MIKRODEV MP211 PLC Series User manual

MP211
HARDWARE MANUAL
MP211
PLC Series
10 / 2017
MIKRODEV_HM_MP211_EN
V1.1

1
MP211 SERIES –HARDWARE MANUAL
CONTENTS
1MP211 GENERAL INFORMATION ........................................................................ 6
1.1 Physical Interfaces .................................................................................... 6
1.2 General Device Specifications ..................................................................... 7
2INSTALLATION INFORMATION........................................................................... 8
2.1 Rail Installation ......................................................................................... 8
2.2 Extension Installation ................................................................................ 9
3CONNECTION DIAGRAMS ................................................................................10
3.1 Supply Connection....................................................................................10
3.2 Digital Inputs...........................................................................................11
3.3 Digital Outputs.........................................................................................12
3.4 Relay Outputs ..........................................................................................13
3.5 Analog Inputs ..........................................................................................14
3.6 Analog Outputs ........................................................................................15
3.7 RTD Inputs ..............................................................................................16
3.8 RS485 SERIAL PORT.................................................................................17
3.9 RS232 SERIAL PORT.................................................................................18

2
MP211 SERIES –HARDWARE MANUAL
FIGURES LIST
Figure 1 Connector and Physical Interfaces ............................................................... 6
Figure 2 Mounting.................................................................................................. 8
Figure 3 Extension Installation ................................................................................ 9
Figure 4 Power Connection Diagram........................................................................10
Figure 5 DIN Connection Diagram...........................................................................11
Figure 6 DOUT Connection Diagram ........................................................................12
Figure 7 Relay Connection Diagram ........................................................................13
Figure 8 Analog Input Connection Diagram ..............................................................14
Figure 9 Analog Output Connection Diagram ............................................................15
Figure 10 RTD Input Connection Diagram ................................................................16
Figure 11 RS485 Input Connection Diagram.............................................................17
Figure 12 RS232 Input Connection Diagram.............................................................18

3
MP211 SERIES –HARDWARE MANUAL
Preface
Mikrodev MP201 and MP211 PLC series are programmable control devices that are used
in a wide range of applications from process automation to building automation, from
machine automation to telemetry applications.
In this document, you can find information about the hardware specifications of Mikrodev
MP201/MP211 series PLCs.
Please follow our website www.mikrodev.com for the up to date version of the document.

4
MP211 SERIES –HARDWARE MANUAL
About Mikrodev
Since 2006, MIKRODEV has been developing and manufacturing industrial control and
communication products. MIKRODEV serves the system integrators in the public and
private sector, OEM and end users.
Our products are manufactured complying with the quality standards required by the
industrial automation industry and the quality of our products are proved on the field for
many years
MIKRODEV is one of the few companies in the world that has its own designed IEC
61131-3 compliant library for its programmable logic control devices. In addition, the
open, flexible, programmable SCADA solution developed by MIKRODEV is also available
to customers.
MIKRODEV products' performance and wide range of applications make them possible for
customers to achieve faster, simplified and cost-effective results.

5
MP211 SERIES –HARDWARE MANUAL
WARNING!
Please take care of the following issues when using Mikrodev devices.
Since the unit operates with 24 VDC (12-36 VDC) voltage, you should take care of
the voltage level that the unit is connected to. If a voltage above this voltage level
is applied, the device may be damaged and may be out of warranty.
Make sure that the energy connection of your device is connected to the ground
or to a properly grounded terminal.
Make sure that the environment in which your device is being used is free of
moisture, electric shock, vibration and dust.
Pay attention to the supply voltage and the connections of the product. Mikrodev
is not responsible for any issues due to power failure since there is no auxiliary
supply (UPS) on the device.
The fuse to be used must be a FF super fast type and current limit value 1A.
Do not use the device under conditions other than the environmental conditions
specified in the "Electrical Specifications" section (humidity, dust, liquid and
temperature, etc.)
Removing the warranty label on the product or removing the protective case will
void the warranty.
Products that are damaged, boxes have been changed and other brand labels are
affixed are not covered by the warranty.
The appliance must not be cleaned with solvents (thinner, benzine, acid etc.) or with
abrasive cleaning agents.
Only dry cloth should be used when cleaning the appliance.
Do not open the device by removing the case of the appliance, do not interfere
with the electronic components and circuits. There is no user-replaceable part
inside the device.
If there is a problem or malfunction on your device, it should only be repaired by
an authorized service. Installation and electrical connections must be made by
technical personnel in accordance with the instructions in the operating manual.
Failure to comply with these rules may result in death, serious injury or
property damage

6
MP211 SERIES –HARDWARE MANUAL
1MP211 GENERAL INFORMATION
1.1 Physical Interfaces
Figure 1 Connector and Physical Interfaces
1
Digital Input Neutral Connection
19
USB Port
2
Analog Output Connections
20
Relay Status Information
3
Analog Neutral Connection
21
Digital Output Status Information
4
Analog Input Connection
22
Digital Input Status Information
5
RS485 Connections
23
System Energised LED
6
RS-232 Neutral Connections
24
System Running LED
7
Rs232 TX-RX Connections
25
Error LED
8
RTD Neutral Connections
26
Protocol Data Transfer
9
RTD Connections
27
Antenna Connection
10
Relay Connections
28
SIM Card Slot
11
CAN BUS Communication
Connection
29
SD Card Slot
12
Digital Input Connections
30
LCD Screen
13
Digital Output Connections
31
LCD Screen Back Button
14
Digital Output Supply Connection
32
LCD Screen Up Button
15
Digital Output Neutral Connection
33
LCD Screen Input Button
16
Device Power (V+) Connection
34
LCD Screen Forward Button
17
Device Power (V-) Connection
35
LCD Screen Down Button
18
Ethernet Port
36

