FLEXIBLE AXIS METER (FAM) Installation Guide
Master Meter, Inc.
|
101 Regency Parkway, Mansfield, TX 76063
|
©2020 Master Meter, Inc. All rights reserved. Master Meter reserves the right to make modifications to the products described herein at any time and without notice.
3.
The installation should be leak-tight, with properly sized gaskets. When meter couplings are
ordered from Master Meter, gaskets are provided. Appropriate gaskets and couplings are
also available from qualified waterworks distributors. Whenever a meter is pulled from the
line, discard and replace old gaskets.
4.
The Flexible Axis Meter can be installed using either meter couplings or solder-joint
connections. When soldering, take care not to apply heat to the polymer components of
the meter. Any resulting damage will not be covered under warranty.
5.
Although AWWA opposes the grounding of electrical systems to potable water delivery
lines, such practices do exist. To prevent accidental harm to service personnel and
residents, make certain that an electrical grounding strap is installed around the meter.
AT THE TIME OF THE INSTALLATION
The FAM Flow Tube will be shipped with either a Plug or Measuring Element in Place. The
Plug allows full flow through the tube for system pressure testing and line flushing. If the plug
is in place when received, do not remove it until the Measuring Unit is to be installed (after
pressure testing and line flushing). Removing the plug can damage the o-ring seal, causing
leaks to occur. A new set of o-rings is shipped with the FAM Measuring Unit, for use when the
Measuring Unit is connected to the Flow Tube.