MG M8YC1 User manual

BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• Functional insulation is maintained between the input
and output.
• The equipment must be mounted inside a panel.
• The actual installation environments such as panel
configurations, connected devices, connected wires, may
affect the protection level of this unit when it is inte-
grated in a panel system. The user may have to review
the CE requirements in regard to the whole system and
employ additional protective measures* to ensure the
CE conformity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 50mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within 0 to 55°C (32
to 131°F) with relative humidity within 30 to 95% RH in
order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Specifications
Span Adj.
Zero Adj.
Mounting Screw
Body
INSTALLATION
Use Installation Base (model: M8BSx).
CONTROL OUTPUT ISOLATOR
(CE) MODEL M8YC1
EM-5387 Rev.2 P. 1 / 2
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
I/O PINS
17.5 (.69)
48 (1.89)
75 (2.95)
83 (3.27)
■CONNECTION DIAGRAM
+
–
Installation Base
OUTPUT
1
2
A
B
10
11
+
–
POWER
9
6
7
8
+
–
INPUT
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input: Check the power input voltage.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.
M8YC1
EM-5387 Rev.2 P. 2 / 2
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Other MG Industrial Equipment manuals

MG M8YS1 User manual

MG

MG M8YS1 User manual

MG M60EYV User manual

MG

MG M60EYV User manual

MG M2BS-16U1 User manual

MG

MG M2BS-16U1 User manual

Popular Industrial Equipment manuals by other brands

Watkiss Vario operating manual

Watkiss

Watkiss Vario operating manual

Thomas Alpha Plus user guide

Thomas

Thomas Alpha Plus user guide

CLEAN ROOM DEVICES CRD500SS Operation manual

CLEAN ROOM DEVICES

CLEAN ROOM DEVICES CRD500SS Operation manual

Hunter A2C-LTEM installation guide

Hunter

Hunter A2C-LTEM installation guide

Graco 24H853 Repair instructions

Graco

Graco 24H853 Repair instructions

Venmar HRV2000i Start-up

Venmar

Venmar HRV2000i Start-up

Cascade TFC Raymond 4150 installation instructions

Cascade

Cascade TFC Raymond 4150 installation instructions

ABB HT578726 Operation manual

ABB

ABB HT578726 Operation manual

ABB HT611036 Operation manual

ABB

ABB HT611036 Operation manual

HEUTE ProfilGate i45 aqua operating manual

HEUTE

HEUTE ProfilGate i45 aqua operating manual

WATSON INDUSTRIES AHRS-S305 owner's manual

WATSON INDUSTRIES

WATSON INDUSTRIES AHRS-S305 owner's manual

CBE 230 Installation, operation & maintenance instructions

CBE

CBE 230 Installation, operation & maintenance instructions

Paradyne Hotwire 8775 installation instructions

Paradyne

Paradyne Hotwire 8775 installation instructions

FRIEND FW-6610A product manual

FRIEND

FRIEND FW-6610A product manual

GSi VersaLoop 8 owner's manual

GSi

GSi VersaLoop 8 owner's manual

HBM MP55DP operating manual

HBM

HBM MP55DP operating manual

TriangleTube Instinct 110 instruction manual

TriangleTube

TriangleTube Instinct 110 instruction manual

Trumpf Track&Trace installation manual

Trumpf

Trumpf Track&Trace installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.