7
MP211 SERIES –HARDWARE MANUAL
1.2 General Device Specifications
SPECIFICATION
ITEM
DESCRIPTION
Processor
Processor Architecture
ARM Cortex M4
Precossror Internal RAM
196 KB
CPU Processing Speed
168 MHz
Adressing Architecture
Little Endian Addressing
Electrical
Supply
24 VDC (12-36VDC)
Power
<10W
Real Time Clock
Integrated
Input / Output
Digital Input
16
Digital Output
8
Analog Input
4
Analog Output
2
Relay Output
4
RTD
2
Enviromental
Conditions
Operating Temperature
-20 / +60 C
Storage Temperature
-40 / +85 C
Humidity
5..95 RH
Memory
Retentive Memory
4KB
Program Memory
4MBit
Communication Ports
Ethernet Port
100 Mbit, MODBUS TCP
RS485
1
RS232
1
Wireless
Communication
GSM / GPRS
Quad-Band
850/900/1800/1900 MHz
Wi-Fi
IEEE 802.11 b/g/n
Extension Capacity
RAIL Type- CANBUS Extension
Max. 640 Digital IO
(256 DI, 256 DO, 128 Relay
Output)Max. 96 Analog IO
(32 AI, 32 RTD Input, 32
AQ)

8
MP211 SERIES –HARDWARE MANUAL
2INSTALLATION INFORMATION
2.1 Rail Installation
DIN Rail Mountage
First, the upper part of the device is mounted on the DIN rail. Then, with the help of the
springs behind the device, when a lightly force is applied to the lower part, the device
locates into the DIN rail easily and the montage is completed. (See 36 A - 36 B)
DIN Rail Demountage
To demount the device, firstly it is pulled from the bottom using flexibility of the spring,
the device is removed from the DIN Rail and the demounting is completed.
Figure 2 Mounting

9
MP211 SERIES –HARDWARE MANUAL
2.2 Extension Installation
The MP211 product and its extensions are mounted by sliding over the rail in such a way
that the connectors correponds.
Figure 3 Extension Installation

10
MP211 SERIES –HARDWARE MANUAL
3CONNECTION DIAGRAMS
3.1 Supply Connection
Supply:
12-36 VDC, Protected
Power:
< 13 W
Figure 4 Power Connection Diagram

11
MP211 SERIES –HARDWARE MANUAL
3.2 Digital Inputs
Module Input:
16 (Sink)
Voltage Range:
0-30 VDC
ON Voltage Level:
7 VDC -30 VDC
OFF Voltage Level:
0-4 VDC
Input Impedance:
>2M
Isolation:
Optical
OFF to ON Response:
20 us
ON to OFF Response:
90 us
Fast Counter Inputs:
DI12, DI13, DI14, DI15
Figure 5 DIN Connection Diagram

12
MP211 SERIES –HARDWARE MANUAL
3.3 Digital Outputs
Module Output:
Mosfet Output
Voltage Range:
0-40 VDC
Max. Output Current:
2 A/point (@30V)
Isolation:
Optical
External Voltage Input:
3.3-40 VDC
Fast Outputs PWM, PTO:
DQ1, DQ2, DQ3, DQ4
Fast Outputs Max. Frekans
20 kHz
Figure 6 DOUT Connection Diagram

13
MP211 SERIES –HARDWARE MANUAL
3.4 Relay Outputs
Module Output:
4
Relay Contact Outputs:
COM-NO (Normally Open)
Contact Max. Current:
3A@250VAC –3A@30VDC
Isolation
Potential of relay contacts are isolated
from power source and inputs.(Dry
Contacts)
Figure 7 Relay Connection Diagram

14
MP211 SERIES –HARDWARE MANUAL
3.5 Analog Inputs
Current Input Count
4
Current Input Type
Current, 0-20 mA
Current Input Precision:
%1 Precision
Common Input GND:
1 (4 point / common)
Figure 8 Analog Input Connection Diagram

15
MP211 SERIES –HARDWARE MANUAL
3.6 Analog Outputs
Current Output Count
2
Current Output Type
Current, 0-20 mA
Current Output Precision:
%1 Precision
Common Output GND:
1 (2 point / common)
Figure 9 Analog Output Connection Diagram

16
MP211 SERIES –HARDWARE MANUAL
3.7 RTD Inputs
RTD Input Count
2
RTD Input Type
PT1000, 2 wire
Temperature Range:
-50 … +200 C
Common Input GND:
1 (2 points / common)
Figure 10 RTD Input Connection Diagram

17
MP211 SERIES –HARDWARE MANUAL
3.8 RS485 SERIAL PORT
RS485 port Count:
1
Isolation:
Galvanic
Maximum Slave Counts:
200
Communication Distance:
1000 m
Data Bits:
7-8
Stop Bits:
1-2
Parity:
None-Even-Odd
Baudrate:
300 bps to 200 kbps
Figure 11 RS485 Input Connection Diagram

18
MP211 SERIES –HARDWARE MANUAL
3.9 RS232 SERIAL PORT
RS232 port Count:
1
Communication Distance:
10 m
Data Bits:
7-8
Stop Bits:
1-2
Parity:
None-Even-Odd
Baudrate:
300 bps to 200 kbps
Figure 12 RS232 Input Connection Diagram
This manual suits for next models
1
Table of contents
Other MIKRODEV Controllers manuals
Popular Controllers manuals by other brands

dixell
dixell EMERSON XR70C Installing and operating instructions

Omron
Omron NX1P Programming manual

FixPosition
FixPosition Vision-RTK 2 quick start guide

Syntec
Syntec 60W-E Wood Operation manual

Thermal Dynamics
Thermal Dynamics IHC XT operating manual

BIFFI
BIFFI EFS2000v4 Instructions and operating manual