OPERATIONAL AND MAINTENANCE
MANUAL
Jet fan
mcr Bora
Revision 19.06.27.4
FIRE VENTILATION SYSTEMS

“MERCOR” SA – The company reserves the right to modify and change the document 2/11
TABLE OF CONTENTS:
1. FOREWORD ........................................................................................................................................ 3
2. MANUFACTURER'S DISCLAIMER ..................................................................................................... 3
3. SUBJECT ............................................................................................................................................. 4
4. INTENDED USE .................................................................................................................................. 4
4.1. Application ................................................................................................................................... 4
4.2. Fire resistance ............................................................................................................................. 4
4.3. Versions....................................................................................................................................... 5
5. IDENTIFICATION MARKINGS ............................................................................................................ 5
6. DESIGN AND OPERATING PRINCIPLE .............................................................................................. 5
6.1. Design ......................................................................................................................................... 5
6.2. Function ....................................................................................................................................... 5
6.3. Dimensions and technical features .............................................................................................. 5
7. INSTALLATION .................................................................................................................................... 7
7.1. Pre-assembly inspection .............................................................................................................. 7
7.2. Location and assembly ................................................................................................................ 7
7.3. Electrical connections .................................................................................................................. 7
7.4. Commissioning ............................................................................................................................ 8
8. TRANSPORT & STORAGE CONDITIONS........................................................................................... 8
9. SAFETY MANUAL ................................................................................................................................ 9
10. MAINTENANCE & SERVICING .......................................................................................................... 8
11. WARRANTY TERMS & CONDITIONS ............................................................................................... 9
FAN MEASUREMENT REPORT ............................................................................................................ 11

“MERCOR” SA – The company reserves the right to modify and change the document 3/11
NOTE
All previous issues of this O&M Manual expire on the date of issue hereof.
This Operating and Maintenance Manual does not apply to any fans manufactured prior to this
Manual's date of issue.
1. FOREWORD__________________________________________________
This Operating and Maintenance Manual is addressed to users/operators of type mcr Bora jet fans. This
document is intended to provide guidelines on the application, design, commissioning and operation of
the product.
Read this manual thoroughly before installing this equipment at its operating site
and commissioning.
If the equipment is found malfunctioning or defective, contact the manufacturer or
their authorised representative.
Due to the continuous product improvement policy, we reserve the right to change
the product design in order to improve its performance and safety.
The design of the fans complies with the essential requirements of PN-EN 12101-3:2004 for smoke
exhaust fans. The design also meets the state of the art in technology, while assuring health and safety
protection.
2. MANUFACTURER'S DISCLAIMER__________________________________
The manufacturer shall not be liable for any consequences of non-intended use or misuse of the
equipment.
DO NOT install any components that are not included in the equipment composition or
accessories.
Unauthorised modifications or alteration of this equipment is strictly prohibited.
Protect the equipment enclosure (casing) from mechanical damage.
Before attempting to install this equipment, verify the load bearing capacity of the structural
members to which the equipment is to be fastened. Unreliable fastening may result in damage or
failure of the equipment and/or be hazardous to all nearby personnel.
This fan is not intended for forcing air with viscous pollutants that may settle on the equipment,
and especially on its rotor.
This fan is not intended for forcing air with corrosive pollutants that may be detrimental to the
equipment.
The maximum actual rotor RPM must never exceed the nominal (rated) RPM speed in operation.
The manufacturer shall not be liable for any injuries, trauma or other bodily harm caused by
misuse of this equipment.

