mercor mcr Monsun Series User manual

ul. Grzegorza z Sanoka 2
80-408 Gdańsk
tel. +48 58 341 42 45
tel./fax +48 58 341 39 85
TECHNICAL
MANUAL
Smoke exhaust axial fan
mcr Monsun
Version: Monsun 19.06.27.3
FIRE VENTILATION SYSTEMS

2/19
CONTENTS:
1. FOREWORD ........................................................................................................................................ 3
2. MANUFACTURER'S DISCLAIMER ..................................................................................................... 3
3. SUBJECT ............................................................................................................................................. 4
4. INTENDED USE .................................................................................................................................. 4
4.1. Application ................................................................................................................................... 4
4.2. Fire resistance ............................................................................................................................. 5
4.3. Versions....................................................................................................................................... 5
5. DESIGN AND OPERATING PRINCIPLE .............................................................................................. 5
5.1. Design ......................................................................................................................................... 5
5.2. Function ....................................................................................................................................... 6
5.3. Dimensions .................................................................................................................................. 6
5.4. Accessories ................................................................................................................................. 6
6. IDENTIFICATION MARKING ............................................................................................................. 11
7. INSTALLATION .................................................................................................................................. 11
7.1. Pre-assembly inspection ............................................................................................................ 11
7.2. Location and assembly .............................................................................................................. 11
7.3. Electrical connections ................................................................................................................ 13
7.4. Commissioning .......................................................................................................................... 14
8. TRANSPORT & STORAGE CONDITIONS......................................................................................... 14
9. SAFETY MANUAL .............................................................................................................................. 16
10. MAINTENANCE & SERVICING ........................................................................................................ 16
11. WARRANTY TERMS & CONDITIONS ............................................................................................. 16
FAN MEASUREMENT REPORT ........................................................................................................... 17

3/19
CAUTION
All previous issues of this Technical Manual expire on the date of issue hereof.
This Technical Manual does not apply to any fans manufactured prior to this Manual's date of
issue.
1. FOREWORD__________________________________________________
This Technical Manual is addressed to users/operators of type mcr Monsun smoke exhaust axial fans.
This document is intended to provide guidelines on the application, design, commissioning and operation
of the product.
Read this Technical Manual thoroughly before installing this equipment at its operating
site and commissioning.
If the equipment is found malfunctioning or defective, contact the manufacturer or their
Authorised Representative.
Due to the continuous product improvement policy, we reserve the right to change the
product design in order to improve its performance and safety.
The design of the ventilators complies with the essential requirements of PN-EN 12101-3:2004 for smoke
exhaust fans. The design also meets the state of the art in technology, while assuring health and safety
protection.
This equipment has been designed and manufactured according to the following standards:
PN-EN 12101-3:2004 Smoke and heat control systems.
Part 3: Specification for powered smoke and heat exhaust fans.
PN-EN ISO 12100-1:2005 Safety of machinery. Basic concepts, general principles for design.
Part 1: Basic terminology, methodology.
PN-EN ISO 12100-2:2005 Safety of machinery. Basic concepts, general principles for design.
Part 2: Technical principles.
PN-EN 60204-1:2001 Safety of machinery. Electrical equipment of machines.
Part 1: General requirements.
The smoke exhaust fan design also meets the state of the art in technology, while assuring health and
safety protection.
2. MANUFACTURER'S
DISCLAIMER____________________________________
The manufacturer shall not be liable for any consequences of non-intended use or misuse of the
equipment.
DO NOT install any components that are not included in the equipment composition or accessories.
Unauthorised modifications or alteration of this equipment is strictly prohibited.
Protect the equipment enclosure (casing) from mechanical damage.
Before attempting to install this equipment, verify the load bearing capacity of the structural
elements to which the equipment is to be fastened. Unreliable fastening may result in damage or

4/19
failure of the equipment and/or be hazardous to all nearby personnel.
This fan is not intended for forcing air with viscous pollutants that may settle on the equipment, and
especially on its rotor.
This fan is not intended for forcing air with corrosive pollutants that may be detrimental to the
equipment.
The maximum actual rotor RPM must never exceed the nominal (rated) RPM speed in operation.
The manufacturer shall not be liable for any injuries, trauma or other bodily harm caused by misuse
of this equipment.
3. SUBJECT________________________________________________________
The subject of this Technical Manual is:
mcr Monsun F400 smoke exhaust axial fans
mcr Monsun F300 smoke exhaust axial fans
mcr Monsun F200 smoke exhaust axial fans
4. INTENDED USE___________________________________________________
4.1. Application_____________________________________________________________
The type mcr Monsun smoke exhaust axial fans are duct fans intended to remove smoke and heat
generated in indoor rooms on fire. The equipment facilitates evacuation of persons from the area on fire,
protect the building structure and its furnishing from high temperature, facilitate fire fighting, and inhibit
spreading of fire to adjacent fire zones.
The available versions include:
single-functional with single-speed motors;
two-functional, i.e. for general and fire ventilation and with two-speed motors.
The fans can be installed indoors or outdoors: on suitable consoles with the motor in the vertical
orientation, or on the bottom feet with the motor in the horizontal orientation.
The fan overall compression ratio makes them compatible with ventilation systems characterised by
relatively high flow resistance.
The operating temperature range for fans in general ventilation systems is – 20°C
to + 40°C.
The fan may force dry air only and with a maximum particulate content of 0.3
g/m³.
This fan is not intended for forcing air with viscous pollutants that may settle
on the equipment, and especially on its rotor.
This fan is not intended for forcing air with corrosive pollutants that may be
detrimental to the equipment.
The maximum actual rotor RPM must never exceed the nominal (rated) RPM
speed in operation.
Following operation in actual fire conditions, the fan will not be fit for further
use.

