MG 18PF User manual

EM-1868 Rev.2 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
POWER FACTOR TRANSDUCER MODEL 18PF
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 80mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
Specifications
Front Cover
(Connection diagram
behind)
■FRONT VIEW (with cover open)
Span Adj.
Zero Adj.
1
78
56
2
34
INSTALLATION
Use Standard Rack (model: 18BXx or 18KBXx).
18PF
EM-1868 Rev.2 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram behind the front cover.
■EXTERNAL DIMENSIONS unit: mm (inch)
110 (4.33 )
93 (3.66)
24 (.94)
7 (.28)
78 (3.07)32 (1.26)
8–M3.5
SCREW
7 (.28)
2–M3
SCREW
■CONNECTION DIAGRAM
6
5
1
2
■3-PHASE/3-WIRE
CONNECTOR
LOAD
123
SOURCE
P3U
P2V
u
v
FUSE VT
k
l
CT
L
K
1L
1S
OUTPUT 1
OUTPUT 2
POWER
■TERMINAL ASSIGNMENTS
12
34
78
56
18PF
EM-1868 Rev.2 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage supplied to the rack
(model: 18BXx or 18KBXx). For the DC power source, be
sure that the ripple level is within 10% p-p.
3) Voltage input: Check that the input shows within 85 –
120% of the rated voltage.
4) Current input: Check that the input shows within 10 –
120% of the rated current.
5) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT 1
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
5) No need of adjustments for the Output 2.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other MG Transducer manuals

MG 18RP User manual

MG

MG 18RP User manual

MG 18WT User manual

MG

MG 18WT User manual

MG LTRPN User manual

MG

MG LTRPN User manual

MG 17CE User manual

MG

MG 17CE User manual

MG W2PV User manual

MG

MG W2PV User manual

MG L2PNA User manual

MG

MG L2PNA User manual

MG LTWT User manual

MG

MG LTWT User manual

MG MUWT User manual

MG

MG MUWT User manual

MG LPAUN User manual

MG

MG LPAUN User manual

Popular Transducer manuals by other brands

Clark Synthesis TST239 datasheet

Clark Synthesis

Clark Synthesis TST239 datasheet

Nexen WEB CONTROL EN40 user manual

Nexen

Nexen WEB CONTROL EN40 user manual

Copal PA-838-D Series instruction manual

Copal

Copal PA-838-D Series instruction manual

HB-THERM M8125-EN Assembly instructions

HB-THERM

HB-THERM M8125-EN Assembly instructions

Garmin ECHOMAP Ultra Series installation instructions

Garmin

Garmin ECHOMAP Ultra Series installation instructions

Airmar ST800 Owner's guide and installation instructions

Airmar

Airmar ST800 Owner's guide and installation instructions

novotechnik RSM-2800 user manual

novotechnik

novotechnik RSM-2800 user manual

Motorola PMLN6766 manual

Motorola

Motorola PMLN6766 manual

Daiichi Electronics SPTT2-92A-12 instruction manual

Daiichi Electronics

Daiichi Electronics SPTT2-92A-12 instruction manual

APG PT-500-P30 user manual

APG

APG PT-500-P30 user manual

S+S Regeltechnik PREMASGARD 711 Series Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik PREMASGARD 711 Series Operating Instructions, Mounting & Installation

Hummingbird XTH 9 20 P manual

Hummingbird

Hummingbird XTH 9 20 P manual

Balluff BTL7-A Series Condensed guide

Balluff

Balluff BTL7-A Series Condensed guide

Sifam Tinsley Theta 30P operating manual

Sifam Tinsley

Sifam Tinsley Theta 30P operating manual

S+S Regeltechnik PREMASGARD 1110 Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik PREMASGARD 1110 Operating Instructions, Mounting & Installation

Ashcroft IXLdp instruction sheet

Ashcroft

Ashcroft IXLdp instruction sheet

R/Evolution RV16 Installation & operation manual

R/Evolution

R/Evolution RV16 Installation & operation manual

Magtrol TM Series user manual

Magtrol

Magtrol TM Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.