“MERCOR” SA – The company reserves the right to modify and change the document 4/11
3. SUBJECT______________________________________
The subject of this Operating and Maintenance Manual is:
Jet fan mcr Bora F400
Jet fan mcr Bora F300
Jet fan mcr Bora F200
Jet fan mcr Bora BO – without fire resistance
4. INTENDED USE___________________________________________________
4.1. Application_________________________________________________________________
The mcr Bora jet fans are intended to remove smoke and heat generated in indoor rooms in case of fire.
The equipment facilitates evacuation of persons from the area on fire, protect the building structure and
its furnishing from high temperature, facilitate fire fighting, and inhibit spreading of fire to adjacent fire
zones.The mcr Bora without fire resistance jet fans are intered to ventilate rooms in case of no fire
occurance.
The available versions include:
single direction fans, with dual-speed motor
reversible fans, with dual-speed motor
The fans can be installed indoors on suitable consoles with the motor in the horizontal orientation.
The operating temperature range for fans in general purpose ventilation
systems is -20°C to + 40°C.
The fan may force dry air only, with a maximum particulate content of 0.3 g/m³.
This fan is not intended for forcing air with viscous pollutants that may settle
on the equipment, especially on its rotor.
This fan is not intended for forcing air with corrosive pollutants that may be
detrimental to the equipment.
The maximum actual rotor RPM must never exceed the nominal (rated) RPM
speed in operation.
Following operation in actual fire conditions, the fan will not be fit for further
use.
4.2. Fire resistance__________________________________________________________
Class F400 – fire resistance at 400°C for 120 minutes
Class F300 – fire resistance at 300°C for 60 minutes
Class F200 – fire resistance at 200°C for 120 minutes
Without fire resistance

“MERCOR” SA – The company reserves the right to modify and change the document 5/11
4.3. Versions ______________________________________________________________________
dual speed jet fans, single-direction - U
dual speed jet fans, reversible - R
Versions ___________________________________________________________________________
Polygonal, painted casing – O
Polygonal, steel casing – L
5. IDENTIFICATION MARKINGS ______________________________________
mcr Bora 40 - R - L - F400
Temperature category
Casing type
Airflow direction
Nominal size [diameter, cm]
Fan type
6. DESIGN AND OPERATING PRINCIPLE _____________________________
6.1 Design _________________________________________________________________________
The mcr Bora jet fan comprises an electrical motor with a suitable insulation class, an axial rotor, a blade
assembly, an outer casing assembly and silencers.
The motor is coupled directly to an aluminium rotor on bearings, and on the rotor the profiled blades are
installed. The angle and number of blades depend on the required thrust and capacity of the fan. The
motor bearings are high temperature resistant and maintenance free. On the inlet and outlet side the
engine is connected to silencers. The medium, which is fire gases and air with smoke, flows through the
casing, the motor, the rotor blades and the silencer.
The mcr Bora fans in O and L versions have a connection box located on the casing.
All types of fans have fasteners or assembly frames, depending on the fan size.
6.2 Function _______________________________________________________________________
The fan does not run while in standby. When 3-phase voltage is present on the terminal box terminals,
the fan is started and running.
6.3 Dimensions and technical features __________________________________________
The basic dimensions of fans as well as their technical parameters are given below.

“MERCOR” SA – The company reserves the right to modify and change the document 6/11
Drawing 1 mcr BORA L, O
Fan ØD
[mm]
L
[mm]
Lc
[mm]
H
[mm]
Hc
[mm]
S
[mm]
E
[mm]
F
[mm]
G
[mm]
K
[mm]
M
[mm]
N
[mm]
mcr Bora 290
290 2000 2410 317 329 472 400 610 580 167 26 12
mcr Bora 315
315 2000 2410 342 354 472 400 610 580 167 26 12
mcr Bora 355
355 2000 2410 377 389 517 400 644 614 167 26 12
mcr Bora 380
380 2000 2410 407 419 557 400 644 614 167 26 12
mcr Bora 400
400 2000 2410 427 440 607 400 694 664 167 26 12
mcr Bora 450
450 2000 2410 482 495 657 400 750 720 167 26 12
mcr Bora 500
500 2650 3060 533 547 708 480 780 750 200 30 14
mcr Bora 560
560 2650 3060 608 622 798 650 950 920 255 30 14
7. INSTALLATION_____________________________________________
The mcr Bora smoke exhaust jet fan is intended for use in rooms designed for moving air and fire gases
(in the fire zone).
7.1. Pre-assembly inspection____________________________________________________
Each smoke exhaust fan is factory inspected by the manufacturer prior to packing and shipping. Upon
unpacking the delivered smoke exhaust fan, visually examine it for any damage in transport.
The motor shaft should rotate with the rotor without evident resistance or scraping.