5/19
4.2. Fire resistance__________________________________________________________
Class F400 – fire resistance at 400oC for 120 minutes
Class F300 – fire resistance at 300oC for 60 minutes
Class F200 – fire resistance at 200oC for 120 minutes
4.3. Versions
Single-speed single-functional fans
Two-speed two-functional fans
5. DESIGN AND OPERATING PRINCIPLE _____________________________
5.1. Design ________________________________________________________________________
1 - Fan housing
2 - Axial rotor
3 - Base support
4 - Motor base
5 - Electrical gland
6 - Electric box
7 - Rotor safety
8 - Motor, fire resistant at the specific temperature class
The smoke exhaust axial fan feature a steel housing in the form of a cylinder with connection flanges at
its end, intended for connection with the ventilation system. Inside of the enclosure the motor is located
and supported by the motor base. The rotor is set directly on the motor shaft neck. At the rotor intake and
in line with its centreline is an aerodynamic cone, which improves the flow performance. The fan can also
feature an air stator type KP, located inside of the ventilator casing on the rotor end.
The electric box is installed on the fan casing, to which the electrical wiring of suitable fire resistance is led
from the motor.
The rotors with the diameter D = [355; 400; 450] mm feature 9 blades, while the rotors with the diameter
D = [500-560-630-710-800-900-1000] mm are available with 12 blades.
The fan may work with various blade angles and numbers. This allows adapting the fan performance to
the ventilation system flow resistance characteristics.
Each fan features an inspection hatch which permits verification of the rotor sense of rotation.

6/19
5.2. Function ______________________________________________________________________
The single-functional fans do not run in standby. When 3-phase voltage is present on the electric box
terminals, the fan is started and running.
The two-functional fans run at low speed (RPM) to handle general ventilation under normal conditions.
When the fan receives an alarm signal, it automatically starts running with the second speed, which is
higher than the first one.
5.3. Dimensions ___________________________________________________________________
mcr Monsun smoke exhaust axial fans - ... - Table of dimensions
Fan - Type D [mm]
~A [mm] ~L [mm] B [mm]
C [°]
nxd [mm]
mcr Monsun 35 355 425 400 395 45 8x9.6
mcr Monsun 40 400 470 500 438 30 12x9.6
mcr Monsun 45 450 520 500 487 30 12x9.6
mcr Monsun 50 500 570 600 541 30 12x9.6
mcr Monsun 56 560 640 700 605 22.5
16x10.5
mcr Monsun 63 630 710 600 674 22.5
16x10.5
mcr Monsun 71 710 790 750 751 22.5
16x10.5
mcr Monsun 80 800 875 750 837 15 24x10.5
mcr Monsun 90 900 975 900 934 15 24x10.5
mcr Monsun 100 1000 1080 1000 1043 15 24x10.5
mcr Monsun 112 1120 1240 1150 1190 15 24 x 14
mcr Monsun 125 1250 1390 1150 1340 15 24 x 14

