Maxsys PC4164-NB User manual

Table of Contents
Section 1: Introduction 3
1.1 Before You Begin ......................................................................................... 3
1.2 How to Use This Manual ........................................................................... 4
1.3 PC4164-NB Specifications .......................................................................... 5
1.4 Wireless Devices .......................................................................................... 5
Section 2: Getting Started 6
2.1 Unpack the PC4164-NB .............................................................................. 6
2.2 Find a Mounting Location for the PC4164-NB ....................................... 6
2.3 Connecting the PC4164-NB ....................................................................... 7
2.4 Enroll the PC4164-NB ................................................................................. 8
Section 3: Enroll & Program Wireless Devices 9
3.1 A Note about Electronic Serial Numbers (ESN) ..................................... 9
3.2 Enroll Wireless Devices using Zones (WLS904-NB and WLS907-NB) 9
3.3 Enroll and Program Wireless Keys (WLS909-NB) ............................... 10
Section 4: Testing & Mounting Devices 12
4.1 Test the Placement of WLS904-NB and WLS907-NB Devices ............ 12
4.2 Test WLS909-NB Reception ..................................................................... 13
4.3 Mount the PC4164-NB and Wireless Devices ....................................... 13
Section 5: Deleting & Replacing Devices 14
5.1 Replacing Devices ..................................................................................... 14
5.2 Deleting Devices ........................................................................................ 15
5.3 Erasing Device Serial Numbers .............................................................. 15
Section 6: Additional Programming Notes 16
6.1 Device Supervision ................................................................................... 16
6.2 Trouble Conditions.................................................................................... 17
Section 7: Troubleshooting 19
Programming Worksheets 20
Index 23
Limited Warranty 24
firealarmresources.com