“MERCOR” SA – The company reserves the right to modify and change the document 7/11
7.2. Location and assembly_______________________________________________________
The mcr Bora fan is designed for horizontal installation. Prior to installation of the fan, verify the load
bearing capacity of the ceiling or other structural element where the equipment is to be suspended. Use
the mounting frame (part of the fan itself) or the fasteners supplied with the fan. Using the above
mentioned element, the device is fitted to the structural elements using bolts or using hangers (not
supplied).
Fan due to his construction, does not require vibration isolation between the structural elements and the
device. In case of demanded by bulining project assembly by means of vibration insolation, the
manufacturer recommend to instal the device according to drawing 2. Other assembly may be provided,
providing that the device is safe and undisturbed, in normal operation and fire condtions. Screws,
anchors, suspensions (diameter, length) and other assembly elements must be selected for the size of
the device and the required fire resistane.
Drawing 2 Example illustrating how to install the mcr Bora with
vibration isolation elements.
7.3. Electrical connections_____________________________________________________
Having properly located, placed and fastened the smoke exhaust fan, connect the equipment to the
relevant electrical system wiring. Lead the wiring through the gland and into the terminal box on the fan
casing; then connect the wiring to the terminals in accordance with the diagram shown in the box. The
electrical wire with the proper fire resistance rating is installed in standard by the manufacturer between
the fan motor and the terminal box. Each fan motor must be connected to the electrical power system
through an overcurrent switch. The safety level must be set in accordance with the nominal current draw
of the fan motor. The protective earth shall be made in accordance with relevant electrical engineering
standards.
Once the smoke exhaust fan has been commissioned as a part of the system, measure the current draw
and verify that it meets the motor rating plate data. The smoke exhaust fan current draw in steady
operation must not exceed 1.1 times the rated current.
The electrical power supply from the control cabinet to the fan power junction box must guarantee
uninterrupted operation in the case of a fire. This can be achieved with high temperature resistant wiring
or with protective tubing and proper safe routing of the electrical power system. No external
service/maintenance switches are to used, which is to prevent inadvertent shutdown of the smoke
exhaust fan (with the sole exception of the fan-dedicated service switch with remote indication of current
circuit switching). The smoke exhaust fan control cabinets must be powered directly from main
switchboards with guaranteed uninterrupted power supply, even if the entire building is cut off from the
power grid. If a main fireman's switch is installed to isolate power from the entire building, the smoke

“MERCOR” SA – The company reserves the right to modify and change the document 8/11
exhaust fan power supply must be independent from that solution and assure normal operation in the
case of a fire.
7.4. COMMISSIONING _____________________________________________________________
Before commissioning your installed smoke exhaust fan do the following:
Check that the smoke exhaust fan is properly and firmly fastened.
Check all seals for tightness.
Check that all electrical wiring is properly and firmly connected.
Check that the phase connection sequence and PE/neutral wiring is properly connected.
Check that the smoke exhaust fan is free of foreign objects.
Check that all protective/safety components have been installed.
If the checks are positive, start the fan and do a functional test.
When starting the smoke exhaust fan, verify the motor direction of rotation against the direction
arrow on the enclosure.
8. TRANSPORT & STORAGE CONDITIONS __________________
The mcr Bora smoke exhaust fans are placed on pallets during transport and storage. Do not topple or
throw the packaging during loading and transport. The smoke exhaust fans can be handled and shipped
using any means of transport, provided that they are secured against weather. The smoke exhaust fans
must be secured against shifting while on transport vehicles. Visually inspect each piece of equipment
following transport and handling.
Store in sheltered rooms, where:
there is no exposure to particulates, gases, corrosive vapours and other aggressive chemical
emissions detrimental to insulation parts and structural components of the fan and/or its motor;
the maximum relative humidity is 80% at +20°C;
the ambient temperature is between -20ºC and + 40ºC;
no vibrations are present.
9. SAFETY MANUAL________________________________________________
Read and understand this Operating and Maintenance Manual before commissioning and servicing the
product.
The smoke exhaust fan is not hazardous when firmly attached to a ventilation system and the fan
support structure.
Make the electrical connections in accordance with the enclosed electrical wiring diagram and the
guidelines in Section 7.3. Electrical connections shall be made by personnel with relevant qualifications
which have been certified as required by current laws.
Inspect the PE wire connection of the smoke exhaust fan during the operating life.
Disconnect the smoke exhaust fan from electrical power before any inspections or checks.
CAUTION:
1. Do not clean smoke exhaust fans of deposits with pressure or steam washers.
2. Loss of seal at the fan connections or flexible ends may result in hazards due to release of the forced
medium and requires immediate replacement of leaking components.
If the equipment is malfunctioning (e.g. excessive noise, vibration and/or erratic operation is found),
disconnect the fan from electrical power supply, and call the manufacturer's technical service or an
inspection and repair contractor authorised by the manufacturer.
10. MAINTENANCE & SERVICING____________________________________
The equipment from “Mercor” SA requires periodic technical inspection and maintenance at least every
12 months throughout its operating life, i.e. during the warranty and post-warranty period. Inspection and
maintenance may only be carried out by the manufacturer or contractors authorised by “MERCOR” SA to
service its products.

