FX2N-2DA SPECIAL FUNCTIONBLOCK
USER’S GUIDE
JY992D74901D
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX2N-2DA special function block and should be read and understood before
attempting to install or use the unit.
Further information can be found in the FX SERIES PROGRAMMING MANUAL(ΙΙ), FX0N/FX1N/FX2N/
FX2NC SERIES HARDWARE MANUAL of each PLC.
1. INTRODUCTION
The FX2N-2DA type analog output block (hereafter referred to as the FX2N-2DA) is used to convert a
digital value of 12 bits into an analog output of two points (voltage and current output), and to forward the
values to the Programmable Controller (hereafter referred to as a PLC).
FX2N-2DA can connected to the FX0N, FX1N, FX2N, and the FX2NC series Programmable Controllers.
1) The analog output is selected from the voltage or current output by the method of connecting wires.
At this time, assume setting to be two channels common analog output.
2) The two analog output channels can accept outputs of 0 to 10V DC, 0 to 5V DC, or 4 to 20mA.
(A mixture of voltage/current output is possible.)
3) Resolution is 2.5mV (0 to 10V DC) and 4µA(4 to 20mA).
4) The digital to analog conversion characteristics can be adjusted.
5) The block occupies 8 I/O points which can be allocated from either the inputs or outputs.
6) The data transfer with the PLC uses the FROM/TO instructions.
2. EXTERNAL DIMENSIONS AND PARTS
Dimensions: mm (inches)
3. WIRING
*1 Connect a 0.1 to 0.47 µF 25V DC capacitor respective to position *1 when there is voltage
ripple in the voltage output or there is a lot of noise.
*2 For voltage output please short circuit IOUT and COM as shown in the diagram.
*3 Channel number enter .
D I N r a i l
m o u n t i n g
s l o t
3 5 m m ( 1 . 3 8 )
M o u n t i n g
holes
2 h o l e s 4 . 5
( 0 . 1 8 ) d i a
E x t e n s i o n
a b l e
43(1.69)
80(3.15)
87(3.43)
9(0.35) 4(0.16)
90(3.54)
M 3 ( 0 . 1 2 )
t e r m i n a l s r e w s
P O W E R
2 N
F X - 2 D A
P O W E R
C O M 2
I O U T 1
V O U T 1
I O U T 2V O U T 2
C O M 1
C H 1
O F F S E T
C O M 1
V O U T 2 I O U T 2
V O U T 1 I O U T 1
C O M 2
O F F S E T
C H 2
G A I N
C H 1
C H 2
G A I N
O F F S E T
C H 1
C O M 2
P O W E R
O F F S E T
C H 2
G A I N
C H 1
C H 2
G A I N
O F F S E T / G A I N
v o l u m e
Mass (Weight):0.2kg (0.44lbs)
Accessories: Special Function block number label
*1
VOUT
IOUT
COM
VOUT
IOUT
COM
Extension
cable
PLC DC/DC
converter
+15V
-15V
AG
Inverter
etc
Recorder
etc
*3
Current output
Voltage output
FX
2N
-2DA
*2
{
4. CONNECTION WITH PROGRAMMABLE CONTROLLER
1) The FX2N-2DA and main unit are connected by a cable on the right of the main unit.
2) Up to 4 FX
2N
-2DA units can connect to the FX
0N
series PLC, up to 5 for FX
1N,
up to 8 for FX
2N
or, up to
4 for the FX
2NC
series PLC, all with powered extension units.
However the following limitation exists when the undermentioned special function blocks are connected.
FX2N: Main unit and powered extension units of 32 points I/O or less. Consumption current available
for undermentioned special function blocks ≤ 190mA
FX2N: Main unit and powered extension units of I/O 48 points or more. Consumption current available
for undermentioned special function blocks ≤ 300mA
FX2NC: Up to 4 undermentioned special function blocks can be connected regardless of the system I/O.
FX0N/1N: Main unit and powered extension units. Up to 2 undermentioned special function blocks can be
connected regardless of the system I/O.
The consumption of the above units is to be subtracted from the service power supply of the host
PLC.
3) The blocks occupies 8 I/O points (the 8 points can be allocated from either inputs or outputs).
4) FX2N-2DA consumes 5V DC 30mA.