WARNING Please Read Carefully
Note to Installers
This warning contains vital information. As the only individual in
contact with system users, it is your responsibility to bring each
item in this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as effective as
possible. There are circumstances, however, involving fire,
burglary, or other types of emergencies where it may not pro-
vide protection. Any alarm system of any type may be com-
promised deliberately or may fail to operate as expected for a
variety of reasons. Some but not all of these reasons may be:
nInadequate Installation
A security system must be installed properly in order to pro-
vide adequate protection. Every installation should be evalu-
ated by a security professional to ensure that all access points
and areas are covered. Locks and latches on windows and doors
must be secure and operate as intended. Windows, doors, walls,
ceilings and other building materials must be of sufficient
strength and construction to provide the level of protection ex-
pected. A reevaluation must be done during and after any con-
struction activity. An evaluation by the fire and/or police de-
partment is highly recommended if this service is available.
nCriminal Knowledge
This system contains security features which were known to
be effective at the time of manufacture. It is possible for per-
sons with criminal intent to develop techniques which reduce
the effectiveness of these features. It is important that a secu-
rity system be reviewed periodically to ensure that its features
remain effective and that it be updated or replaced if it is found
that it does not provide the protection expected.
nAccess by Intruders
Intruders may enter through an unprotected access point, cir-
cumvent a sensing device, evade detection by moving through
an area of insufficient coverage, disconnect a warning device,
or interfere with or prevent the proper operation of the system.
nPow er Failure
Control units, intrusion detectors, smoke detectors and many
other security devices require an adequate power supply for
proper operation. If a device operates from batteries, it is pos-
sible for the batteries to fail. Even if the batteries have not
failed, they must be charged, in good condition and installed
correctly. If a device operates only by AC power, any interrup-
tion, however brief, will render that device inoperative while it
does not have power. Power interruptions of any length are
often accompanied by voltage fluctuations which may damage
electronic equipment such as a security system. After a power
interruption has occurred, immediately conduct a complete
system test to ensure that the system operates as intended.
nFailure of Replaceable Batteries
This system’s wireless transmitters have been designed to pro-
vide several years of battery life under normal conditions. The
expected battery life is a function of the device environment,
usage and type. Ambient conditions such as high humidity,
high or low temperatures, or large temperature fluctuations may
reduce the expected battery life. While each transmitting de-
vice has a low battery monitor which identifies when the bat-
teries need to be replaced, this monitor may fail to operate as
expected. Regular testing and maintenance will keep the sys-
tem in good operating condition.
nCompromise of Radio Frequency
( Wi reless) Devices
Signals may not reach the receiver under all circumstances which
could include metal objects placed on or near the radio path or
deliberate jamming or other inadvertent radio signal interference.
nSystem Users
A user may not be able to operate a panic or emergency switch
possibly due to permanent or temporary physical disability,
inability to reach the device in time, or unfamiliarity with the
correct operation. It is important that all system users be trained
in the correct operation of the alarm system and that they know
how to respond when the system indicates an alarm.
nSmoke Detectors
Smoke detectors that are a part of this system may not properly
alert occupants of a fire for a number of reasons, some of which
follow. The smoke detectors may have been improperly installed
or positioned. Smoke may not be able to reach the smoke detec-
tors, such as when the fire is in a chimney, walls or roofs, or on
the other side of closed doors. Smoke detectors may not detect
smoke from fires on another level of the residence or building.
Every fire is different in the amount of smoke produced and
the rate of burning. Smoke detectors cannot sense all types of
fires equally well. Smoke detectors may not provide timely
warning of fires caused by carelessness or safety hazards such
as smoking in bed, violent explosions, escaping gas, improper
storage of flammable materials, overloaded electrical circuits,
children playing with matches or arson.
Even if the smoke detector operates as intended, there may be
circumstances when there is insufficient warning to allow all
occupants to escape in time to avoid injury or death.
nMotion Detectors
Motion detectors can only detect motion within the designated
areas as shown in their respective installation instructions. They
cannot discriminate between intruders and intended occupants.
Motion detectors do not provide volumetric area protection.
They have multiple beams of detection and motion can only be
detected in unobstructed areas covered by these beams. They
cannot detect motion which occurs behind walls, ceilings, floor,
closed doors, glass partitions, glass doors or windows. Any
type of tampering whether intentional or unintentional such as
masking, painting, or spraying of any material on the lenses,
mirrors, windows or any other part of the detection system
will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in
temperature. However their effectiveness can be reduced when
the ambient temperature rises near or above body temperature
or if there are intentional or unintentional sources of heat in or
near the detection area. Some of these heat sources could be
heaters, radiators, stoves, barbeques, fireplaces, sunlight, steam
vents, lighting and so on.
nWarning Devices
Warning devices such as sirens, bells, horns, or strobes may
not warn people or waken someone sleeping if there is an in-
tervening wall or door. If warning devices are located on a
different level of the residence or premise, then it is less likely
that the occupants will be alerted or awakened. Audible warn-
ing devices may be interfered with by other noise sources such
as stereos, radios, televisions, air conditioners or other appli-
ances, or passing traffic. Audible warning devices, however
loud, may not be heard by a hearing-impaired person.
nTelephone Lines
If telephone lines are used to transmit alarms, they may be out of
service or busy for certain periods of time. Also an intruder may
cut the telephone line or defeat its operation by more sophisti-
cated means which may be difficult to detect.
nInsufficient Ti m e
There may be circumstances when the system will operate as
intended, yet the occupants will not be protected from the emer-
gency due to their inability to respond to the warnings in a
timely manner. If the system is monitored, the response may
not occur in time to protect the occupants or their belongings.
nComponent Failure
Although every effort has been made to make this system as
reliable as possible, the system may fail to function as intended
due to the failure of a component.
nInadequate Testing
Most problems that would prevent an alarm system from operat-
ing as intended can be found by regular testing and maintenance.
The complete system should be tested weekly and immediately
after a break-in, an attempted break-in, a fire, a storm, an earth-
quake, an accident, or any kind of construction activity inside or
outside the premises. The testing should include all sensing de-
vices, keypads, consoles, alarm indicating devices and any other
operational devices that are part of the system.
nSecurity and Insurance
Regardless of its capabilities, an alarm system is not a substitute for
property or life insurance. An alarm system also is not a substitute
for property owners, renters, or other occupants to act prudently to
prevent or minimize the harmful effects of an emergency situation.
firealarmresources.com

