SMS command input type input 3: <CODE> TYPEIN3:xx
The input types IN1 and IN2 define the character of the additional inputs IN1 and IN2. This can be
Normally Open (NO) or Normally Closed (NC). In case an input is set to NO, the alarm will be
triggered as soon as the terminals of the input are closed. If the input is set to NC, the alarm is
triggered in case the connection between the input terminals is broken. The default input type is
set to NO.
SMS command input type input 1: <CODE> TYPEIN1:xx
SMS command input type input 2: <CODE> TYPEIN2:xx
4.4.6 Input delay time
The input delay time defines the time that the input are triggered before an alarm is initiated. If the
input returns to the non-alarm status within the delay time, no alarm is sent. The time can be set
between 0 and 999 seconds.
As default, the input delay time is set to 1 second.
SMS command alarm delay input 1: <CODE> DELAY1:xxx
SMS command alarm delay input 2: <CODE> DELAY2:xxx
SMS command alarm delay water sensor: <CODE> DELAY3:xxx
4.4.7 Inactive time
The “inactive time” defines the time input 1 or input 2 is not active after an activation. In case the
time is set to “0” (minutes), the input is active again immediately after returning to the non-alarm
status. In case the time is set to e.g. 30 minutes, the input remains inactive for the first 30
minutes. In case the input is again (or still) activated after these 30 minutes, a new alarm
message is sent. The time can be set between 0 and 60 minutes. As default, the inactive time is
set to “0”.
SMS command inactive time input 1: <CODE> INACTIVEIN1:xx
SMS command inactive time input 2: <CODE> INACTIVEIN2:xx
SMS command inactive time Water sensor: <CODE> INACTIVEIN3:xx
4.4.8 Alarm repeat time
In order to emphasize the urgency of the alarm messages, all alarms can be repeated. As long as
the alarm status has not returned to the inactive status, the SMS alarm will be repeated after the
‘alarm repeat time’. The time can be set between 0 and 24 hours. As default the alarm repeat
time is set to 4 hour.
SMS command alarm repeat time: <CODE> REPEAT:xx
4.4.9 Test SMS text message
The Mobeye WaterGuard can send regular test SMS messages (´keep alive’) to the
administrator, to ensure the proper functioning of the unit. The test message function is only
active in case the unit is armed.
The interval between the test messages can be set between 0 days (no test message) and 30
days. The default test interval is set to 0 (no test message).
SMS command interval test message: <CODE> TEST:xx
4.4.10 Power failure SMS message
In case the Mobeye WaterGuard is powered externally and the power fails it sends an SMS text
message to the administrator. The message is only sent in case the unit is armed. This message
can be set to ‘OFF’. The default setting for the ‘power failure SMS text message’ is set to “ON”.
SMS command power failure message: <CODE> POWERSMS:xx