACK PLATE CONNECTION DETAIL:
1
2
3
4
5
6
7
8
9
10
11
12
C
NO
NC
C
NO
NC
25
26
29
30
28
27
31
32
33
34
35
36
R
L
3
C
NO
NC
NO
C
NC
R
L
1
R
L
2
R
L
4
-
+
DD
R S4 8 5
D
+
-
L/+
N/-
E
*100 Ohms 0.1%
RX
RX
13
14
15
mA
*
V
+
T/C
-
R TD
C H1
16
17
18
mA
*
V
+
T/C
-
R TD
C H2
19
20
21
mA
*
V
+
T/C
-
R TD
C H3
22
23
24
mA
*
V
+
T/C
-
R TD
C H4
37
38
39
mA
*
V
+
T/C
-
R TD
C H5
40
41
42
mA
*
V
+
T/C
-
R TD
C H6
43
44
45
mA
*
V
+
T/C
-
R TD
C H7
46
47
48
mA
*
V
+
T/C
-
R TD
C H8

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 13 of 42
RECOMMENDED TERMINAL LUGS DETAIL:
DIMENSIONS:-
Length (b)
16 mm
Width (a)
5.7 mm
Length of insulation sleeve (c)
4.5 mm
Inner dimension of the insulating collar (d)
1.9 mm
Inner diameter (f)
3.2 mm
Inner diameter (f)
0.75 mm

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 14 of 42
5. KEY FUNCTION Description:
MENU/ENTER KEY:
It is used to enter in the sub menu (various levels) and save the parameters to
nonvolatile memory, when user setting a proper data by Increment and shift key for
parameter configuration.
ESCAPE KEY:
It is used to come out from any sub menu (various levels) to the run mode.
INCREMENT KEY:
It is used to increment the parameter for selection. Value of parameter can be
incremented by pressing this key. When first time increment key pressed, DP
(decimal point) in SV display blink, so user can modify the value with increment key.
It is used to increment the value in particular digit. Value can be incremented from
0- 9 and from „9‟ again it rollovers to „0‟.
SHIFT KEY/DECREMENT KEY:
It is used to Shift the digit to set the parameter as describe in increment key when
DP (decimal point) started to blink. Menu key is used to go forward to show next
parameter and Shift key is used to go backward to show previous parameter. Also,
in Run mode Shift key is used to give Acknowledge for ALARM and TRIP.
AUTO/MANUAL KEY:
It is used to switch between auto to manual mode and manual to auto mode. During
manual mode Increment key is used to change channel number.

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 15 of 42
6. Menu Layout:
RUN TIME INDICATION:
Following parameters can view or change during run time.
Immediately after powering, unit will run in Auto Mode. In auto
mode channel will scan automatically according to scan time
selection (1-250 second).
Press A/M Key in run mode, Channel no scanning on display is
stopped. By pressing increment key, we can change channel
number manually.
Level –1:-
Pressing MENU key DATA window shows LVL1 (LvL1) message. Press MENU
key again PV Display shows pWd(PWD) message, press increment key
twice to select password and then press MENU key to enter into Level-1.
DATA window shows SP.1 (SP.1) message and by pressing increment key,
DATA window shows Set Point-1 Value Use Inc and shift key to modify
value. OR press MENU key again to change Set-point 1 for Channel 2.
ESCAPE KEY will use to come out SP.1
LEVEL 1
Parameter
(DATA window)
Setti ng na me and
desc ription
Defaul t
value
Show s
only if
Symbol
Name
(PWD)
Level -1 Passw ord
0 t o 9999
0000
-
(SP.1)
Target S et point -1
SetPoi nt-1 for Chan nel
1 t o 8 .
0100 (for
all 8
channel )
-
(SP.2)
Target S et point -2
SetPoi nt-2 for Chan nel
1 t o 8 .
0200(f or
all 8
channel )
Relay
group is
select ed
2
(HYS)
Hystre sis
Hystre sis for Chann el 1
to 8.
00 02(f or
all 8
channel )
-

