MicroElektronika MC30-X/10-4 User manual

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
1
of
43
MICROPROCESSOR
OVERCURRENT and EARTH FAULT RELAY
TYPE
(Expansion Board)
OPERATION MANUAL

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
2
of
43
1. General Utilization and Commissioning Directions _________________________________________________________4
1.1 - Storage and Transportation______________________________________________________________________4
1.2 - Installation __________________________________________________________________________________4
1.3 - Electrical Connection ___________________________________________________________________________4
1.4 - Measuring Inputs and Power Supply _______________________________________________________________4
1.5 - Outputs Loading ______________________________________________________________________________4
1.6 - Protection Earthing ____________________________________________________________________________4
1.7 - Setting and Calibration _________________________________________________________________________4
1.8 - Safety Protection______________________________________________________________________________4
1.9 - Handling ____________________________________________________________________________________4
1.10 - Maintenance ________________________________________________________________________________5
1.11 - Waste Disposal of Electrical & Electronic Equipment __________________________________________________5
1.12 - Fault detection and repair ______________________________________________________________________5
2. General Characteristics _____________________________________________________________________________6
2.1 - Power Supply ________________________________________________________________________________6
2.2 - Operation and Algorithms _______________________________________________________________________7
2.2.1 - Reference Input Values _____________________________________________________________________7
2.2.2 - Input quantities ___________________________________________________________________________7
2.2.3 - Time Current Curves IEC (TU1029 Rev.0) _______________________________________________________9
2.2.4 - Time Current Curves IEEE (TU1028 Rev.0) _____________________________________________________10
3. Functions and Settings (Function) ____________________________________________________________________11
3.1 - T> (F49) - Thermal Image protection level_________________________________________________________11
3.1.1 - Thermal Image Curves (TU0445 Rev.0)________________________________________________________12
3.2 - I> (1F51) - First overcurrent protection level _______________________________________________________13
3.3 - I>> (2F51) - Second overcurrent protection level ___________________________________________________14
3.4 - IH (3F51) - Third overcurrent protection level ______________________________________________________15
3.4.2 –Automatic doubling or Overcurrent thresholds on current inrush ____________________________________15
3.5 - Io> (1F51N) - First Earth Fault protection level _____________________________________________________16
3.6 - Io>> (2F51N) - Second Earth Fault protection level __________________________________________________17
3.7 - IoH (3F51N) - Third Earth Fault protection level _____________________________________________________17
3.8 - BF (F51BF) - Breaker Failure____________________________________________________________________18
3.9 - I.R.F. - Internal Relay Failure ___________________________________________________________________18
3.10 - Osc - Oscillographic Recording _________________________________________________________________19
3.11 - Comm –Communication Parameters ____________________________________________________________20
3.12 - LCD –Display and Buzzer operation _____________________________________________________________20
4. Logic Blocking of Functions _________________________________________________________________________21
4.1 - Blocking Outputs _____________________________________________________________________________21
4.2 –Blocking Inputs______________________________________________________________________________21
5. Output Relays ___________________________________________________________________________________22
5.1 - RelayCfg (Relay Configuration only via Software “MSCom”) ____________________________________________22
5.1.1 –Output Relay ____________________________________________________________________________22
5.1.2 –“OutCfg” Outputs Configuration - via MSCom2 software ___________________________________________22
5.2 - Example: Change settings for “0.R1” _____________________________________________________________25
5.2.1 - “Output Config” __________________________________________________________________________25
5.2.2 - “Functions”______________________________________________________________________________25
5.2.3 - “OpLogic” _______________________________________________________________________________26
5.2.4 - “Output config”___________________________________________________________________________26
5.2.5 - “Timer”_________________________________________________________________________________27
6. Digital Inputs____________________________________________________________________________________28
6.1 –Digital Input on Main Module (Only via MSCom Software) _____________________________________________28
6.2 –Digital Input on Expansion Module (Optional and configured via MSCom Software)__________________________28
7. Self-diagnostic___________________________________________________________________________________28
8. Relay Management _______________________________________________________________________________29
9. Signalizations ___________________________________________________________________________________30
10. Keyboard Buttons _______________________________________________________________________________30
11. Serial Communication Port ________________________________________________________________________31
11.1 - Main RS485 Serial Communication Port __________________________________________________________31
11.2 - Communication Port on Front Face Panel _________________________________________________________32
12. Menu and Variables ______________________________________________________________________________33
12.1 - Real Time Measurements _____________________________________________________________________33
12.2 - Measure (Instantaneous Measurements) _________________________________________________________33
12.3 - Counter (Operation Counters)__________________________________________________________________33
12.4 - LastTrip (Event Recording) ____________________________________________________________________34
12.5 - R/W Set (Programming / Reading the Relay Settings) _______________________________________________35
12.5.1 - CommAdd (Communication Address)_________________________________________________________35
12.5.2 - Time/Date (Time/Date) ___________________________________________________________________35
12.5.3 - RatedVal (Rated Input Values) ______________________________________________________________35
11.5.4 - Function (Functions)______________________________________________________________________36
12.6 - Commands ________________________________________________________________________________37
12.7 - Info&Ver (Firmware - Info&Version) _____________________________________________________________37
13. Keyboard Operational Diagram _____________________________________________________________________38
14. Password ______________________________________________________________________________________39