3
The PC4164-NB is a wireless signal receiver for use with Maxsys PC4010 and PC4020
v3.0 panels. The PC4164-NB receives signals from WLS9XX wireless devices.
New features of the PC4164-NB v2.0:
•Identification of Wireless Keys (WLS909-NB): Wireless keys 1 to 16 can be
identified as user numbers 0101 to 0116 (respectively) for identified openings/
closings and command output activation. For more information regarding this
feature, see Section 3.3 “Enroll and Program Wireless Keys.”
•6 digit serial numbers for all wireless devices: These new serial numbers
include hexadecimal digits. Please read Section 3.1 “A note on Electronic
Serial Numbers (ESN)” for more information on enrolling older 5-digit and
newer 6-digit devices.
1.1 Before You Begin
This manual describes how to install, program and maintain the PC4164-NB on a
PC4010/4020 Security System. You should have completed the following steps in
your PC4010/4020 installation, before you install the PC4164-NB module:
1. Plan the installation and wiring of the PC4010/4020 system (see PC4010/4020
Installation Manual, Section 2: Installation and Wiring)
2. Install the control panel, and install and enroll at least one keypad to use for
programming (see PC4010/4020 Installation Manual, Section 3: How to Program)
3. Install and enroll any hardwired zone expander modules (PC4108Aor PC4116)
you plan to use (see PC4010/4020 Installation Manual, Section 4: Module
Enrollment).
You can program the PC4164-NB from a PC4010/4020 system LCD keypad or using
downloading software on a remote computer. Read your system Installation Manual,
section 3 “How to Program” for more information.
S E C T I O N 1
Introduction
firealarmresources.com

4
1.2 How to Use This Manual
To install and set up the PC4164-NB and wireless devices, follow these steps:
1. Enroll and temporarily mount the PC4164-NB module (see Section 2)
2. Enroll and program wireless devices using zones, wireless keys and handheld
keypads (see Section 3)
3. Complete zone and other programming on the system (see Sections 4 and 5)
4. Test the placement of all the wireless devices (see Section 6)
5. Permanently mount the PC4164-NB receiver and wireless devices (see Section
6)
To replace or delete wireless devices already enrolled, see Section 4.
For additional information on wireless motion detectors and wireless keys, see
Sections 7 and 8.
For help with troubleshooting, see Section 9.
Record the zone or slot and serial numbers of all wireless devices, and other
programming in the Programming Worksheets section at the end of the manual.
PC4010/4020 Programming
All programming sections in this manual are referred to by reference number. A
detailed description of PC4010/4020 programming is in the PC4010/4020
Installation Manual, section 3 “How to Program.”
To program using reference numbers, enter Installer’s programming
([*][8][Installer’s Code]). Press and hold the [A]uxiliary key until the keypad
displays the following message:
“Enter Ref # then *.”
Enter the reference number found in the programming Worksheets for the section
you wish to program, then press the [*] key. The display will immediately go to the
programming item you have selected.
I N T R O D U C T I O N
firealarmresources.com

5
1.3 PC4164-NB Specifications
• One PC4164-NB receiver may be installed per PC4010/4020 system
• Nominal current draw of 80mA
• Frequency: 434 MHz
• Receives signals from up to 56 wireless zones on a PC4010 v3.0 and later, and
up to 64 wireless zones on a PC4020 v3.0 and later
• Antenna - diversity design for enhanced performance
• Programmable supervisory window, 01:00 to 23:59
• Location
- can be wired up to 750 ft. / 230 m from the main panel with 22 gauge wire
- connects to Combus
- for longer wire runs, thicker gauge wire must be used.
1.4 Wireless Devices
Please refer to the Installation Instruction sheets of the following devices for more
information.
The PC4164-NB v2.0 can receive signals from the following devices:
This unit is listed as a single or multiple station smoke detector accessory.
• WLS904-NB Motion Detector
• WLS907-NB Universal Transmitter
• WLS909-NB Wireless Key (up to 16)
Batteries
The wireless devices are designed to use Eveready Alkaline Energizer batteries
only.
NOTE: Do not use other brands of batteries. Using any other brand voids any approvals
and may affect the system operation.
I N T R O D U C T I O N
firealarmresources.com

6
S E C T I O N 2
This section describes how to set up and enroll the PC4164-NB module.
2.1 Unpack the PC4164-NB
Check that the following parts are in your PC4164-NB package:
• PC4164-NB PCB
• PC4164-NB plastic cabinet
• 2 antennas
2.2 Find a Mounting Location for the PC4164-NB
NOTE: Do not permanently mount the PC4164-NB now. Mount the PC4164-NB receiver
after you have done placement tests with all the wireless devices (see sections 4.1
and 4.2).
Find a place that is:
• Dry
• Central to the proposed placement of all wireless devices
• As high as possible
• Far from sources of interference, including: electrical noise such as computers,
televisions and electric motors in appliances and heating and air conditioning
units; large metal objects like heating ducts and plumbing which may shield
the antenna.
Make sure that electrical wires will not run over the antenna(s) of the module when
it is mounted.
When mounting the PC4164-NB in a basement, place the module as high and as
close to the underside of the first floor as possible. The range of the module will be
smaller if the unit is mounted below ground level.
Getting Started
firealarmresources.com