“MERCOR” SA – The company reserves the right to modify and change the document 9/11
The obligation to carry our regular service inspections of fire protection devices results from the Art. 3(3)
of the Regulation by the Minister of Internal Affairs and Administration of 7 June 2010 on fire protection
of buildings, other civil structures and areas (Journal of Laws 2010 no. 109 item 719):
Do these recommended actions in the inspection intervals:
Check the electrical connections, especially for all mechanical damage.
Check the equipment casing, especially for any mechanical damage.
Check for any obstructions to proper operation of the equipment.
To facilitate the activities under service inspection, servicing and warranty claim response, e.g. visual
inspection or repairs, the equipment user/operator shall provide physical access to the equipment by
removing thermal insulation, suspended ceilings, and other installations, as required and applicable to
warrant unobstructed access.
If the equipment is only operated for smoke exhaust during fire, test run it for ca. 10 minutes every 3
months.
Refer all matters related to technical inspection, maintenance and servicing of this equipment to the
341 39 85, from 8 AM to 4 PM (Mo-Fri).
11. WARRANTY TERMS & CONDITIONS______________________________
1. “MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase,
unless the sales contract states otherwise.
2. Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty
eligible defect
3. Submit warranty claims by calling at: tel. +48 58 341 42 45, by fax: +48 58 341 39 85, by e-mail:
408 Gdańsk, Poland.
4. If physical defects of equipment are found during the warranty period, “MERCOR” SA warrants and
represents to remove them in shortest possible time from serving the written warranty claim with
the proof of purchase or sales contract, subject to Item 10.
5. “MERCOR” SA has the right to extend the time of repair if the defect removal is complicated or
requires purchase of custom components or spare parts.
6. The warranty liability only covers all defects arising from causes present in the equipment at the
date of sale.
7. Defects caused by improper operation or otherwise as listed in Item 10 herein, the buyer / warranty
beneficiary will be charged with the costs of their removal.
8. Condition for rectifying defects is that the applicant makes the site/localisation where devices are
installed available, in particular, ensuring: the lift in the case of devices mounted at a height above
3m, free access to the rooms where the devices were installed and necessary revisions,
dismantling thermal insulation, disassembling suspended ceilings, disassembling other
installations, if they prevent free access to the device.
9. If the device can not be repaired at the place of its installation, "MERCOR" SA reserves the
necessity of its disassembly, possible delivery to the address indicated by "MERCOR" SA and re-
assembly. The cost of this operation lies with the buyer / holder of the guarantee.
10. The warranty does not cover:
Any damage or failure of the equipment caused by improper operation, tampering, failure to
conduct periodic technical inspection and/or maintenance established in the Operating and
Maintenance Manual, section “SERVICING AND MAINTENANCE”.
Any damage beyond reasonable control of “MERCOR” SA, and specifically: caused by force
majeure, such as torrential rainfall, flooding, hurricanes, inundation, lightning strike, power
grid overvoltage, explosion, hail, collision with aircraft, fire, avalanche, landslide and indirect
damage due to those causes. Torrential rainfall is understood as any rainfall with the
effectiveness factor of 4 or higher in accordance with the definition of the Polish Institute of
Meteorology and Water Management - National Research Institute (IMGW-PIB). If the
effectiveness factor value specified in the preceding sentence cannot be reasonably
established, the actual condition and extent of damage shall be considered at the site of their
origin as the action of torrential rain. Hurricane is understood as any wind with a minimum