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
3
of
43
14.1 - MS-Com Password___________________________________________________________________________39
15. Maintenance ___________________________________________________________________________________39
16. Power Frequency Insulation Test ____________________________________________________________________39
17. Connection Diagram _____________________________________________________________________________40
17.1 - Connection Diagram –Expansion Module –UX10-4 _________________________________________________40
18. Overall Dimensions ______________________________________________________________________________41
19. Direction for Pcb's Draw-Out and Plug-In _____________________________________________________________42
19.1 - Draw-Out _________________________________________________________________________________42
19.2 - Plug-In ___________________________________________________________________________________42
20. Electrical Characteristics __________________________________________________________________________43

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
4
of
43
1. General Utilization and Commissioning Directions
Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.
1.1 - Storage and Transportation
Must comply with the environmental conditions stated on the product's instruction or by the applicable IEC
standards.
1.2 - Installation
Must be properly made and in compliance with the operational ambient conditions stated by the Manufacturer.
1.3 - Electrical Connection
Must be made strictly according to the wiring diagram supplied with the Product, to its electrical
characteristics and in compliance with the applicable standards particularly with reference to human safety.
1.4 - Measuring Inputs and Power Supply
Carefully check that the value of input quantities and power supply voltage are proper and within the
permissible variation limits.
1.5 - Outputs Loading
Must be compatible with their declared performance.
1.6 - Protection Earthing
When earthing is required, carefully check its effectiveness.
1.7 - Setting and Calibration
Carefully check the proper setting of the different functions according to the configuration of the protected
system, the safety regulations and the co-ordination with other equipment.
1.8 - Safety Protection
Carefully check that all safety means are correctly mounted, apply proper seals where required and
periodically check their integrity.
1.9 - Handling
Notwithstanding the highest practicable protection means used in designing M.S. electronic circuits, the
electronic components and semiconductor devices mounted on the modules can be seriously damaged by
electrostatic voltage discharge which can be experienced when handling the modules.
The damage caused by electrostatic discharge may not be immediately apparent but the design reliability and
the long life of the product will have been reduced. The electronic circuits reduced by M.S. are completely safe
from electrostatic discharge (8 KV IEC 255.22.2) when housed in their case; withdrawing the modules
without proper cautions expose them to the risk of damage.
a.
Before removing a module, ensure that you are at the same electrostatic potential as the equipment by
touching the case.
b.
Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the
electronic components, printed circuit tracks or connectors.
c.
Do not pass the module to any person without first ensuring that you are both at the same electrostatic
potential. Shaking hands achieves equipotential.
d.
Place the module on an antistatic surface, or on a conducting surface which is at the same potential as
yourself.
e.
Store or transport the module in a conductive bag.
More information on safe working procedures for all electronic equipment can be found in BS5783
and IEC 147-OF.