7/19
5.4. Accesories ___________________________________________________________________
Type SW bottom feet
made of galvanized steel sheet. Powder-coated in standard, or galvanized on custom order. The bottom
feet are intended for horizontal installation of the fan [horizontal orientation of the fan axis]. Fasten the feet
to the fan housing flange with M8 or M10 bolts, depending on the equipment size. Note that the motor
base must be level in the horizontal plane once the fan has been set in place. The openings in the bottom
shelf of each feet allow tightening of vibration dampers.
Do not use type SW bottom feet for installation in the vertical orientation.
Type SW bottom foot
Fan - Type Type A
[mm]
B
[mm]
C
[mm]
d
[mm]
H
[mm]
L
[mm]
m
[kg]
mcr Monsun 35 SW-35 305 245 50 12.5 260 344 1.1
mcr Monsun 40 SW-40 300 240 50 12.5 280 444 0.9
mcr Monsun 45 SW-45 320 260 50 12.5 320 444 1.1
mcr Monsun 50 SW-50 400 320 50 12.5 350 544 1.4
mcr Monsun 56 SW-56 450 370 50 12.5 375 644 1.7
mcr Monsun 63 SW-63 500 420 50 12.5 425 544 2.1
mcr Monsun 71 SW-71 550 470 50 12.5 475 694 2.4
mcr Monsun 80 SW-80 650 570 50 12.5 525 694 3.1
mcr Monsun 90 SW-90 700 620 60 12.5 575 834 3.4
mcr Monsun 100 SW-100
780 670 70 12.5 650 924 10.2
mcr Monsun 112 SW-112
900 780 75 18 710 1065 15,5
mcr Monsun 125 SW-125
1000 880 75 18 775 1065 17,5
Type KD flexible joint
features a laminar design; it is terminated with a flange with the holes sized and spaced as on the fan
housing flange. The special fiberglass silicate textile ensure durability at 400ºC for 120 min.
Type KD flexible joint is used to eliminate the vibrations transmitted from the fan to the ventilation system.
It acts as a vibration damper. It is also used to compensate for thermal elongation. The fan integrated in a
ventilation system should feature the flexible joint on the suction and pressure sides.
Type KD flexible joint
Fan - Type Type D
[mm]
~A
[mm]
B
[mm]
L
[mm] C nxd
[mm]
m
[kg]
mcr Monsun 35 KD-35 355 425 395 150 45 8x9.6 1.1
mcr Monsun 40 KD-40 400 470 438 150 30 12x9.6 1.3
mcr Monsun 45 KD-45 450 520 487 150 30 12x9.6 1.4
mcr Monsun 50 KD-50 500 570 541 150 30 12x9.6 1.6
mcr Monsun 56 KD-56 560 640 605 150 22.5
16x10.5 1.8
mcr Monsun 63 KD-63 630 710 674 200 22.5
16x10.5 2.0
mcr Monsun 71 KD-71 710 790 751 200 22.5
16x10.5 2.3
mcr Monsun 80 KD-80 800 875 837 200 15 24x10.5 2.6
mcr Monsun 90 KD-90 900 975 934 200 15 24x10.5 2.9
mcr Monsun 100 KD-100
1000 1080 1043 200 15 24x10.5 3.2
mcr Monsun 112 KD-112
1120 1240 1190 200 15 24x14 3,5
mcr Monsun 125 KD-125
1250 1370 1320 200 15 24x14 3,8

8/19
Type PK counterflange
made of galvanized steel sheet. Powder-coated in standard, or galvanized on custom order. This fitting is
first used for installation of type KD flexible joints on the fan and to connect the ventilation system to the
ventilator.
Type PK counterflange
Fan - Type Type D
[mm]
~A
[mm]
B
[mm] C nxd
[mm]
m
[kg]
mcr Monsun 35 PK-35 359 425 395 45 8x9.6 0.9
mcr Monsun 40 PK-40 404 470 438 30 12x9.6 1.0
mcr Monsun 45 PK-45 454 520 487 30 12x9.6 1.2
mcr Monsun 50 PK-50 504 570 541 30 12x9.6 1.3
mcr Monsun 56 PK-56 564 640 605 22.5
16x10.5 1.6
mcr Monsun 63 PK-63 634 710 674 22.5
16x10.5 1.8
mcr Monsun 71 PK-71 716 790 751 22.5
16x10.5 2.0
mcr Monsun 80 PK-80 806 875 837 15 24x10.5 2.1
mcr Monsun 90 PK-90 906 975 934 15 24x10.5 2.2
mcr Monsun 100 PK-100 1006 1080 1043 15 24x10.5 2.8
mcr Monsun 112 PK-112 1126 1240 1190 15 24x14 8,1
mcr Monsun 125 PK-125 1256 1370 1320 15 24x14 9,1
Type SO safety mesh
made of galvanized steel sheet and galvanized wire mesh. Powder-coated in standard, or galvanized on
custom order. The fitting protects the fan from ingress of foreign bodies. The product is designed for direct
mounting on the fan housing flange with free-flow suction and forcing. Periodically check that the safety
mesh is clean and clean it when necessary.
Type SO safety mesh
Fan - Type Type D
[mm]
A
[mm]
~B
[mm]
~h
[mm] C nxd
[mm]
m
[kg]
mcr Monsun 35 SO-35 355 395 425 5 45 8x9.6 1.2
mcr Monsun 40 SO-40 400 438 470 5 30 12x9.6 1.3
mcr Monsun 45 SO-45 450 487 520 5 30 12x9.6 1.5
mcr Monsun 50 SO-50 500 541 570 5 30 12x9.6 1.7
mcr Monsun 56 SO-56 560 605 640 5 22.5
16x10.5 2.2
mcr Monsun 63 SO-63 630 674 710 5 22.5
16x10.5 2.5
mcr Monsun 71 SO-71 710 751 790 5 22.5
16x10.5 2.9
mcr Monsun 80 SO-80 800 837 875 5 15 24x10.5 3.1
mcr Monsun 90 SO-90 900 934 975 5 15 24x10.5 3.5
mcr Monsun 100 SO-100 1000 1043 1080 5 15 24x10.5 4.4
mcr Monsun 112 SO-112 1120 1190 1240 7 15 24x14 12,9
mcr Monsun 125 SO-125 1250 1320 1370 7 15 24x14 14,6