The total 5V consumption of all special function blocks connected to either an FX2N, FX2NC main unit
or an FX2N extension unit must not exceed the 5V source capacity of the system.
5. SPECIFICATIONS
5.1 Environmental specification
Environmental specifications other than the above are the same as the main unit of the
Programmable Controller. (Refer to the Hardware manual of the Programmable controller)
5.2 Power supply specification and others
5.3 Defining gain and offset
FX2N-2DA FX2N-2AD FX0N-3A
Consumption current of 24V DC forone unit 85mA 50mA 90mA
Item Content
Directric Withstand
voltage 500V AC 1min (between analog output terminals and case)
Item Content
Analog circuits 24V DC ±10% 85mA (Internal power supplied from the main unit)
Digital circuits 5V DC 30mA (Internal power supplied from the main unit)
Isolation Photo-coupler isolation between analog and digital circuits.
(No isolation between analog channels.)
Number of occupied
I/O points The blocks occupies either 8 input or output points.
(Can be either inputs or outputs)
Item Voltage output Current output
Range of analog output
At shipping, the unit is adjusted to a digital range of 0 to 4000 for an analog
voltage output of 0 to 10V DC. When using an FX2N-2DA for current or
differing voltage output except 0 to 10V DC, it is necessary to adjust the
offset and gain.
0 to 10V DC, 0 to 5V DC
(External load resistance 2K to
1MΩ)
4 to 20mA
(External load resistance 400Ω or
less)
Digital input 12bit
Resolution 2.5mV: 10V/4000(At shipment)
Change depending on the output
characteristic.
4µA: (20-4)A/4000
Change depending on the output
characteristic.
Integrated accuracy ± 0.1V ± 0.16mA
Processing time 4ms/1 channel (synchronized to be sequence program)
Output characteristics
If a digital source data of greater than 12 bits is used, only the lower 12 bits
will be valid. Additional (upper) bits will be ignored
Use a digital value within the range from 0 to 4095.
The output characteristic can be set to each of the two channels.
Digital value
04000
10V
Analog value
Digital value :0 to 10V
:0 to 4000
Analog
value
10.238V
4095
at
shipment
Analog
value
Digital value
04000
20mA
4mA
Analog value
Digital value :4 to 20mA
:0 to 4000
20.380mA
4095
6. ALLOCATION OF BUFFER MEMORY (BFM)
6.1 Buffer memory
BFM#16: The D/A conversion data of the channel specified with BFM#17 (digital value) is written.
The D/A data is written in binary in order of the lower 8bit and higher 4bit and divided into two
portions.
BFM#17: b0•••The D/A conversion of CH2 begins by changing of 1→0.
b1•••The D/A conversion of CH1 begins by changing of 1→0.
b2•••The lower eight bit data for the D/A conversion is held by changing of 1→0.
Write data in the above-mentioned buffer memory by "8. Program example".
BFM
number b15 to b8 b7 to b3 b2 b1 b0
#0 to #15 Reserved
#16 Reserved Digital source data for output (8 bit)
#17 Reserved Lower data holding
bit
CH1 D/A
conversion
beginning
CH2 D/A
conversion
beginning
#18 or more Reserved
HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310 TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
7. ADJUSTMENT OF OFFSET AND GAIN
7.1 Change in output characteristic
At shipment, 0 to 4000 range is selected for 0 to 10V DC output.
When using an FX2N-2DA for current or differing voltage output except 0 to 10V DC, it is necessary to
readjust the offset and gain.
The output characteristic can be set for each of the two channels.
Set analog values within the range specified in the table below when changing the output characteristic.
Range of output characteristic
Resolution changes depending on the set value when the output characteristic changes accordingly.
Example: Resolution becomes (5 - 0V)/4000=1.25mV at voltage output 0 to 5V/0 to 4000.