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
5
of
43
1.10 - Maintenance
Make reference to the instruction manual of the Manufacturer ; maintenance must be carried-out by specially
trained people and in strict conformity with the safety regulations.
1.11 - Waste Disposal of Electrical & Electronic Equipment
(Applicable throughout the European Union and other European countries with separate collection program).
This product should not be treated as household waste when you wish dispose of it. Instead, it should be
handed over to an applicable collection point for the recycling of electrical and electronic equipment.
By ensuring this product is disposed of correctly, you will help prevent potential negative consequence to the
environment and human health, which could otherwise be caused by inappropriate disposal of this product. The
recycling of materials will help to conserve natural resource.
1.12 - Fault detection and repair
Internal calibrations and components should not be altered or replaced.
For repair please ask the Manufacturer or its authorized Dealers.
Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
6
of
43
2. General Characteristics
The MC is a very innovative and versatile line of Protective Relays which takes advantage of the long and
successful experience coming from the M-Line.
The main features of the MC-Line relays are:
Compact draw-out execution for Flush Mounting or for assembly in 19” 3U chassis for 19” Rack systems.
User friendly front face with 2x8 characters LCD Display, four signal Leds, four keys for complete local
management and 9-pin socket for local RS232 serial communication.
Four user programmable Output Relays. On request one of the Output Relays can be replaced by a Can Bus
port for control of additional I/O modules.
Three optoisolated, self-powered Digital Inputs.
RS485 communication port (independent from the RS232 port on front panel)
Totally draw-out execution with automatic C.T. shorting device.
Input currents are supplied to 3 current transformers: measuring phase currents.
An additional internal CT directly measures the residual (Zero Sequence) current of the three inputs.
Current inputs can be 1 or 5A: selection between 1A or 5A is made by movable jumpers provided on the Relay
card. (see Fig 1)
The Measuring Ranges of the different inputs
respectively are:
Phase Currents
:
(0.1-40) In
Residual Current
:
(0.01-10) In
Make electric connection in conformity with the
diagram reported on relay's enclosure.
Check that input currents are same as reported
on the diagram and on the test certificate.
2.1 - Power Supply
The auxiliary power is supplied by a built-in module fully isolated a self-protected.
The relay can be fitted with two different types of power supply:
Type 1
24V(-20%) / 110V(+15%) a.c.
24V(-20%) / 125V(+20%) d.c.
Type 2
80V(-20%) / 220V(+15%) a.c.
90V(-20%) / 250V(+20%) d.c.
Before energizing the unit check that supply voltage is within the allowed limits.

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
7
of
43
2.2 - Operation and Algorithms
2.2.1 - Reference Input Values
Display
Description
Setting Range
Step
Unit
I1
100
A
Rated Primary current of phase C.T.
1
-
9999
1
A
I2
5
A
Rated Secondary current of phase C.T.
1
-
5
1/5
A
In
100
A
Reference primary current of the relay
1
-
9999
1
A
Freq
50
Hz
System rated frequency
50
-
60
10
Hz
TW
30
min
Warming-up time constant for Thermal Image
1
-
60
1
min.
Ib
105
%In
Maximum admissible continuous overload for Thermal Image
50
-
130
1
%In
2.2.2 - Input quantities
2.2.2.1 - Mains Frequency (Freq)
The relay can operate either in 50Hz or 60Hz systems.
The rated Mains Frequency “Freq” must be set accordingly.
2.2.2.2 - Phase Current inputs (I1)
The relay directly displays the r.m.s. value of the Phase Currents “IA”, “IB”, “IC” flowing in the Primary
of the input Current Transformers and refers all its measurements to that value.
To make the relay properly working with any C.T., when programming the relay settings, input the value
“I1” of the primary current of the phase C.Ts
The measure is not displayed below
:
< 5% In
2.2.2.3 - Earth Fault Current Input (Ion)
Same as for the Phase Currents, the relay directly displays the r.m.s. value of the Zero Sequence
Residual Current flowing at the Primary of the Current Transformers.
The measure is not displayed below
:
< 1% On

