MG R7F4DH-1-DAC16B User manual

EM-7799-F Rev.5 P. 1 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Discrete I/O module ............................................................(1)
DIN rail mounter slider......................................................(2)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVE
• Use dual-shield cables (Shinko Seisen Industry Model
ZHY262 PBA) for the network. If it is not sufficient, use
a ferrite core (Kitagawa Industries Model GRFC-13) for
the network cable.
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V DC ±10%, approx. 35mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply, input signal and output signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
NPN DISCRETE INPUT & PNP TRANSISTOR OUTPUT
MODULE, 8 points each
(High-speed Link System, e-CON connector)
MODEL
R7F4DH-1-DAC16B

R7F4DH-1-DAC16B
EM-7799-F Rev.5 P. 2 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
■FRONT VIEW
Power
×10×1
HLS1 HLS2
Run
Status Indicator LED
Station Address Setting Rotary SW
Power Supply / Sensor Exc. Connectors
I/O Connector
Discrete I/O Status Indicator LED
RJ-45 Modular Jack for HLS
Operating Mode Setting DIP SW (SW1)
Terminating Resistor SW
SW1
STATION ADD.
O
N
1
2
3
4
5
6
7
8
SW1
TERM
ON
ON
PWR
+
--
+
FE
SNSR.EXC
ON
■STATUS INDICATOR LED
ID COLOR FUNCTION
Power Green Turns on when the internal 5V is supplied
normally.
Run Green Turns on when the refresh data is received
normally.
■DISCRETE I/O STATUS INDICATOR LED
LED indicators show the signal status.
ON : LED ON (red)
OFF : LED OFF
■STATION ADDRESS
The left switch determines the sixteenths place digit, while
the right switch does the ones place digit of the address.
(Range: 01H to 3FH)
Station Address Setting (x1)
Station Address Setting (x16)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
■OPERATING MODE
(*) Factory setting
• Transfer rate (SW1-1, 1-2)
SW1-1 SW1-2 TRANSFER RATE
OFF OFF 12Mbps (*)
ON OFF 6Mbps
OFF ON 3Mbps
• Output at the loss of communication (SW1-3)
SW1-3 OUTPUT AT THE LOSS OF COMMUNICATION
OFF Hold the output (*)
(maintains the last data received normally)
ON Reset the output (turned off)
Note: Be sure to set unused SW1-4 through 1-8 to OFF
■TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)

R7F4DH-1-DAC16B
EM-7799-F Rev.5 P. 3 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■POWER SUPPLY
Cable connector
: TFMC1,5 / 5–STF–3,5
(Phoenix Contact) (included in the package)
Applicable wire size
:
0.2 − 1.5 mm2;stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm
2(Phoenix Contact)
• AI0,34−10TQ 0.34 mm
2(Phoenix Contact)
• AI0,5−10WH 0.5 mm
2(Phoenix Contact)
• AI0,75−10GY 0.75 mm
2(Phoenix Contact)
• A1−10 1.0 mm
2(Phoenix Contact)
• A1,5−10 1.5 mm
2(Phoenix Contact)
1
2
3
4
5
1. PWR+
2. PWR–
3. FE
4. SNSR.EXC+
5. SNSR.EXC–
Power Supply
Power Supply
Functional earth
Sensor excitation
Sensor excitation
Note: The numbers marked on the connector have no relationship
to the pin number of the unit.
Wire according to the instruction manual of the unit.
1. NC
2. NC
3. TXD+
4. TXD–
5. RXD+
6. RXD–
7. NC
8. SLD
Unused
Unused
Network (slave, transmission +)
Network (slave, transmission –)
Network (master, transmission +)
Network (master, transmission –)
Unused
Shield
■NETWORK
Recommended cable connector
: TM21P–88P (Hirose Electric)
(not included in the package)
• Full-duplex communication
• Half-duplex communication
12345678
12345678
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD
Unused
Unused
Network (+)
Network (–)
Unused
Unused
Unused
Shield
■TERMINAL ASSIGNMENTS
• I/O Connection
Reccommended cable connector: 37104-( )-000FL (3M Company)
(The cable connector is not included in the package. Specify
wire size instead of ( ); refer to the specifications of the prod-
uct)
1
2
3
4
2
3
4
1
2
3
4
X0 X1 X2 X3 X4 X5 X6 X7
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
PIN
No. ID FUNCTION PIN
No. ID FUNCTION
X0 1 +24V 24V DC Y0 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X0 Input 0 4 X8 Output 0
X1 1 +24V 24V DC Y1 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X1 Input 1 4 X9 Output 1
X2 1 +24V 24V DC Y2 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X2 Input 2 4 XA Output 2
X3 1 +24V 24V DC Y3 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X3 Input 3 4 XB Output 3
X4 1 +24V 24V DC Y4 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X4 Input 4 4 XC Output 4
X5 1 +24V 24V DC Y5 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X5 Input 5 4 XD Output 5
X6 1 +24V 24V DC Y6 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X6 Input 6 4 XE Output 6
X7 1 +24V 24V DC Y7 1 +24V 24V DC
2 NC Unused 2 NC Unused
3 GND 0V 3 GND 0V
4 X7 Input 7 4 XF Output 7

