
KT60443-1A
4 . Preparation for measurement
(1) Wiring
Connect the unit with a transmitter to be combined with an attached cable of this unit .
Refer to the operation manual for the details of transmitter ( CSA-562B ) for the details .
(2) Calibration
When no load is applied , adjust zero point and calibrate the output .
Refer to the operation manual for the details of transmitter ( CSA -562B ) .
As for torque outputs , when thr rotor is twisted counterclockwise , a plug lutput will be outputted .
If you want to change the polarity , wire the + and - of the transmitter output cable reversely.
(3) Trial operation
Carrying out trial operation at a low speed , check and confirm that there are no abnormal output ,
sound , temperature , vibration etc . and carry out measuring operations .
5 . Maintenance inspection
Signals are taken and received by photo transmission in this transducer . Therefore , if luminous
and light receiving elements should be stained with black soot etc ., no signals will be taken
sometimes . In this case , the surface of luminous and light receiving surfaces must be cleaned with
such solvents as ethanol etc .
6 . Cautions for use
(1) For the reasons of taking and receiving singals by photo transmission , there is no problem at all
in tha case of fluorescent light etc . But this unit , this unit malfunctions in some cases in the case
of infrared rays of sun-light and incandescent light . If used exposed to the abovmentioned rays and
lights , shut off them with a protective cover .
(2) An electric current runs for transmission of an input voltage transmission in the antenna section
of the stator . Therefore , prevent it from coming contact with surrounding metal bodies such
as cover .
(3) There are connectors for taking out of signals at 2 places of both sides .
The connectors are so arranged that the cable can be taken out in any direction for the reason
of layout . But , be sure to use only one side . No signal can be taken out at the same time from
both sides .
(4) As it is a rotary body , be sure to fit a protective cover for prevention of flying away .
(5) An unbalance cuased by fitting of a coupling results in generation of vibration .
Therefore , dynamic balance must be adjusted overally sfter combining torque transducer and
coupling etc .
(6) If there should be impact load and vibration , a dynamic load caused by multiplying static load by
acceleration will act on the torque transducer .
Therefore , the value calculated by taking accleration into consideration shall not exceed the
rated capacity of torque transducer .
(7) If there is a possibility that an excess load acts on the torque transducer , provide a safety device
against damage .
MINEBEA CO.,LTD.MEASURING COMPONENTS BUSINESS UNIT
5