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
8
of
43
rs
atTKB
1
Is
I
A
t(I) +••
+
−
=α
2.2.2.4 - Algorithm of the time current curves
The Time Current Curves are generally calculated with the following equation:
(1)
where:
t(I) = Actual trip time delay when the input current equals “I”
I = Maximum of the three input currents.
Is = Set minimum pick-up level
K =
Ts= Set time delay: t(I) = Tswhen
tr = Operation time of the output relay on pick-up (7ms).
The parameters “A” and “a” have different values for the different Time Current Curves.
Curve Name
Curve Identifier
A
B
a
IEC A Inverse
A
0.14
0
0.02
IEC B Very Inverse
B
13.5
0
1
IEC C Extremely Inverse
C
80
0
2
IEEE Moderate Inverse
MI
0.0104
0.0226
0.02
IEEE Short Inverse
SI
0.00342
0.00262
0.02
IEEE Very Inverse
VI
3.88
0.0963
2
IEEE Inverse
I
5.95
0.18
2
IEEE Extremely Inverse
EI
5.67
0.0352
2
The maximum measuring current is “40xIn” for phase elements and “10xOn” for the neutral
element.
1
a110A−
−
10
II
s
=

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
9
of
43
2.2.3 - Time Current Curves IEC (TU1029 Rev.0)

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
10
of
43
2.2.4 - Time Current Curves IEEE (TU1028 Rev.0)

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
11
of
43
3. Functions and Settings (Function)
3.1 - T> (F49) - Thermal Image protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
No Param
No Parameters
TripLev
→
Tal
50
%Tb
(50 110)
step
1
%Tb
→
Tst
100
%Tb
(10 100)
step
1
%Tb
Timers
→
No Param
No Parameters
FuncEnab
:
If disable the function is disactivated.
Tal
:
Thermal prealarm temperature.
Tst
:
Reset level.
Trip when
:
The temperature exceeded for time “tI>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Led reset when
:
Return in normal condition
Warming-up is computed proportionally to the square of the largest phase current “I”.
-Allowed overloading time (See Curve)
The trip time delay “t”of the thermal element, depends on the warming-up time constant
“tw”, on the previous thermal status (Ip/In)2, on the admissible continuous overload (Ib) and, of
course, on the actual load (I)
tw
=
Warming-up time constant
(1-60) min.
I
=
Largest of the three phase currents
Ip
=
Preheating current: Steady-State Current corresponding to the thermal status
existing at the moment when the current is increased to the overload value “I”
Ib
=
Continuously admissible current
(50-130) %In, step 1%In
In
=
Rated primary current of phase C.Ts
n
=
Natural logarithm
Reset takes please when the simulated temperature drops below the programming level [Tst].
An alarm signal is issued when the computed warming exceeds the set percentage “Tal” of the Full
Load temperature “Tb”.
:where
(Ib/In)(I/In) (Ip/In)(I/In)
twt22
22
−
−
= n

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
12
of
43
3.1.1 - Thermal Image Curves (TU0445 Rev.0)

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
13
of
43
3.2 - I> (1F51) - First overcurrent protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
TCC
D
[D / A / B / C / MI / VI / I / EI / / SI ]
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
I>
0.1
In
(0.1 4)
step
0.01
In
Timers
→
tI>
0.05
s
(0.05 60)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
TCC
:
Time current curves
D
=
Independent Definite Time
A
=
IEC A Inverse
B
=
IEC B Very Inverse
C
=
IEC C Extremely Inverse
MI
=
IEEE Moderate Inverse Curve
VI
=
IEEE Very Inverse Curve
I
=
IEEE Inverse Curve
EI
=
IEEE Extremely Inverse Curve
SI
=
IEEE Short Inverse Curve
BI
:
Operation controlled by Blocking Digital Input
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
I>
:
Minimum phase current pick-up level (limited to 40 times In)
tI>
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tI>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% I>.
Led reset when
:
push-button is pressed