R7F4DH-1-DAC16B
EM-7799-F Rev.5 P. 4 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING INSTRUCTIONS
■DIN RAIL MOUNTING (PARALLEL)
• Mounting
1) Set the upper hook at the rear side of the unit on the DIN
rail.
2) Push in the lower.
1
2
• Dismounting
1) Push down the DIN rail mounter slider with tip of a mi-
nus screwdriver.
2) Pull the lower of the unit.
3) Remove the upper hook of the unit from the DIN rail.
1
2
3
■DIN RAIL MOUNTING (RIGHT ANGLE)
• Mounting
1) Insert the longer DIN rail mounter slider until it clicks
twice, as shown below.
1
2) Set the upper hook at the rear side of the unit on the DIN
rail.
3)Push in the lower.
2
3
• Dismounting
1) Push down the DIN rail mounter slider with tip of a mi-
nus screwdriver.
2) Pull the lower of the unit.
3) Remove the upper hook of the unit from the DIN rail.
1
2
3
■SURFACE MOUNTING
1) Insert the two DIN rail mounter sliders until it clicks
once, as shown below.
1
1
2) Mount the unit with M4 screws referring the External
Dimensions. (Torque: 1.4 N∙m)

R7F4DH-1-DAC16B
EM-7799-F Rev.5 P. 5 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
115 (4.53) 35 (1.38)
36.5 (1.44)123 (4.84)
DIN RAIL
35mm wide
4 (.16)
50 (1.97)5 (.20)
138 (5.43)
3 (.12)
2
-
4.3 dia. 4 deep
(2
-
1.17 dia. 0.16 deep)
■CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
SLD
NC
NC
NC
TXD+ (TR+)
TXD−(TR–)
RXD+ (NC)
RXD−(NC)
TXD+ (TR+)
TXD−(TR–)
RXD+ (NC)
RXD−(NC)
HLS1
1
2
4
3
6
5
8
7
SLD
NC
NC
NC
HLS2
1
2
4
3
6
5
8
7
SNSR.EXC+
SNSR.EXC–
FE
PWR–
PWR+
1
2
4
5
3
POWER SUPPLY (IN)
SENSOR EXC. (IN)
SNSR.EXC+
SNSR.EXC–
FE
PWR–
PWR+
1
2
4
5
3
POWER SUPPLY (OUT)
SENSOR EXC. (OUT)
X0
GND
NC
GND
NC
+24V
INPUT X0
1
2
4
3
X7
+24V
1
2
4
3INPUT X7
1
2
4
3OUTPUT Y0
Y0
GND
NC
1
2
4
3OUTPUT Y7
Y7
GND
NC
+24V
Detecting
Circuit
Detecting
Circuit
:
:
:
:
■2-Wire Sensor
Xn
GND
NC
+24V
1
2
4
3
Detecting Circuit

R7F4DH-1-DAC16B
EM-7799-F Rev.5 P. 6 / 6
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING REQUIREMENTS unit: mm (inch)
125 (4.92)
2–M4
COMMUNICATION CABLE CONNECTIONS
Master Module
RXD+
RXD−
TXD+
TXD−
SLD
Slave Module
RXD+
RXD−
TXD+
TXD−
SLD
Slave Module
Terminating
Resistor
Terminating
Resistor
Terminating
Resistor
TXD+
TXD−
RXD+
RXD−
SHIELD
Master Module
TR+
TR−
SLD
Slave Module
TR+
TR−
SLD
Slave Module
Note: Be sure to turn ON the switch of the terminating resistor located at both ends of the modules.
TR+
TR−
SHIELD
• Full-duplex communication
• Half-duplex communication
■MASTER CONNECTION
Terminating
Resistor
I/O DATA DESCRIPTIONS
■DISCRETE I/O (16 points)
Unused Unused
07815 015 87
• Di
• Do
Output 0
Output 1
Output 2
Output 3
Output 7
Input 0
Input 1
Input 2
Input 3
:
:
Input 7
:
:
0: OFF
1: ON