“MERCOR” SA – The company reserves the right to modify and change the document 10/11
speed of 17.5 m/s (and damage shall be recognised as caused by hurricanes if the effects of
such weather phenomenon has been found in the direct vicinity of the damaged property).
Damage due to failure to immediately report any defect found.
Deterioration in the quality of coatings due to natural weathering/ageing.
Defects caused by abrasive or aggressive cleaning agents.
Damage caused by aggressive external influence, specifically chemical or biological in
nature, or when the origin of which is related to the production processing or activity carried
out within the facility protected by the equipment or in its direct vicinity.
Wearing parts and consumables (e.g. gaskets/seals), unless they have defects of
workmanship and/or material.
Damage caused by improper transport, handling, unloading and/or storage of the equipment.
Damage caused by installation of the equipment in violation of this Operating and
Maintenance Manual and/or good construction practice.
The equipment and/or parts thereof with removed or damaged nameplate (rating plate)
and/or warranty seals.
11. The buyer/warranty rights holder is required to operate the equipment properly and carry out
technical inspection and maintenance in accordance with the section “MAINTENANCE AND
SERVICING” in the following Operating and Maintenance Manual.
12. This warranty shall be made immediately void and null if:
The buyer/warranty rights holder modifies the product design without prior authorisation from
“MERCOR” SA.
Periodic technical inspection and/or maintenance is not carried out per schedule and/or is
carried out by unauthorised personnel or service providers not authorised to do so by
“MERCOR” SA and/or the equipment has not been properly operated.
Unauthorised personnel attempts any intervention in the product outside of the normal
operation and maintenance of this equipment.
13. Any circumstances listed in Item 10 will relieve “MERCOR” SA from the obligation of surety.
The relevant provisions of the Polish Civil Code shall apply to all matters not regulated in these Warranty Terms & Conditions.

“MERCOR” SA – The company reserves the right to modify and change the document 11/11
FAN MEASUREMENT REPORT
FAN TYPE
SERIAL NUMBER
INSTALLATION SITE
RATED CURRENT
Once the fan has been installed at its intended operating site and all electrical connections have
been made, immediately measure the current draw in steady-state operation of the equipment.
MEASUREMENT RESULTS [A]
U1 V1 W1 U2 V2 W2
NOTES:
Full name of the measuring technician Date measured Signature
Return this Report immediately after completion of measurements to:
“MERCOR” SA
Fire Ventilation Systems
ul. Grzegorza z Sanoka 2
80-408 Gdańsk
and not later than within 8 weeks from the date of equipment purchase (equivalent to the date of the VAT
sales invoice).
THE EQUIPMENT WARRANTY BECOMES ENFORCEABLE UPON RETURN OF THIS
MEASUREMENT REPORT
This manual suits for next models
3
Table of contents
Other mercor Fan manuals
Popular Fan manuals by other brands

Craftmade
Craftmade Copeland CN52 installation guide

Steba
Steba VT 5 Instructions for use

CONCORD
CONCORD Avia 60AV5E Owner's manual and installation instructions

Fanimation
Fanimation Vetricco FP3120 Series Specification sheet

villavent
villavent VR-400 EV User and maintenance instructions

BOMANN
BOMANN VL 1133 S CB instruction manual