7
G E T T I N G S T A R T E D
Diagram 1
2.3 Connecting the PC4164-NB
The PC4164-NB is connected to the control panel via the Combus.
CAUTION: Remove all power from the panel while connecting modules to the Combus.
Wire the PC4164-NB to the Combus of the PC4010/PC4020 according to diagram 1:
firealarmresources.com

8
2.4 Enroll the PC4164-NB
You must enroll the PC4164-NB module with the PC4010/4020 panel, before you
can install and program the WLS9XX devices. The PC4164-NB will reserve up to 56
zones on a PC4010 and up to 64 zones on a PC4020 for wireless use.
To make sure you have enough space for hardwire zones, you should enroll the
PC4164-NB after you have enrolled all the hardwire zone expander modules. For
example, if you enroll the PC4164-NB first on a PC4020, it would use up zones 17
to 80, leaving only 48 spots left for hardwire zone expander modules.
NOTE: You cannot have more than 64 zones on the PC4010 and 128 zones on the
PC4020. If the total number of zones theoretically available on the zone expanders
exceeds the maximum for the panel, you will not be able to use the extra zones.
A description of how to enroll keypads and modules is in your PC4010/4020
Installation Manual, section 4: Module Enrollment.
Follow these steps to enroll your PC4164-NB module.
1. At a PC4010/4020 system LCD keypad, enter [*][8][Installer’s code] to go to
the Installer’s Programming section.
2. Enter Ref #[0200], to go to the Enroll Module section.
3 Scroll to PC41XX Zn. Ex., press [*]. The LCD keypad will display
Create Tamper on Desired Unit.
4. Tamper the PC4164-NB:
i) makesure theconnection betweenthe T1and T2tamper terminalsis closed
(tamper zone secured) (see Diagram 1).
ii) openthe normally closed contact, ifpresent, orremove thewiring fromone
of the tamper terminals (tamper zone violated). The change from secure to
violated will enroll the module.
The LCD keypad will display PC4164-NB Zn. Ex. Mod XX Enrolled.
5. When the module is enrolled, re-secure the connection between the T1 and T2
terminals.
6. Press [#]. The LCD keypad will display Zones XXX - XXX. Record the zone
number range for the module in the worksheets.
7. To exit module enrollment, press [#].
The PC4164-NB module is now installed and enrolled on the PC4010/4020 system. You
can now enroll and program the wireless devices. How to do this is described in Section 3.
G E T T I N G S T A R T E D
firealarmresources.com

9
This section describes how to enroll and program:
• wireless devices using zones (WLS904-NB and WLS907-NB)
• wireless keys (WLS909-NB)
For more information on these devices, read the instruction sheet included with
each device.
3.1 A Note about Electronic Serial Numbers (ESN)
In order to reduce the occurrence of wireless devices with the same serial number,
6-digit serial numbers are now printed on the back of each wireless device. The 6-
digit serial numbers include hexadecimal digits. For instructions on programming
hexadecimal numbers, see your PC4010/4020 Installation manual, section 3: How to
Program.
Older wireless devices will only have 5-digit serial numbers. To enroll these devices,
enter [0], then the 5-digit serial number.
3.2 Enroll Wireless Devices using Zones (WLS904-NB and
WLS907-NB)
NOTE: Before you permanently mount wireless devices, test each one in its intended
mounting location to make sure that it can communicate properly with the PC4164-NB.
Test the device 2-3 times. See Section 4.1 for more information.
1. At a system LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001300] to go to the Enroll Device programming section.
This section will only be available if you have enrolled the PC4164-NB with the
panel (see Section 2.5).
The LCD keypad will display Enroll Device Serial # [ ].
3. Look at the back of the first wireless device you want to enroll. If the device has
a 6-digit serial number, enter it now. If the device only has a 5-digit number,
enter a [0] and then the 5-digit number.
4. The LCD keypad will briefly show Enroll Device Zone XXX, where XXX = the
zone number the device is assigned to on the control panel.
Record the serial number and assigned zone number in the programming
worksheets in the back of this manual.
5. The LCD keypad will display Enroll Device Serial # [ ]. Continue with steps
3 – 4 until all devices have been enrolled.
6. To exit device enrollment, press [#].
S E C T I O N 3
Enroll & Program Wireless Devices
firealarmresources.com