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 16 of 42
LEVEL 2:-
Pressing MENU key DATA window shows LvL2(LvL2) message. Press MENU
key again DATA window shows pwd (PWD) message, press increment key
twice to select password and then press MENU key to enter into Level-2.
Following parameters can be configured in LEVEL –2.
LEVEL 2:
Param eter
(DATA Win dow)
Setti ng na me and
desc ription
Defaul t
value
Show s
only if
Symbol
Name
(PWD)
Level -2
Passw ord
0 t o 9999
0000
-
(inP.t)
PV Input Typ e
(E, J, K , T Etc.)
Foll ow T able 3(In put
type fo r 1-8 cha nnel)
K-TC(for
all 8
channel )
-
(PV.HI)
Proce ss val ue
rang e hig h
setti ng
(PV high > PV
low)
Range of the sensor
/-199 9 to 9 999
(for linea r i nput
types) (1-8 Chann el)
1370(f or
all 8
channel )
-
(PV.LO)
Proce ss val ue
rang e low er
settin g
Range of the sensor
/-199 9 to 9999
(for linea r i nput
types) (1-8 Chann el)
-200(f or
all 8
channel )
-
(dP)
Decimal P oint
Setti ng Only
appli cable for
Linear inp ut t ype
i s s el e ct e d
0 to 3 (1 –8
Chann el)
0(for al l 8
channel )
-
(rL.LG)
Relay /OC
Logic(Appli cable
for 4-RE LAY)
nrml / flsf
0:Nora ml
1:Fail Saf e
Normal (for
all 4
Relay)
-
(rL.Fn)
Relay /OC
F un cti on ( Ap pl i ca
ble for 4-R ELAY)
ALRM / TRiP
0:ALAR M
1:TRIP
Alarm( for
all 4
Relay)
-
(rL.dL)
Relay /OC
Delay( Applicable
for 4-RE LAY)
1 t o 99 seconds
1
secon d(for
all 4
Relay)
-
(rL.o.S)
Relay /OC Open
sensor (Appli cable
for 4-RE LAY)
up / DoWn
0:DOWN
1:UP
Up
S ca l e(fo r
all 4
Relay)
-
(rl.mp)
Relay /OC
mapping
(Appl icable f or 1
-8 Chann el)
See Relay
Config uration
Refer
Note:1
-
(rl.tp)
Relay /OC Group
Type
See Relay
Config uration
Refer
Note:2
-

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 17 of 42
Relay Configuration:
Relay configuration depends on selection of Relay group i.e. Relay
group 2 or Relay group 4 in Level-3.
Relay Group - 2:
If relay group –2 is selected, there will be two group of relay. Each group has two
relay. (G-1 and G-2).
G-1 means RELAY 1 and RELAY 3
G-2 means RELAY 2 and RELAY 4
Example:
Note:
1) Both Groups can not be selected for single Channel.
2) None means no group is selected for particular channel.
Relay/OC Type can be selected as shown below:
Relay Group - 4:
If relay group –4 is selected, there will be four group of relay. Each group has one
relay. (G-1, G-2, G-3 and G-4).
G-1 means RELAY 1
G-2 means RELAY 2
G-3 means RELAY 3
G-4 means RELAY 4
Example:
CHANNEL NO
NONE
G-1
G-2
G-3
G-4
1
2
3
4
5
6
7
8
Note:
1) More than one Group can not be selected for single Channel.
2) None means no group is selected for particular Channel.
CHANNEL NO
NONE
G-1
G-2
1
2
3
4
5
6
7
8
Relay Group
Relay Type
G –1
High/ Very High (H-VH) or
Very Low /Low (VL-L) or
Low/High (L-H)
G –2
High/ Very High (H-VH) or
Very Low /Low (VL-L) or
Low/High (L-H)

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 18 of 42
Relay Type can be selected as shown below:
For relay functionality Refer Relay outputs (Chapter –7).
LEVEL –3:
Pressing MENU key DATA window shows LvL3(LvL3) message. Press MENU key
again DATA window shows pwd (PWD) message, press increment key twice to select
password and then press MENU key to enter into Level-3.Following parameters can
be configured in LEVEL –3.
LEVEL 3:
Parameter
(DATA Window)
Setti ng na me and
desc ription
Defaul t
value
Show s
only if
Symbol
Name
(PWD)
Level -3
Passw ord
0 t o 9999
0000
-
(skip)
Chann el
skip/Un skip
selecti on.
yes / no
0:NO
1:YES
0(for all 8
channel
-
(rL.LH)
Relay /OC Latch
on / off
0:OFF
1:ON
0
-
(rL.GP)
Relay /OC Group
RGP.4/ rGP.2
0:Rel ay Group-4
1:Rel ay Group-2
1
-
(SCAn)
Scan Time
1 t o 250 second s
1
-
A.CJC
(A.CJC)
Auto cold
juncti on(Onl y
appli cable fo r TC
inpu t ty pe
yes / no
0:NO
1:YES
1
-
F.CJC
(F.CJC)
Fix cold
juncti on(Onl y
appli cable fo r TC
inpu t ty pe
0.0 to 60.0 D eg C
0.0 Deg C
-
Sr.no
(Sr.no)
Unit ID
1 t o 247
1
-
(Baud)
Communi cati on
Baud rate
9600 /1 9 . 2 K
0:(960 0) –9600 bps
1:(19.2K ) –19.2 Kb ps
19.2k bps
(Pr.St)
Parity/S top bit
selecti on
p.n.S.1 /P.nS.2 /P.o.s1
/ P.ES.1
0:(P. N.S.1) -parity
No p arit y
/Stop bit
- 2
Relay Group
Relay Type
G - 1
Low ON (L) or High ON (H)
G - 2
Low ON (L) or High ON (H)
G - 3
Low ON (L) or High ON (H)
G - 4
Low ON (L) or High ON (H)