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
14
of
43
3.3 - I>> (2F51) - Second overcurrent protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
2xI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
I>>
0.5
In
(0.50 40)
step
0.01
In
Timers
→
tI>>
0.05
s
(0.05 60)
step
0.01
s
→
t2xI
0.02
s
(0.02 9.99)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
2xI
:
Automatic threshold doubling on inrush
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
I>>
:
Minimum phase current pick-up level (limited to 40 times In)
tI>>
:
Trip time delay
t2xI
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tI>>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% I>>.
Led reset when
:
push-button is pressed

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
15
of
43
3.4 - IH (3F51) - Third overcurrent protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
2xI
Enable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
IH
0.5
In
(0.5 40)
step
0.01
In
Timers
→
tIH
0.05
s
(0.05 60)
step
0.01
s
→
t2xI
0.02
s
(0.02 9.99)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
2xI
:
Automatic threshold doubling on inrush
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
IH
:
Minimum phase current pick-up level (limited to 40 times In)
t2xI
:
Trip time delay
tIH
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tIH”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% IH.
Led reset when
:
push-button is pressed
3.4.2 –Automatic doubling or Overcurrent thresholds on current inrush
For some of the phase Overcurrent functions it is possible to have the set trip level [Is] automatically
doubled when strong inrush current is detected.
If at circuit Breaker switch-on (i.e. when the input current rises from zero to a minimum measurable value)
the current increases from 0 to 1.5 times the rated value [In] in less than 60ms, the set minimum pick-up
level [Is] is dynamically doubled ([Is]→[2Is]) and keeps this value until the input current drops below
1.25xIn or the set time [t2xI] has elapsed.
This functionality is very useful to avoid spurious tripping of the instantaneous or short-time delayed
Overcurrent elements that could be experienced at switch-on of reactive loads like Transformer or
Capacitors.

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
16
of
43
3.5 - Io> (1F51N) - First Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
TCC
D
[D / A / B / C / I / VI / EI / MI / SI ]
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
Io>
0.01
Ion
(0.01 4)
step
0.01
Ion
Timers
→
tIo>
0.05
s
(0.05 60)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
TCC
:
Time current curves
D
=
Independent Definite Time
A
=
IEC A Inverse
B
=
IEC B Very Inverse
C
=
IEC C Extremely Inverse
MI
=
IEEE Moderate Inverse Curve
VI
=
IEEE Very Inverse Curve
I
=
IEEE Inverse Curve
EI
=
IEEE Extremely Inverse Curve
SI
=
IEEE Short Inverse Curve
BI
:
Operation controlled by Blocking Digital Input
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Io>
:
Minimum Zero Sequence Residual Current Pick-up level
tIo>
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tIo>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% Io>.
Led reset when
:
push-button is pressed

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
17
of
43
3.6 - Io>> (2F51N) - Second Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
Io>>
0.01
Ion
(0.01 9.99)
step
0.01
Ion
Timers
→
tIo>>
0.05
s
(0.05 60)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
Io>>
:
Minimum Zero Sequence Residual Current Pick-up level
tIo>>
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tIo>>”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% Io>>.
Led reset when
:
push-button is pressed
3.7 - IoH (3F51N) - Third Earth Fault protection level
FuncEnab
→
Enable
[Disable / Enable]
Options
→
BI
Disable
[Disable / Enable]
→
Trg
Enable
[Disable / Enable]
TripLev
→
IoH
0.01
Ion
(0.01 9.99)
step
0.01
Ion
Timers
→
tIoH
0.05
s
(0.05 60)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
Trg
:
Function operation triggers the oscillographic wave form capture
(see § Oscillographic Recording)
IoH
:
Minimum Zero Sequence Residual Current Pick-up level
tIoH
:
Trip time delay
Trip when
:
The current trip level is exceeded for time “tIoH”.
When the function is tripped
:
Signalization
=
Led “Trip” is illuminated
Last Trip
=
Is recorded
Function reset when
:
The current drop below 95% IoH.
Led reset when
:
Push-button is pressed