9/19
Type PP vertical support
made of galvanized steel sheet. Powder-coated in standard, or galvanized on custom order. The product
is designed for installing the fan in the vertical orientation. Set the support on e.g. a foundation structure
indirectly with vibration dampers bolted to the 4 holders at the support circumference.
Type PP vertical support
Fan - Type Type Dn
[mm]
dp
[mm]
A
[mm]
H
[mm]
B
[mm]
nxd
[mm] C [º]
m
[kg]
mcr Monsun 35 PP-35 355 12.2 479 50 395 8x9.6 45 5.4
mcr Monsun 40 PP-40 400 12.2 524 50 438 12x9.6 30 5.8
mcr Monsun 45 PP-45 450 12.2 574 50 487 12x9.6 30 6.3
mcr Monsun 50 PP-50 500 12.2 624 50 541 12x9.6 30 6.8
mcr Monsun 56 PP-56 560 12.2 684 50 605 16x10.5 22.5
7.8
mcr Monsun 63 PP-63 630 12.2 754 100 674 16x10.5 22.5
9.1
mcr Monsun 71 PP-71 710 12.2 836 100 751 16x10.5 22.5
11.6
mcr Monsun 80 PP-80 800 12.2 926 100 837 24x10.5 15 12.4
mcr Monsun 90 PP-90 900 12.2 1026 100 934 24x10.5 15 13.3
mcr Monsun 100 PP-100 1000 12.2 1126 100 1043 24x12.2 15 15.2
mcr Monsun 112 PP-112 1120 12,2 1190 100 1190 24x14 15 24
mcr Monsun 125 PP-125 1250 12,2 1460 100 1320 24x14 15 28
Automatic non-return damper: type KS [horizontal] and KS-V [vertical]
the damper body is made of galvanized steel sheet. Powder-coated in standard, or galvanized on custom
order. The damper blade is made of aluminium sheet. Type KS and KS-V automatic non-return dampers
are installed to prevent air circulation and heat losses when the fan is in standstill. The damper needs to
be truly level to operate correctly.
Automatic non-return damper; type KS, KS-V
Fan - Type Type D
[mm]
~A
[mm]
B
[mm]
L
[mm] C nxd
[mm]
m
[kg]
mcr Monsun 35 KS[V]-35 355 425 395 240 45 8x9.6 6.6
mcr Monsun 40 KS[V]-40 400 470 438 250 30 12x9.6 7.6
mcr Monsun 45 KS[V]-45 450 520 487 290 30 12x9.6 9.5
mcr Monsun 50 KS[V]-50 500 570 541 320 30 12x9.6 11.3
mcr Monsun 56 KS[V]-56 560 640 605 350 22.5
16x10.5 14.0
mcr Monsun 63 KS[V]-63 630 710 674 360 22.5
16x10.5 16.2
mcr Monsun 71 KS[V]-71 710 790 751 430 22.5
16x10.5 20.8
mcr Monsun 80 KS[V]-80 800 875 837 470 15 24x10.5 24.8
mcr Monsun 90 KS[V]-90 900 975 934 540 15 24x10.5 30.9
mcr Monsun 100 KS[V]-100 1000 1080 1043 580 15 24x10.5 37.4
mcr Monsun 112 KS[V]-112 1120 1240 1190 650 15 24x14 90
mcr Monsun 125 KS[V]-125 1250 1370 1320 700 15 24x14 107
Type KS automatic non-return damper is intended for horizontal installation [with the damper blade in the
vertical].
Type KS-V automatic non-return damper is intended for vertical installation [with the damper blade in the
horizontal].

10/19
Type TH noise muffler
the noise muffler body is made of galvanized steel sheet. The inner core is made of perforated galvanized
metal sheet. The muffling part is made of non-flammable sound-proofing wool.
The threaded holes in the noise muffler allow direct fastening on the fan housing flange. Seal the joint
interface with high-temperature silicone.
Type TH noise muffler dampens the noise generated by the fan.
Type TH noise muffler
Fan - Type Type d1
[mm]
d2
[mm]
d3
[mm]
d4
[mm]
L
[mm] A [º]
nxM m
[kg]
mcr Monsun 35 TH-35 359 550 200 395 950 45 8xM8 41
mcr Monsun 40 TH-40 404 600 220 438 950 30 12xM8 53
mcr Monsun 45 TH-45 454 650 250 487 950 30 12xM8 56
mcr Monsun 50 TH-50 504 700 280 541 950 30 12xM8 62
mcr Monsun 56 TH-56 564 760 315 605 950 22.5
16xM8 69
mcr Monsun 63 TH-63 634 830 355 674 950 22.5
16xM8 78
mcr Monsun 71 TH-71 716 960 400 751 1400 22.5
16xM8 122
mcr Monsun 80 TH-80 806 1050 450 837 1400 15 24xM10
138
mcr Monsun 90 TH-90 906 1150 500 934 1400 15 24xM10
155
mcr Monsun 100 TH-100 1006 1250 560 1043 1400 15 24xM10
170
mcr Monsun 112 TH-112 1126 1370 480 1190 1400 15 24xM12
200
mcr Monsun 125 TH-125 1256 1500 480 1320 1400 15 24xM12
250
Type DS nozzle with safety mesh
the nozzle with safety mesh is made of galvanized steel sheet. The product is designed to equalize the air
stream entering the fan.
Dysza ssawna osiatkowana DS
wentylator - typ typ D [mm] A [mm] ~C [mm] B [mm] nxd [mm] E [mm]
mcr Monsun 35 DS-35 355 425 500-700 395 8x10 [co 45 °] 80-200
mcr Monsun 40 DS-40 400 470 540-740 438 12x10 [co 30 °] 80-200
mcr Monsun 45 DS-45 450 520 590-790 487 12x10 [co 30 °] 80-200
mcr Monsun 50 DS-50 500 570 640-840 541 12x10 [co 30 °] 80-200
mcr Monsun 56 DS-56 560 640 710-910 605 16x11 [co 22,5 °] 80-200
mcr Monsun 63 DS-63 630 710 800-1000 674 16x11 [co 22,5 °] 100-300
mcr Monsun 71 DS-71 710 790 890-1090 751 16x11 [co 22,5 °] 100-300
mcr Monsun 80 DS-80 800 875 900-1200 837 24x11 [co 15 °] 100-300
mcr Monsun 90 DS-90 900 975 1000-1300 934 24x11 [co 15 °] 100-400
mcr Monsun 100 DS-100
1000 1080 1100-1400 1043 24x11 [co 15 °] 100-400
mcr Monsun 112 DS-112
1120 1240 1220-1500 1190 24x14 [co 15 °] 150-500
mcr Monsun 125 DS-125
1250 1370 1350-1600 1320 24x14 [co 15 °] 150-500