10
Program Partitions and Zones
Now that you have enrolled and mounted the wireless devices, you should program
your PC4010/4020 partitions and zones. See your PC4010/4020 Installation Manual,
section 5: Partitions and Zones.
3.3 Enroll and Program Wireless Keys (WLS909-NB)
For wireless keys to work on the system, you need to enroll them and then program
the function buttons. You can enroll up to 16 wireless keys on the PC4164-NB.
Step 1: Enroll Wireless keys
1. At a PC4010/4020 system LCD keypad, enter [*][8][Installer’s code] to go to
the Installer’s Programming section.
2. Enter Ref #[001300], to go to the Enroll Device programming section. This
section will only be available if you have enrolled the PC4164-NB with the
panel (see Section 2.6). The LCD keypad will display
Enroll Device Serial # [ ].
3. Look at the back of the wireless key. If it has a 6-digit serial number, enter it
now. If it only has a 5-digit number, enter a [0] and then the 5-digit number.
4. The display will show Enroll Device WKEY #XX, where XX = the Wkey slot to
which the WLS909-NB is assigned (01 to 16).
5. Record the serial number and assigned slot number in the programming
worksheets in the back of this manual.
6. Continue with steps 3 – 5 until all wireless keys have been enrolled.
Wireless Key Reporting
When you enroll a wireless key, the panel will assign a user number (0101 to 0116)
to the key. The wireless key enrolled in slot 01 will be given user number 0101, slot
02 will have user number 0102, and so on. This allows the panel to transmit and
log the arm/disarm events performed by each wireless key.
You can still program access codes for user numbers 0101 to 0116.
For example:
User 0101 arms or disarms using an access code - the panel transmits and logs
Closing/Opening User 0101.
A user arms or disarms using wireless key 01 - the panel transmits Closing/Opening
User 0101 and logs Closing/Opening User 0101 AND Closing/Opening WKey #01.
I N S T A L L I N G W I R E L E S S D E V I C E S
firealarmresources.com

11
Step 2: Program the WLS909-NB Function Buttons
WLS909-NB wireless keys have four programmable function buttons. When you
press and hold a button for two seconds, the programmed function will be executed.
Each function button can be assigned to one partition.
NOTE: Wireless key function buttons will not work when the partition(s) they are
assigned to are being accessed for zone bypassing or programming.
1. From Installer’s Programming, enter Ref #[001304], to go toWLSKey Functions.
2. Scroll to the slot number of the key you want to program (01-16). Press [*].
3. Scroll to the number of the button you want to program (1-4). Press [*].
4. Enter the 2-digit number of the function you want to select, or scroll to the
function you want to assign to that button and press [*]. The following functions
may be programmed:
00 Null Key 07 Arm Interior
01 Stay Arm 08-15 [*][7] Command Outputs 1-8
02 Away Arm 16 Fire Alarm
03 No-Entry Arm 17 Auxiliary Alarm
04 Chime On/Off 18 Panic Alarm
05 System Test 19 Disarm (Off)
06 Quick Exit
NOTE: If programmed, these options do not require access code entry regardless of
other system options. The programmed function will be executed immediately.
5. The LCD keypad will show Select (01) Partition 1. Scroll to the partition you
want the button to work in, and press [*] to select.
6. Repeat steps 3 to 5 until all the buttons are programmed.
7. Repeat steps 4 to 6 until all the wireless keys are programmed.
8. To exit, press [#].
NOTE: When a Wireless Key is used to disarm a partition, all courtesy pulse outputs
enabled for that partition will activate for two minutes.
Now that you have enrolled and programmed all the wireless devices, you will need to
test the devices and mount wireless devices using zones. See section 4 for more
information.
I N S T A L L I N G W I R E L E S S D E V I C E S
firealarmresources.com