Integrated accuracy does not change. (Voltage output: ± 0.1V, Current output: ± 0.16mA)
The adjustment of the offset and gain values sets a digital equivalent to the analog data.
(The “POT” requires 18 revolutions to move between MIN and MAX setting.)
*1 The analog value increases if the volume is turned clockwise.
7.1.1 Adjustment of gain
The gain value can be set to an arbitrary digital value.
However, using the maximum of 12bit resolution provides the user with a full scale analog value.
7.1.2 Adjustment of offset
The offset value in the case of voltage output is 0V. The offset value in the case of current output is 4mA.
However, the offset value can be minutely adjusted if necessary. Set the following when minute
adjustments are necessary.
For instance, when a digital range of 0 to 4000 is used with the analog range of 0 to 10V, a digital value of
40 is equal to an analog output of 100mV, (40 × 10V/4000 digital points). When a digital range of 0 to 4000
is used with the analog range of 4 to 20mA, a digital value of 0 is equal to an analog output of 4mA.
1) Adjust the offset and gain respectively for CH1 and CH2.
2) Repeat offset and gain adjustments until a stable value is obtained.
3) Adjust the gain before the offset.
Voltage output Current output
Analog value when digital value is 0 0 to 1V 4mA
Analog value when digital value is 4000 5 to 10V 20mA
+
-
VOUT
IOUT
COM
FX
2N
-2DA
Ammeter
A
V+
-
VOUT
IOUT
COM
FX
2N
-2DA
Voltmeter
POWER
COM2
IOUT1
VOUT1
IOUT2
VOUT2
COM1
CH1
OFFSET
OFFSET
CH2
GAIN
CH1
CH2
GAIN
OFFSET
CH1
COM2
POWER
OFFSET
CH2
GAIN
CH1
CH2
GAIN
CH1
Offset volume
CH1
Gai volume
CH2
Offset volume
CH2
Gai volume
OUT2
Voltage output Current output Volume *1
04000
10V
Voltage output
characteristic (0 to 10V)
Analog
value
Digital value 04000
5V
Voltage output
characteristic (0 to 5V)
Analog
value
Digital value
Voltage output
characteristic (4 to 20mA)
04000
20m
A
4mA
Analog
value
Digital value
Analogue
value
Digital value
040
100mV
Voltage output
characteristic (0 to 10V)
at shipment
080
100mV
Voltage output
characteristic (0 to 5V)
Analogue
value
Digital value
Voltage output
characteristic (4 to 20mA)
0
4mA
Analogue
value
Digital value
8. PROGRAM EXAMPLE
The following program examples (8.1 and 8.2) are formula circuits.
The device numbers that have been underlined can be assigned by the user during programming.
8.1 At connection to FX0N series PLC
Digital to analog conversion execution input of CH1 :X000
Digital to analog conversion execution input of CH2 :X001
At the same time X000 and X001 can be turned ON.
D/A output data CH1:D100 (Replace with auxiliary relay M100 to M131. Assign these numbers only once)
D/A output data CH2:D101 (Replace with auxiliary relay M100 to M131. Assign these numbers only once)
Processing time: 4ms / 1 channel
(Time until FX2N-2DA outputs analog value after turning on X000 and X001.)
8.2 At connection to FX1N, FX2N or FX2N series PLC
Digital to analog conversion execution input of CH1 :X000
Digital to analog conversion execution input of CH2 :X001
At the same time X000 and X001 can be turned ON.
D/A output data CH1:D100 (Replace with auxiliary relay M100 to M115. Assign these numbers only once)
D/A output data CH2 :D101 (Replace with auxiliary relay M100 to M115. Assign these numbers only
once)
Processing time:4ms / 1 channel
(Time until FX2N-2DA outputs analog value after turning on X000 and X001.)
8.3 Connection to FX2N (V3.00 or later) or FX2N (V3.00 or later) series PLC
Please use FNC 177 (WR3A).
Refer to FX series Programming Manual ΙΙ.
0X000
[T0 K0 K16 K4M116 K1 ]
[T0 K0 K17 H0004 K1 ]
[T0 K0 K17 H0000 K1 ]
[M0V D100 K4M100 ]
[M0V K2M100 K2M116 ]
[M0V K2M108 K2M116 ]
