Doc# 1870872 • REV A (January 2018) Page 7 of 7
2.9 Create a chain of requests to scan all the registers you want to poll from DA-
TAWATCH.
2.10 Create register chain in your PLC conguraon soware and start to monitor or
control the parameters in your applicaon.
The most common registers if 8 channels are used, please consult Metrix customer service for any ques-
on.
Parameter Descripon Type Address
(Hex)
Address
(Decimal)
Channel.1.Main.Measured Value Measured value oat32 0X1814 6164
Channel.1.Main.PV The process variable (output) of the channel oat32 0X0100 256
Channel.1.Main.PV2 The secondary input process variable (ouput) of
the channel
oat32 0X0110 272
Channel.2.Main.Measured Value Measured value oat32 0X1894 6292
Channel.2.Main.PV The process variable (output) of the channel oat32 0X0104 260
Channel.2.Main.PV2 The secondary input process variable (ouput) of
the channel
oat32 0X0114 276
Channel.3.Main.Measured Value Measured value oat32 0X1914 6420
Channel.3.Main.PV The process variable (output) of the channel oat32 0X0108 264
Channel.3.Main.PV2 The secondary input process variable (ouput) of
the channel
oat32 0X0118 280
Channel.4.Main.Measured Value Measured value oat32 0X1994 6548
Channel.4.Main.PV The process variable (output) of the channel oat32 0X010c 268
Channel.4.Main.PV2 The secondary input process variable (ouput) of
the channel
oat32 0X011c 284
VirtualChannel.1.Main.ModbusInput Modbus input value oat32 0X1c06 7174
VirtualChannel.2.Main.ModbusInput Modbus input value oat32 0X1c86 7302
VirtualChannel.3.Main.ModbusInput Modbus input value oat32 0X1d06 7430
VirtualChannel.4.Main.ModbusInput Modbus input value oat32 0X1d86 7558