12
You should test each device you have enrolled to ensure good signal strength
between the devices and the PC4164-NB. Follow the instructions in this section to
test wireless devices which use zones, wireless keys and handheld keypads.
If several wireless devices produce BAD test results, you may need to move the
PC4164-NB to a better location. (See section 2.3 for tips on finding a location for the
PC4164-NB.)
4.1 Test the Placement of WLS904-NB and WLS907-NB Devices
It is very important to test each wireless device before it is mounted. Following
these steps will test the placement of WLS904-NB and WLS907-NB wireless devices,
based on the signal strength between the PC4164-NB and the device:
NOTE: You cannot test the Wireless Key (WLS909-NB) in this mode. See section 4.2
for instructions on testing this device.
1. Temporarily place the device in its intended mounting location.
2. At a system LCD keypad, enter [*][8][Installer’s code].
3. Enter Ref # [001303] to go to the Device Test section.
4. Enter [00] to have test results sounded on the keypad buzzers only. Enter [01]
to have test results sounded by the system bells, as well as the keypad buzzers.
5. Use the [<][>] keys to scroll to the device and press [*] to select it. The keypad
will display Activate Device.
6. Activate the device being tested. A result will be displayed on the keypad or
sounded by the keypad or bell.
WLS904-NB: Remove the detector from its backplate, wait for 5 seconds, then
reattach the detector to its backplate.
WLS907-NB: Open and close the contact by moving the magnet away from the
unit. If the unit is attached to a door or a window, open and close the door or
window to activate the device.
7. Read the test results:
Placement LCD Keypad Display Keypad Buzzer/ Bells
Good Good 1 Beep/squawk
Fair Fair 2 Beeps/squawks
Bad Bad 3 Beeps/squawks
Activate the device until you get 3 good or fair results in a row. Wait 10 seconds
between each test on the same device. You may mount wireless devices where
results were good or fair.
S E C T I O N 4
Testing & Mounting Devices
firealarmresources.com

13
Devices indicating a bad result must be moved to another location. You may
only have to move the device a few inches to correct a bad result.
NOTE: Do not mount any device where a “bad” test result was indicated.
If several wireless devices produce BAD test results, you may need to move the
PC4164-NB to a better location. (See section 2.3 for tips on finding a location for
the PC4164-NB.)
8. To test another device, press [#] once, then repeat steps 4 - 7. Continue to test
the devices until both the PC4164-NB and the devices are in good or fair
locations.
9. To exit installer programming, press [#].
4.2 Test WLS909-NB Reception
The wireless key (WLS909-NB) cannot be tested using the module placement test
described above. To ensure that the PC4164-NB is receiving transmissions from
these devices, conduct the following tests:
Use the function keys to arm and disarm the system at several different points in
the installation.
NOTE: Do not use a Fire, Auxiliary or Panic key to test your WLS909-NB as pressing
these buttons will always notify your central station of a non-medical emergency.
If these devices do not operate from all points in the installation, you will need to
move the PC4164-NB receiver. Moving the PC4164-NB higher will usually improve
the reception.
If you move the PC4164-NB, repeat the tests described in sections 4.1 and 4.2 on all
the wireless devices. Continue to test the devices until you have found locations
with good or fair placement results for the PC4164-NB and the WLS904-NB and
WLS907-NB devices, and there is acceptable range between the PC4164-NB and
the WLS909-NB devices.
4.3 Mount the PC4164-NB and Wireless Devices
Do not permanently mount the PC4164-NB until you have tested reception with all
the wireless devices (see sections 4.1 and 4.2). Once you have done this and have a
good location, mount the PC4164-NB:
1. Remove the four screws that attach the PC4164-NB to the plastic cabinet.
2. Pull the Combus wires through the hole at the back of the cabinet.
3. Mount the cabinet securely to the wall.
4. Reattach the PC4164-NB to the mounted cabinet using the four mounting screws.
Mount the WLS904-NB and WLS907-NB Devices
If you have conducted the placement test described in section 4.1 and got 3 “Good”
or “Fair” results in a row for each device, you can mount the wireless devices. See
the Installation sheet for each device for mounting instructions.
T E S T I N G & M O U N T I N G D E V I C E S
firealarmresources.com

14
If a device is not working, or you need to change the setup of the system, you may
need to replace or delete wireless devices. Follow the appropriate procedure in this
section.
5.1 Replacing Devices
Wireless devices are divided into the following classes:
Class Model
2 WLS907-NB
3 WLS904-NB
6 & 9 WLS909-NB
This section describes how to replace one device with another device of the same
class. All programming that was used with the old device will be used with the
new device. For example, a WLS907-NB can be replaced with a WLS907-NB.
1. At a system LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001302] to go to the Replace Device section. The LCD keypad will
display
Serial # [ ] and either
Zone XXX, Wkey# XX or HHK# XX
3. Use the [<][>] keys to scroll to the device to be deleted, then press [*]. The LCD
keypad will display
With Device
Serial# [ ].
4. Enter the serial number of the new device. The LCD keypad will display Device
Replaced Serial # [ ] Zone XXX
NOTE: You cannot replace devices of different classes. (For example, a motion detector
cannot be replaced by a universal transmitter.) If you need to do this, you must delete
the first device (see Deleting Devices, below) and enroll the second. You will also need
to change the programming for the new device. See Section 3: Installing WLS9XX
Wireless Devices.
NOTE: To change the partition a handheld keypad is assigned to, you must delete and
then re-enroll the keypad.
5. To exit, press [#].
S E C T I O N 5
Deleting & Replacing Devices
firealarmresources.com