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 19 of 42
none- stop bit-1
1:(P. N.S.2) -parit y
none - stop bit-2
2:(P. O.S.1) -pari ty odd
-stop bit -1
3:(P. E.S.1)- pari ty
even - stop bit- 1
(t.out)
Timeout for
displ ay back to
Run Mode
10 t o 100 Second s
60
-
(rt.o.s)*
Retras missi on
Open sens or
up / DoWn
0:DOWN
1:UP
1
-
(rt.tp)*
Retran smissi on
Output Typ e
0-20/4-20/0-5v/1-5v/
0-10v
0:(0-2 0) –0-20mA
1:(4-2 0) –4-20mA
2:(0 - 5) –0 –5 vol t
3:(1 - 5) –1 –5 vol t
4:(0 –10) - 0 -1 0volt
1
-
(rt.dr)*
Retran smissi on
directi on
Dir / rev
1:(di r)
0: ( rev)
1
-
(rt.CH)*
Retran smissi on
Chann el
1 t o 8 cha nnel
1
-
(rt.rd)*
Retran smissi on
Chann el V alue
MAx / MIn
1:(Max)
0: ( Min )
1
-
(S.PWD)
Passw ord
Set pass word to
lock sele cted
level
0 t o 9999
0
-
NOTE:- When Digital Output is use * Parameter is not applicable.
Calib ration: -
Pressing MENU key, DATA window shows CAL (CAL) message. Press MENU key again,
DATA window shows pwd (PWD) message, press increment key twice to select
password and then press MENU key to enter into Calibration.
Calib ration:
Parameter
(DATA Window)
Setti ng na me and
desc ription
Defaul t
value
Show s onl y
if
Symbol
Name
(PWD)
Passw ord
0 t o 9999
0000
-
(Amb)
Ambient
Ambient ad justm en t
-
-

8-CHANNEL SCANNER-8208
REF NO: m82A/om/101
masibus
Issue NO: 08
User‟s Manual Page 20 of 42
(CAL.Z)
Therm ocoupl e,
Rtd and Linea r
Zero
Cali btriaon
Dependi ng on PV
sensor t ype sel ect ed
-
-
(CAL.S)
Therm ocoupl e,
Rtd and Linea r
Span
Cali btriaon
Depend ing on PV
sensor t ype sel ect ed
-
-
(rtr.Z)
Retran smissi on
voltag e and
current Z ero
cali bration
Dependi ng on
Retras missi on type
select ed
-
-
(rtr.S)
Retran smissi on
voltag e and
current Sp an
cali bration
Dependi ng on
Retras missi on type
select ed
-
-
Facto ry Re set P aramet ers:
Pressi ng ME NU key , DATA wi ndow show s F.RST (F.rST) m essage . Press
MENU k ey again , DATA window sho ws p w d (PWD) me ssage, press
Incre ment k ey tw ice to s elect pas swor d and th en pr es s MENU ke y to
ent er i nt o F act ory R e set .
F ac t ory R es et M od e :
Parameter
(DATA window)
Setti ng na me and
desc ription
Defaul t
value
Show s onl y
if
Symbol
Name
(Pwd)
Passw ord
0 to 99 99
-
-
(L.dEF)
LOAD Defau lt
CAL\P A R A\a l l
(CAL)\ (PARA) \(AL L)
CAL- Only cal ibrati on
set to defaul t val ue
PARA- Al l param et ers
excludi ng calib ration
will set to default
value
ALL- Calibrati on and
paramet ers will set to
defaul t val ue
-
-
Table of contents
Popular Scanner manuals by other brands

Blackmagicdesign
Blackmagicdesign cintel Installation and operation manual

caenrfid
caenrfid R1210I Technical information manual

Compaq
Compaq S4 100 owner's guide

Silvercrest
Silvercrest 307324 operating instructions

Bin Master
Bin Master 3DLevelScanner Quick installation guide

Microtek
Microtek ScanMaker 4700 install guide