11/19
Type WO outlet nozzle with safety mesh
the nozzle with safety mesh is made of galvanized steel sheet. The product is designed to equalize the air
stream exhaust from the fan.
Type WO outlet nozzle with safety mesh
wentylator – typ typ D [mm] A [mm] B [mm] nxd [mm] L [mm]
mcr Monsun 35 WO-35 355 425 395 8x10 [co 45 °] 1D-3D
mcr Monsun 40 WO-40 400 470 438 12x10 [co 30 °] 1D-3D
mcr Monsun 45 WO-45 450 520 487 12x10 [co 30 °] 1D-3D
mcr Monsun 50 WO-50 500 570 541 12x10 [co 30 °] 1D-3D
mcr Monsun 56 WO-56 560 640 605 16x11 [co 22,5 °] 1D-3D
mcr Monsun 63 WO-63 630 710 674 16x11 [co 22,5 °] 1D-3D
mcr Monsun 71 WO-71 710 790 751 16x11 [co 22,5 °] 1D-3D
mcr Monsun 80 WOS-80 800 875 837 24x11 [co 15 °] 1D-3D
mcr Monsun 90 WO-90 900 975 934 24x11 [co 15 °] 1D-3D
mcr Monsun 100 WO-100 1000 1080 1043 24x11 [co 15 °] 1D-3D
mcr Monsun 112 WO-112 1120 1240 1190 24x14 [co 15 °] 1D-3D
mcr Monsun 125 WO-125 1250 1370 1320 24x14 [co 15 °] 1D-3D
Type WS service switch
Designed to cut-off electric power from the fan when inspection or maintenance work is necessary. Each
service switch features an auxiliary contact which indicates the power off position.
Install the service switch at a minimum distance of 9 cm from the fan body, i.e. on a console attached to
e.g. the casing flange.
The 3-pole service switch is designed for motors rated at 230/400 V [single-speed versions].
The 6-pole service switch is designed for single- and two-speed motors rated at 400/690 V and two-speed
motors rated at 230/400 V.
Connection: 3-pole switch Connection: 6-pole switch
Type WS service switch
Type A [mm]
B [mm]
E [mm]
F [mm]
H [mm]
nxd [mm] U
[V]
I
[A] Glands [D] Comments
WS-16/3 90 90 67 48 95 4x4 690 16 M20[x4] 3-pole
WS-16/6 90 90 67 48 95 4x4 690 16 M20[x4] 3-pole
WS-32/6 116 100 90 52 108 4x4 690 32 M25[x4] 6-pole
WS-63/6 170 155 105 95 185 4x6 690 63 M25/M32[x4] 6-pole
WS-100/6 200 180 130 125 200 4x6 690 100
M32/M40[x4] 6-pole
Service switch
Service switch

12/19
Type AM/BM vibration damper
cap-type vibration damper. The fitting is designed for flexible anchoring of the fan on the substrate, level
the equipment and limit the transmission of vibrations to the substrate [by accumulating the vibration
energy].
The vibration dampers are bolted to type SW bottom feet or type PP vertical support holders.
Type AM/BM vibration damper
wentylator - typ typ Amm]
B[mm]
C[mm]
E[mm]
F[mm]
M S[mm]
d[mm]
m[kg]
mcr Monsun 35 AM-35
136 80 108 85 135 M12
7 10 0,6
mcr Monsun 40 AM-40
mcr Monsun 45 AM-45
mcr Monsun 50 AM-50
mcr Monsun 56 AM-56
mcr Monsun 63 AM-63
mcr Monsun 71 AM-71
mcr Monsun 80 AM-80
mcr Monsun 90 AM-90
mcr Monsun 100 AM-100
mcr Monsun 112 AM-112
mcr Monsun 125 AM-125