15
5.2 Deleting Devices
This section describes how to delete any of the enrolled wireless devices from the
PC4164-NB, and from the system.
1. At a system LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001301] to go to the Delete Device section. The LCD keypad will
display
Serial # [ ] and either
Zone Label XXX, Wkey# XX or HHK# XX
3. Use the [<][>] keys to scroll to the device you want to delete, then press [*]. The
bottom line of the display will read Device Deleted.
4. To exit, press [#].
When you enroll a new device, the serial number will fill the first available empty
zone, key or keypad slot. For example, if zones 017 to 019 and 021 to 023 are used,
but zone 020 is empty, the next device enrolled will be placed in zone number 020.
If you enroll a device of the same class as the one deleted (See Replacing Devices,
above) it will be placed in the old device’s slot.
Make sure you update the programming for each device you enroll.
5.3 Erasing Device Serial Numbers
Entering this programming section will erase the serial numbers of all the wireless
devices.
Zone and partition programming will not be affected. When you re-enroll the
wireless devices, remember to change the zone and partition programming, if
necessary.
1. At a LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001308], or scroll to Default Wireless and press [*].
3. The LCD will display Confirm Default Press *. To confirm the default
procedure, press [*]. To cancel the default procedure, press any other key.
D E L E T I N G & R E P L A C I N G D E V I C E S
firealarmresources.com

16
6.1 Device Supervision
When supervision of a wireless device on a zone is turned ON, the panel will show
a trouble if a wireless zone stops working or is removed from the system. When
supervision is turned OFF, the panel will not show a trouble.
NOTE: Wireless Keys are NOT supervised.
A zone supervisory is a test transmission that each wireless zone sends to the
PC4164-NB. When the PC4164-NB receives the supervisory transmission from the
zone, the PC4164-NB will transmit this information to the control panel.
If the control panel does not get a supervisory transmission from a zone within the
Device Fail time, the zone will be considered “missing” causing a Device Fault.
The next supervisory transmission that the PC4164-NB receives from the “missing”
zone will restore communication with that zone and restore the Zone Supervisory
Fault. The Device Fail timer will also be reset.
Change the Supervision Option
1. At a LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001306] to go to the Supv Window section.
3. Devices are listed by zone number in the order in which they were enrolled.
Scroll to each device. Press [*] to turn the supervision option ON or OFF for
that device.
4. To exit, press [#].
Change the Device Fail Time
The default amount of time is 3 hours.
1. At a LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[001307] to go to the Device Fail Time section.
3. Enter the time as [HHMM] (valid entries 01:00 - 23:59).
4. To exit, press [#].
S E C T I O N 6
Additional Programming Notes
firealarmresources.com

17
6.2 Trouble Conditions
The PC4010/4020 always watches for possible trouble conditions. If a trouble
condition occurs, the LCD keypad “Trouble” light will turn on and the keypad will
beep. Press [*][2] to display the trouble conditions.
The following trouble conditions apply to the PC4164-NB. For a description of all
troubles, please see Section 16 “Diagnostics and Troubleshooting” in the PC4010/4020
Installation Manual.
• PC4164 Tamper • Smoke Low Sense
• RF Jam Detected (see below) • Device Low Batt
• Device Fault (see section 6.1)
Wireless Device Low Battery Trouble Transmission Delay
When a device reports a low battery trouble, the keypad will indicate the trouble
immediately, but the panel will delay transmission of the trouble to the monitoring
station. You can program the length of the delay (in days) in Installer’s
programming. If the user does not correct the low battery condition before the
delay expires, the low battery trouble will be transmitted.
The low battery alarm and restore codes will only be reported once per armed
period. The Low Battery Restore transmission is not delayed. The default
transmission delay is 7 days.
To change the transmission delay:
1. At a LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[00040211] to go to the 4164 Low Bat Dly section.
3. Enter the new transmission delay (from 000 to 255 days).
4. To exit, press [#].
Replacing Batteries in Wireless Devices
1. Remove the cover of the device from its back plate. This creates a tamper
condition on the zone.
2. Refer to the battery installation instructions on the installation sheet of each
component. Be sure to note the proper orientation of the batteries as you install
them.
3. When the fresh batteries are in place, re-attach the cover to the back plate. The
tamper is restored and the zone sends a battery trouble restoral signal to the
PC4164-NB. The battery trouble is now clear.
NOTE: When batteries in one device need to be replaced, the batteries in all devices
should be replaced at the same time.
A D D I T I O N A L P R O G R A M M I N G N O T E S
firealarmresources.com