[T0 K0 K17 H0002 K1 ]
[T0 K0 K16 K4M116 K1 ]
[T0 K0 K17 H0004 K1 ]
[M0V D101 K4M100 ]
[T0 K0 K17 H0000 K1 ]
[M0V K2M100 K2M116 ]
[M0V K2M108 K2M116 ]
[T0 K0 K17 H0000 K1 ]
[T0 K0 K16 K4M116 K1 ]
[T0 K0 K17 H0000 K1 ]
61 X001
a
b
c
d
e
g
h
i
j
k
l
m
n
[T0 K0 K16 K4M116 K1 ] f
[T0 K0 K17 H0001 K1 ]
a)Digital data (D100) is progressed to
supplementary relay (M100-M115).
b)The lower 8 bit data is moved.
c)The lower 8 bit data is written to the
FX2N-2DA.
d)The lower 8 bit data is held.
e)The higher 4 bit data is moved.
f) The higher 4 bit data is written to the
FX2N-2DA.
g)The D/A conversion of CH1 is
executed.
h)Digital data (D101) is progressed to
supplementary relay (M100-M115).
i) The lower 8 bit data is moved.
j) The lower 8 bit data is written to the
FX2N-2DA.
k)The lower 8 bit data is held.
l) The higher 4 bit data is moved.
m)The higher 4 bit data is written to the
FX2N-2DA.
n)The D/A conversion of CH2 is
executed.
0X000
[T0 K0 K17 H0004 K1 ]
51 X001
[T0 K0 K16 K1M108 K1 ]
[T0 K0 K17 H0000 K1 ]
[T0 K0 K17 H0000 K1 ]
[T0 K0 K17 H0004 K1 ]
[T0 K0 K16 K1M108 K1 ]
[T0 K0 K17 H0000 K1 ]
[T0 K0 K17 H0000 K1 ]
[T0 K0 K16 K2M100 K1 ]
[M0V D100 K4M100 ]
b
c
[T0 K0 K16 K2M100 K1 ]
[M0V D101 K4M100 ]
a
e
i
d
g
h
f
j
[T0 K0 K17 H0002 K1 ]
[T0 K0 K17 H0001 K1 ]
a)Digital data (D100) is progressed to
supplementary relay (M100-M115).
b)The lower 8 bit data is written to the
FX2N-2DA.
c)The lower 8 bit data is held.
d)The higher 4 bit data is written to
the FX2N-2DA.
e )The D/A conversion of CH1 is
executed.
f) Digital data (D101) is progressed to
supplementary relay (M100-M115).
g)The lower 8 bit data is written to the
FX2N-2DA.
h)The lower 8 bit data is held.
i) The higher 4 bit data is written to
the FX2N-2DA.
j) The D/A conversion of CH2 is
executed.
9. NOTES IN DRIVE
1) Confirm whether the output wiring of FX2N-2DA and the connection of the extension cable are
correctly done.
2) Confirm whether the "4. Connection with programmable controller" condition is satisfied.
3) When shipped from the factory, the output characteristic is adjusted to 0 to 10V DC.
If a different output characteristic is desired, please adjust as required.
4) The mixture use for the voltage output/the current output is possible.
10. ERROR CHECK
Confirm the following items when it seems that the FX2N-2DA does not operate correctly.
1) Confirm the state of POWER LED.
Lit :The extension cable is correctly connected.
Turn off or blinks :Confirm the proper connection of the extension cable.
2) Confirm external wiring per section “3. WIRING”
3) Confirm whether the load resistance of the connected equipment corresponds to the specification of
the FX2N-2DA.
4) Confirm the Voltage and Current Output values with a voltmeter and an ammeter. Confirm the digital
to analog conversion from the output characteristic. Readjust the offset and gain per "7.
ADJUSTMENT OF OFFSET AND GAIN". The output characteristic when shipped from the factory is
0 to 10V DC.
Guidelines for the safety of the user and protection of the FX2N-2DA SPECIAL
FUNCTION BLOCK
• This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery, low voltage and EMC.
• If in doubt at any stage during the installation of the FX2N-2DA always consult a professional
electrical engineer who is qualified and trained to the local and national standards. If in doubt
about the operation or use of the FX2N-2DA please consult the nearest Mitsubishi Electric
distributor.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
• Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
Manual number: JY992D74901
Manual revision: D
Date : SEPTEMBER 2002
JY992D74901D Effective Sep. 2002
Specificationsaresubjectto
change without notice