13/19
6. IDENTIFICATION
MARKING_______________________________________________________
Example of smoke exhaust fan identification:
mcr Monsun - 50 / 4 - 1.5 - 5 / F400
7. INSTALLATION_____________________________________________
The mcr Monsun smoke exhaust axial fan is designed for vertical and horizontal installation. The
equipment can be installed indoors or outdoors.
7.1. Pre-assembly inspection____________________________________________________
Each smoke exhaust fan is factory inspected by the manufacturer prior to packing and shipping. Upon
unpacking the delivered smoke exhaust fan, visually examine it for any damage in transport.
The motor shaft should rotate with the rotor without evident resistance or scraping.
7.2. Location and assembly_______________________________________________________
The mcr Monsun smoke exhaust fan can be installed horizontally or vertically. Prior to installation, verify
the load bearing capacity of the roof, floor, wall or ceiling where the equipment is to be located.
If the smoke exhaust fan is to be installed vertically on a roof, prepare and secure an opening in the roof
slope at a diameter that fits the equipment. Set a special roof fan base over and aligned with the opening,
and suitable for the roof type, the fan weight and the fan diameter. Level out and anchor the roof fan base
to the roof slope. Put the fan on the roof fan base. Fasten both the equipment to the base with bolts.
Secure the fan exhaust with a roof exhaust vent assembly to prevent rain water and snow from entering
the building through the ducting.
When installing the smoke exhaust fan vertically on a baseplate, put the equipment on type PP vertical
support. It is recommended to bolt vibration dampers to the support in order to reduce the vibration from
the fan operation.
When installing the smoke exhaust fan horizontally, fasten type SW bottom feet to the fan housing flange
with bolts. Set the finished assembly on previously prepared vibration dampers, which have been
previously anchored to the substrate or a framework. The anchor and bolt diameter and length must match
the equipment size.
When installing the smoke exhaust fan below a ceiling, do this on a suitable support structure. Install the
vibration dampers and bottom feet on the support structure, then place the smoke exhaust fan there. The
anchor and bolt diameter and length must match the equipment size.
Connecting the smoke exhaust fan to the (smoke exhaust) ventilation system:
Connect the ventilation duct to the smoke exhaust fan via type PK counterflanges. Use type KD flexible
joints, which need to be fastened to the smoke exhaust fan to reduce the vibration transmission to the
ducting. This assembly is installed by sealing the joint interfaces [with high-temperature silicone] and
tightening the two parts with the bolts sized according to the fan size. The ventilation duct must not exert
loads on the smoke exhaust fan or other components of the assembly. The ventilation duct must be
supported by independent bearing slings. If the suction and forcing is free-flow, secure the smoke exhaust
fan intake and exhaust with type SO safety mesh. If the smoke exhaust fan is operated within a ventilation
Fire resistance class
Rotor blade angle
Motor power [kW]
No. of pole pairs
Fan nominal diameter [x10 mm]
Product commercial name

14/19
system, secure the intake and exhaust sides from entrainment of foreign bodies or accidental entry of
persons, animals, etc.
When installing the smoke exhaust fan, secure the installation site and all involved structures, and prepare
passage and access ways for all personnel not involved in the installation. The smoke exhaust fan must
be assured to enable inspection and servicing.
Example horizontal installation of the smoke exhaust fan
Notes:
Secure the system against entrainment of foreign bodies and accidental entry of persons, animals, etc.
Ensure that the fan is aligned with the system components.
The automatic non-return damper must be levelled for good performance.
Install a straight duct section with a min. length of 2.5xD on the fan pressure side.
Seal the system joints with silicone or other high-temperature compound.
Example vertical installation of the smoke exhaust fan
Notes:
The support structure must carry the load of the fan weight
Counterflanges
Seal with HT silicone
Vibration damper Vibration damper
Direction of flow
Ventilator foot
Vibration damper
Automatic non
-return damper
Installation over the
ceiling
Floor
Floor
System/flexible joint
Type PP vertical
support
Type AM vibration
damper
Support structure
Installation under the
ceiling
[Not offered]
Type PP vertical
support
Type AM vibration
damper
Installation with a non-
return damper
Type KS-
V
automatic non
-
return damper
Roof fan base
[Sockle]

15/19
Example installation of accesories
7.3. Electrical connections_____________________________________________________
Having properly located, placed and fastened the smoke exhaust fan, connect the equipment to the
relevant electrical system wiring. Lead the wiring through the gland and into the electric box on the fan
housing; then connect the wiring to the terminals according to the diagram shown in the box. The electrical
wire with the proper fire resistance rating is installed in standard by the manufacturer between the fan
motor and the electric box. Each fan motor must be connected to the electrical power system over a safety
switch. The safety level must be present according to the nominal current draw of the fan motor. The
protective earth shall be made according to relevant electrical engineering standards.
Once the smoke exhaust fan has been commissioned as a part of the system, measure the current draw
and verify that it meets the motor rating plate data. The smoke exhaust fan current draw in steady operation
must not exceed 1.1 times the current ratings.
The electrical power supply from the control cabinet to the fan power junction box must guarantee
uninterrupted operation in the case of a fire. This can be achieved with high temperature resistant wiring
or with protective tubing and proper safe routing of the electrical power system. No external
service/maintenance switches are to used, which is to prevent inadvertent shutdown of the smoke exhaust
fan (with the sole exception of the fan-dedicated service switch with remote indication of current circuit
switching). The smoke exhaust fan control cabinets must be powered directly from mail switchboards with
guaranteed uninterrupted power supply, even if the entire building is cut off from the power grid. If a main
fireman's switch is installed to isolate power from the entire building, the smoke exhaust fan power supply
must be independent from that solution and assure normal operation in the case of a fire.
If the system uses the service switch, install it outside of the fan casing, i.e. at a min. distance of 9 cm,. on
a bracket bolted to e.g. the fan casing flange [see the figure below].
Type PK counterflanges
Seal with HT silicone
Type KD flexible joint Type KD flexible joint
Direction of flow
Type SW bottom foot
Type AM vibration
damper
Type KS automatic non-return
damper