18
Enable RF Jam Detect Trouble
The RF Jam Detect trouble condition will be generated and logged when the
PC4164-NB module detects an attempt to block RF signals. This tells the user that
the PC4164-NB is not receiving wireless device transmissions. The panel will
transmit the General System Trouble reporting code.
The default setting for this option is OFF. To enable warning of this trouble condition:
1. At a LCD keypad, enter [*][8][Installer’s code].
2. Enter Ref #[000200] to go to the System Toggles section.
3. Scroll to RF Jam Detect.
4. Press [*] to toggle the option ON or OFF.
5. To exit System Toggles, press [#}.
A D D I T I O N A L P R O G R A M M I N G N O T E S
firealarmresources.com

19
Troubleshooting
S E C T I O N 7
1. When I enter [0013] PC4164 options, the keypad gives me a long beep.
You cannot enter ESNs unless the PC4164-NB wireless receiver is enrolled. See
section 2 for instructions on enrolling the PC4164-NB module.
2. I have entered the ESN for the device but when I violate the
device, the zone does not show open on the keypad.
Check the following:
• Check that you are looking at a keypad on the same partition as the device you
are testing
• Check that the ESN has been entered correctly
• Check that the zone is assigned to one or more partitions.
3. When I try a module placement test I get no result or “Bad” results.
Check the following (see sections 4.1 and 4.2 for more information on testing devices):
• Verify that you are testing the correct zone
• Verify that the correct ESN was entered when the device was enrolled
• Verify that the device is in range of the PC4164-NB. Try testing the device in the
same room as the receiver.
• Confirm that the PC4164-NB is properly connected to the Combus (see section
2 for PC4164-NB set up and wiring instructions).
• Check that you are testing the zone correctly (see sections 4.1 and 4.2 for testing
instructions)
• Check that the batteries are working and installed correctly.
• Look for large metal objects that may be preventing the signal from reaching
the PC4164-NB.
The device must be located where consistent “Good”or “Fair” results are obtained.
If several devices show “Bad” results, or if panic pendants and wireless keys operate
inconsistently, move the receiver. See section 2.3 for tips on choosing a mounting
location for the PC4164-NB.
4. The LED on the motion detector does not turn on when I walk in
front of the unit.
The LED is for walk test purposes only. See your WLS904-NB instruction sheet for
walk test instructions.
firealarmresources.com

20
Programming Worksheets
S E C T I O N 4
[001300] Enroll Device (see section 3.2)
• Default = 000000
• 6-digit entry is required; for 5-digit serial numbers, enter [0], then the number
(See section 3.1 “A Note About Electronic Serial Numbers”.)
System PC4164 Serial No.
Zone Zone
l
_____l_____l_____l1l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l2l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l3l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l4l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l5l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l6l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l7l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l8l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l9l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l10 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l11 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l12 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l13 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l14 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l15 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l16 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l17 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l18 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l19 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l20 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l21 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l22 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l23 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l24 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l25 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l26 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l27 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l28 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l29 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l30 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l31 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l32 l
_____l_____l_____l_____l_____l_____l
System PC4164 Serial No.
Zone Zone
l_____l_____l_____l33 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l34 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l35 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l36 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l37 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l38 l_____l_____l_____l_____l_____l_____l
l_____l_____l_____l39 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l40 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l41 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l42 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l43 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l44 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l45 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l46 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l47 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l48 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l49 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l50 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l51 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l52 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l53 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l54 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l55 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l56 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l57 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l58 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l59 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l60 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l61 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l62 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l63 l
_____l_____l_____l_____l_____l_____l
l_____l_____l_____l64 l
_____l_____l_____l_____l_____l_____l
PC4020 only
firealarmresources.com
Table of contents
Other Maxsys Receiver manuals