This manual suits for next models

2

Other Mitsubishi I/O System manuals

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Mitsubishi MELSEC QS Series User manual

Mitsubishi

Mitsubishi MELSEC QS Series User manual

Mitsubishi FX3U-16CCL-M User manual

Mitsubishi

Mitsubishi FX3U-16CCL-M User manual

Mitsubishi AJ65BT-68TD User manual

Mitsubishi

Mitsubishi AJ65BT-68TD User manual

Mitsubishi AJ65SBTB2-16R User manual

Mitsubishi

Mitsubishi AJ65SBTB2-16R User manual

Mitsubishi FX-16E-TB/UL User manual

Mitsubishi

Mitsubishi FX-16E-TB/UL User manual

Mitsubishi GT15V-75ROUT User manual

Mitsubishi

Mitsubishi GT15V-75ROUT User manual

Mitsubishi Q68TD-G-H02 User manual

Mitsubishi

Mitsubishi Q68TD-G-H02 User manual

Mitsubishi Q Series User manual

Mitsubishi

Mitsubishi Q Series User manual

Mitsubishi AJ65BT-68TD User manual

Mitsubishi

Mitsubishi AJ65BT-68TD User manual

Mitsubishi FX2N-5A User manual

Mitsubishi

Mitsubishi FX2N-5A User manual

Mitsubishi A8GT-50KBF User manual

Mitsubishi

Mitsubishi A8GT-50KBF User manual

Mitsubishi FX2N-4AD-TC User manual

Mitsubishi

Mitsubishi FX2N-4AD-TC User manual

Mitsubishi MELESEC-ST User manual

Mitsubishi

Mitsubishi MELESEC-ST User manual

Mitsubishi CL1Y2-T1D2S User manual

Mitsubishi

Mitsubishi CL1Y2-T1D2S User manual

Mitsubishi CL2XY16-DTP1C5V User manual

Mitsubishi

Mitsubishi CL2XY16-DTP1C5V User manual

Mitsubishi FX2N-10PG User manual

Mitsubishi

Mitsubishi FX2N-10PG User manual

Mitsubishi AJ65BT-64RD3 User manual

Mitsubishi

Mitsubishi AJ65BT-64RD3 User manual

Mitsubishi CL1XY4-DT1B2 User manual

Mitsubishi

Mitsubishi CL1XY4-DT1B2 User manual

Mitsubishi CL1XY2-DTE1D5S User manual

Mitsubishi

Mitsubishi CL1XY2-DTE1D5S User manual

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Popular I/O System manuals by other brands

Weidmuller UR67 Series manual

Weidmuller

Weidmuller UR67 Series manual

M-system R7 Series instruction manual

M-system

M-system R7 Series instruction manual

FA goods FA-TB32XYP3 user manual

FA goods

FA goods FA-TB32XYP3 user manual

Kernel DLC 1200SG user manual

Kernel

Kernel DLC 1200SG user manual

Keysight Technologies VXI bus 75000 C Series Configuration and user's guide

Keysight Technologies

Keysight Technologies VXI bus 75000 C Series Configuration and user's guide

Galletti EVO quick start guide

Galletti

Galletti EVO quick start guide

DAQ system PCI-DIO64 Series user manual

DAQ system

DAQ system PCI-DIO64 Series user manual

WAGO 750-585 manual

WAGO

WAGO 750-585 manual

WAGO 750-871 manual

WAGO

WAGO 750-871 manual

CTI 2550-A Installation and operation guide

CTI

CTI 2550-A Installation and operation guide

Pilz PSS u2 ES 8DOD 0.5A operating manual

Pilz

Pilz PSS u2 ES 8DOD 0.5A operating manual

Cognex In-Sight CIO-MICRO manual

Cognex

Cognex In-Sight CIO-MICRO manual

Tews Technologies TPCE636 user manual

Tews Technologies

Tews Technologies TPCE636 user manual

Acces I/O products PCIE-ADIO16-16F Hardware manual

Acces I/O products

Acces I/O products PCIE-ADIO16-16F Hardware manual

Bristol Babcock ControlWave BB-8DI2-8DO2-H instruction manual

Bristol Babcock

Bristol Babcock ControlWave BB-8DI2-8DO2-H instruction manual

Bosch Rexroth IndraControl S20 manual

Bosch

Bosch Rexroth IndraControl S20 manual

Autonics ARD-D Series manual

Autonics

Autonics ARD-D Series manual

YASKAWA VIPA SLIO SDI operating manual

YASKAWA

YASKAWA VIPA SLIO SDI operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.