16/19
Electrical wiring connections must only be made by electricians with valid licenses.
Connections for 230/400V motors Connections for 400/690V motors
7.4. Commissioning____________________________________________________________
Before commissioning your installed smoke exhaust fan, do the following:
Check that the smoke exhaust fan is properly and firmly fastened.
Check all seals for tightness.
Check that all electrical wiring is properly and firmly connected.
Check that the phase connection sequence and PE/neutral wiring is properly connected.
Check that the smoke exhaust fan and its connected ducting are free of foreign bodies.
Check that all protective/safety components have been installed.
If the checks are positive, start the fan and do a functional test.
When starting the smoke exhaust fan, verify the motor sense of rotation against the direction arrow
on the enclosure.
8. TRANSPORT & STORAGE CONDITIONS __________________________
During transport and storage, the mcr Monsun smoke exhaust fans are placed on pallets. Do not topple
or throw the packaging during loading and transport. The smoke exhaust fans can be handled and shipped
on any means of transport, provided that they are secured against weather and elements. The smoke
exhaust fans on transport vehicles must be secured against shifting. Visually inspect each piece of
equipment following transport and handling.
Store in sheltered rooms, where:
there is no exposure to dust particulates, gases, corrosive vapours and other aggressive
chemical emissions detrimental to insulation parts and structural components of the ventilator
and/or its motor;
the maximum relative humidity is 80% at +20°C;
the ambient temperature does not exceed the range of -20ºC to + 40ºC;
no vibrations are present.
Type WS service switch
Type WW service switch
console
Ventilator flange
Bolted joint
Min. 9
cm

17/19
9. SAFETY MANUAL________________________________________________
Read and understand this Technical Manual before commissioning and servicing the product.
The smoke exhaust fan is not hazardous when firmly attached to a ventilation system and the ventilator
support structure.
Make the electrical connections according to the enclosed electrical wiring diagram and the guidelines in
Section 7.3. Electrical connections shall be made by personnel with relevant qualifications which have
been certified as required by current laws.
Inspect the PE wire connection of the smoke exhaust ventilator during the operating life.
Disconnect the smoke exhaust fan from electrical power before any inspections or checks.
CAUTION:
1. Do not clean smoke exhaust fans of deposits with pressure or steam washers.
2. Loss of seal at the fan connections or flexible ends may result in hazards due to
release of the forced medium and requires immediate replacement of leaking components.
If the equipment is malfunctioning (e.g. excessive noise, vibration and/or erratic operation is found),
disconnect the fan from electrical power supply, and call the manufacturer's technical service or an
inspection and repair contractor authorised by the manufacturer.
10. MAINTENANCE & SERVICING____________________________________
The equipment from “Mercor” SA require periodic technical inspection and maintenance at least every 12
months throughout its operating life, i.e. during the warranty and post-warranty period. Inspection and
maintenance may only be carried out by the manufacturer or contractors authorised by “Mercor” SA to
service its products.
Regular service inspections of fire protection equipment is mandatory in Poland according to § 3 Section
3 of the Polish Regulation of the Ministry of the Interior and Administration of 7 June 2010 on the fire
protection of buildings, other structures and areas (Polish Journal of Laws, Year 2010, No. 109 Item 719).
Do these recommended actions in the inspection intervals:
Check the electrical connections, especially for all mechanical damage.
Check the equipment casing, especially for all mechanical damage.
Check for any obstructions to proper performance of the equipment.
To facilitate the activities under service inspection, servicing and warranty claim response, e.g. visual
inspection or repairs, the equipment user/operator shall provide physical access to the equipment by
removing thermal insulation, suspended ceiling, and other installations, as required and applicable to
warrant unobstructed access.
In the case of roof mounted equipment, provide access to the area (via ladders or elevated platforms).
If the equipment is only operated for smoke exhaust during fire, test run it for ca. 10 minutes every 3
months.
Refer all matters related to technical inspection, maintenance and servicing of this equipment to the
“Mercor” SA Service Department, serw[email protected], tel. +48 58 341 42 45 ext. 170, fax: +48 58 341
39 85, from 8 AM to 4 PM (Mo-Fri).
11. WARRANTY TERMS & CONDITIONS _________________________
1. “MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase,
unless the sales contract states otherwise.
2. Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty
eligible defect
3. Submit warranty claims by calling at: tel. +48 58 341 42 45, by fax: +48 58 341 39 85, by e-mail:
[email protected]m.pl or by traditional mail: “MERCOR” SA, ul. Grzegorza z Sanoka 2, 80-408
Gdańsk, Poland.
4. If physical defects of equipment are found during the warranty period, “MERCOR” SA warrants and
represents to remove them in shortest possible time from serving the written warranty claim with the
proof of purchase or sales contract, subject to Item 10.

