1
1. IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions that should be followed during the installation and the
operation of the Remote Power Manager (RPM).
SAVE THESE INSTRUCTIONS
An Important Notice
To ensure safety in all applications ensure that a Qualified Service Personnel installs the system.
Make sure that the AC Utility outlet is properly grounded.
Do not open the unit there are no serviceable parts inside. This will void the warranty.
Do not try to repair the unit yourself, see Obtaining Service.
Please make sure that the input voltage of the RPM matches the supply voltage.
Use a certified input power cord with the correct plugs and sockets for the appropriate voltage
system.
Make sure the RPM is installed in the proper environment as specified. (0-50°C and 0-90% non-
condensing humidity)
This RPM series is ONLY intended to be installed in an indoor temperature controlled environment
that is free of conductive contaminants.
Do not operate the RPM in: extremely dusty and/or unclean areas, locations near heating devices,
water or excessive humidity, or where the RPM is exposed to direct sunlight.
Select a location, which will provide good air circulation for the RPM at all times.
This RPM supports electronic equipment in offices, telecommunications, process control, security,
and IT applications.
Servicing of RPM should be performed by Qualified Service Personnel Only.
CAUTION – To reduce the risk of fire, connect only to a branch circuit with over current protection in
accordance with the National Electric Code.
CAUTION - Connect the RPM to a two pole, three wire grounding AC wall outlet. The receptacle
must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any
other type of receptacle may result in a shock hazard and violate local electrical codes. Do not use
extension cords, adapter plugs, or surge strips.
Route power cords so they cannot be walked on or damaged.
CAUTION - To reduce the risk of electrical shock with the installation of this RPM equipment and the
connected equipment, the user must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
CAUTION - To de-energize the outputs of the RPM: Disconnect the RPM from the AC wall outlet.
CAUTION - Do not install this device if there is not at least 30 feet (10 meters) or more of wire
between the electrical outlet and the electrical service panel.
SSL Configuration:
These RPMs only support the SSLv1 protocol, which in most browsers is no longer
supported. Please DO NOT ENABLE the SSL function, doing so will require resetting the
RPM back to the factory default settings. See page 5 the ‘Function Button’ to reset to the
factory default settings.