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
18
of
43
3.8 - BF (F51BF) - Breaker Failure
FuncEnab
→
Enable
[Disable / Enable]
Options
→
TrR
Relay1
Relay1 –Relay2 –Relay3 –Relay4
TripLev
→
No Param
No Parameters
Timers
→
tBF
0.2
s
(0.05 0.75)
step
0.01
s
Description of variables
FuncEnab
:
If disable the function is disactivated
TrR
:
Output relay programmed for trip command to the Circuit Breaker
tBF
:
Trip time delay
Operation: If after the time “tBF” from pick-up of the programmed relay “TrR” the current measured still
exceeds 5%In, the output relay associated to the “BF” function is operated (relay another than TrR).
3.9 - I.R.F. - Internal Relay Failure
FuncEnab
→
No Param
No Parameters
Options
→
Opl
NoTrip
[NoTrip / Trip]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
Opl
:
The variable “Opl”can be programmed to trip the output relays same as the other
protection functions (Opl = TRIP), or to only operate the “IRF” signal led without tripping
the output relays (Opl = NoTRIP).
Trip when
:
an internal fault in the relay is detected (see Diagnostics)
When the function is tripped
:
Signalization
=
Led “PWR/I.R.F.” blink
Last Trip
=
Is recorded
Function reset when
:
it returns to normal operation
Led reset when
:
Push-button is pressed

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
19
of
43
3.10 - Osc - Oscillographic Recording
FuncEnab
→
Enable
[Disable / Enable]
Options
→
Trg
Trip
[Disable / Start / Trip / Ext.Inp.]
TripLev
→
No Param
No Parameters
Timers
→
tPre
0.3
s
(0.1 0.5)
step
0.1
s
→
tPost
0.3
s
(0.1 1.5)
step
0.1
s
Description of variables
FuncEnab
:
If disable the function is disactivated
Trg
:
Disab
=
Function Disable (no recording)
Start.
=
Trigger on time start of protection functions
Trip
=
Trigger on trip (time delay end) of protection functions
Ext.Inp.
=
Trigger from the Digital Input D3
tPre
:
Recording time before Trigger
tPost
:
Recording time after Trigger
When the option “Start” or “Trip” is selected:
The oscillographic recording is started respectively by the “Time Start” or by the “Time End” of any of the
functions that have been programmed to Trigger the Wave Form Capture (I>, I>>, IH, Io>, Io>>, IoH).
The “Osc” Function includes the wave Form Capture of the input quantities (IA, IB, IC, Io) and can totally
store a record of 3 seconds.
The number of events recorded depends on the duration of each individual recording (tPre + tPost).
In any case the number of event stored cannot exceed ten (10 x 0.3 sec).
Any new event beyond the 3 sec capacity of the memory, cancel and overwrites the former records (FIFO
Memory).

MC30-X/10-4
Doc. N° MO-0350-ING
Copyright 2016
FW: 1211.37.06.x
Date
17.06.2022
Rev.
3
Pag.
20
of
43
3.11 - Comm –Communication Parameters
FuncEnab
→
No Param
No Parameters
Options
→
LBd
9600
[9600 / 19200 / 38400]
→
RBd
9600
[9600 / 19200]
→
Mod
8,n,1
[8,n,1 / 8,o,1 / 8,e,1]
→
RPr
Modbus
[Iec103 / Modbus]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
LBd
:
Local Baud Rate (Front panel RS232 communication speed)
RBd
:
Remote Baud Rate
(Rear panel terminal blocks RS485 communication speed)
Mod
:
Remote mode (communication parameters)
Note: Any change of this setting becomes valid at the next power on
RPr
:
Remote Protocol
3.12 - LCD –Display and Buzzer operation
FuncEnab
→
No Param
No Parameters
Options
→
Key
BeepON
[BeepOFF / BeepON]
→
BkL
Auto
[Auto / On]
→
AnF
View
[View / Hidden]
TripLev
→
No Param
No Parameters
Timers
→
No Param
No Parameters
Description of variables
Key
:
Buzzer “Beep” on operation of Keyboard buttons.
BkL
:
LCD Backlight continuously “ON” or switched-on Automatically on operation of
Keyboard buttons.
AnF
:
Field Alarms
View
=
Visible if preset an Home page local HMI
Hidden
=
Presence not visible on Home page local HMI