18/19
5. “MERCOR” SA has the right to extend the time of repair if the defect removal is complicated or
requires purchase of custom components or spare parts.
6. The warranty liability only covers all defects arising from causes present in the equipment at the date
of sale.
7. Defects caused by improper operation or otherwise as listed in Item 10 herein, the buyer / warranty
beneficiary will be charged with the costs of their removal.
8. Condition for rectifying defects is that the applicant makes the site/localisation where devices are
installed available, in particular, ensuring: the lift in the case of devices mounted at a height above
3m, free access to the rooms where the devices were installed and necessary revisions, dismantling
thermal insulation, disassembling suspended ceilings, disassembling other installations, if they
prevent free access to the device.
9. If the device can not be repaired at the place of its installation, "MERCOR" SA reserves the necessity
of its disassembly, possible delivery to the address indicated by "MERCOR" SA and re-assembly.
The cost of this operation lies with the buyer / holder of the guarantee.
10. The warranty does not cover:
Any damage or failure of the equipment caused by improper operation, tampering, failure to
conduct periodic technical inspection and/or maintenance established in the Operating and
Maintenance Manual, section “SERVICING AND MAINTENANCE”.
Any damage beyond reasonable control of “MERCOR” SA, and specifically: caused by force
majeure, such as torrential rainfall, flooding, hurricanes, inundation, lightning strike, power grid
overvoltage, explosion, hail, collision with aircraft, fire, avalanche, landslide and indirect
damage due to those causes. Torrential rainfall is understood as any rainfall with the
effectiveness factor of 4 or higher in accordance with the definition of the Polish Institute of
Meteorology and Water Management - National Research Institute (IMGW-PIB). If the
effectiveness factor value specified in the preceding sentence cannot be reasonably
established, the actual condition and extent of damage shall be considered at the site of their
origin as the action of torrential rain. Hurricane is understood as any wind with a minimum
speed of 17.5 m/s (and damage shall be recognised as caused by hurricanes if the effects of
such weather phenomenon has been found in the direct vicinity of the damaged property).
Damage due to failure to immediately report any defect found.
Deterioration in the quality of coatings due to natural weathering/ageing.
Defects caused by abrasive or aggressive cleaning agents.
Damage caused by aggressive external influence, specifically chemical or biological in nature,
or when the origin of which is related to the production processing or activity carried out within
the facility protected by the equipment or in its direct vicinity.
Wearing parts and consumables (e.g. gaskets/seals), unless they have defects of
workmanship and/or material.
Damage caused by improper transport, handling, unloading and/or storage of the equipment.
Damage caused by installation of the equipment in violation of this Operating and Maintenance
Manual and/or good construction practice.
The equipment and/or parts thereof with removed or damaged nameplate (rating plate) and/or
warranty seals.
11. The buyer/warranty rights holder is required to operate the equipment properly and carry out
technical inspection and maintenance in accordance with the section “MAINTENANCE AND
SERVICING” in the following Operating and Maintenance Manual.
12. This warranty shall be made immediately void and null if:
The buyer/warranty rights holder modifies the product design without prior authorisation from
“MERCOR” SA.
Periodic technical inspection and/or maintenance is not carried out per schedule and/or is
carried out by unauthorised personnel or service providers not authorised to do so by
“MERCOR” SA and/or the equipment has not been properly operated.
Unauthorised personnel attempts any intervention in the product outside of the normal
operation and maintenance of this equipment.
13. Any circumstances listed in Item 10 will relieve “MERCOR” SA from the obligation of surety.
The relevant provisions of the Polish Civil Code shall apply to all matters not regulated in these Warranty Terms & Conditions.

19/19
FAN MEASUREMENT REPORT
FAN TYPE
SERIAL NUMBER
INSTALLATION SITE
RATED CURRENT
Once the fan has been installed at its intended operating site and all electrical connections have
been made, immediately measure the current draw in steady-state operation of the equipment.
MEASUREMENT RESULTS [A]
U1 V1 W1 U2 V2 W2
NOTES:
Full name of the measuring technician Date measured Signature
Return this Report immediately after completion of measurements to:
“MERCOR” SA
Fire Ventilation Systems
Ul. Grzegorza z Sanoka 2
80-408 Gdańsk
and not later than in 8 weeks from the date of equipment purchase (equivalent to the date of the VAT
sales invoice).
THE EQUIPMENT WARRANTY BECOMES ENFORCEABLE UPON RETURN OF THIS
MEASUREMENT REPORT
This manual suits for next models
3
Table of contents
Other mercor Fan manuals
Popular Fan manuals by other brands

Black & Decker
Black & Decker FD1600 user manual

Americ Corporation
Americ Corporation VAF-8000 owner's manual

Monte Carlo Fan Company
Monte Carlo Fan Company 5YK60 Series Owner's guide and installation manual

Ruck Ventilatoren
Ruck Ventilatoren KVT Series Assembly instruction

Hunter
Hunter 22438 Manual de Installatión y Operatión

Vent-Axia
Vent-Axia HR100R Installation and servicing instructions